SIMATIC S7-300, CPU 317F-2DP, CENTRAL PROCESSING UNIT WITH 1024 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, MICRO MEMORY CARD NECESSARY FOR USE WITH SOFTWARE OPTION S7 DISTRIBUTED SAFETY V5.2 SP1 AND HIGHER |
|
General information |
Hardware product version |
01 |
Firmware version |
V2.6 |
Engineering with |
Programming package |
STEP 7 V5.2 SP1 or higher with hardware update; S7 Distributed Safety V5.2 SP1 or higher |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
external protection for power supply lines (recommendation) |
2 A min. |
Input current |
Current consumption (in no-load operation), typ. |
100 mA |
Inrush current, typ. |
2.5 A |
I²t |
1 A²·s |
Power loss |
Power loss, typ. |
4 W |
Memory |
Type of memory |
other |
Work memory |
integrated |
1024 kbyte |
expandable |
No |
Load memory |
Plug-in (MMC) |
Yes |
Plug-in (MMC), max. |
8 Mbyte |
Data management on MMC (after last programming), min. |
10 a |
Backup |
present |
Yes; Guaranteed by MMC (maintenance-free) |
without battery |
Yes; Program and data |
CPU processing times |
for bit operations, typ. |
0.05 µs |
for bit operations, max. |
0.05 µs |
for word operations, typ. |
0.2 µs |
for fixed point arithmetic, typ. |
0.2 µs |
for floating point arithmetic, typ. |
1 µs |
CPU-blocks |
Number of blocks (total) |
2048; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB |
Number, max. |
2047; Number band: 1 to 2047 |
Size, max. |
64 kbyte |
FB |
Number, max. |
2048; Number range: 0 to 2047 |
Size, max. |
64 kbyte |
FC |
Number, max. |
2048; Number range: 0 to 2047 |
Size, max. |
64 kbyte |
OB |
Description |
see instruction list |
Size, max. |
64 kbyte |
Number of free cycle OBs |
1; OB 1 |
Number of time alarm OBs |
1; OB 10 |
Number of delay alarm OBs |
2; OB 20, 21 |
Number of time interrupt OBs |
4; OB 32, 33, 34, 35 |
Number of process alarm OBs |
1; OB 40 |
Number of DPV1 alarm OBs |
3; OB 55, 56, 57 |
Number of isochronous mode OBs |
1; OB 61 |
Number of startup OBs |
1; OB 100 |
Number of asynchronous error OBs |
5; OB 80, 82, 85, 86, 87 |
Number of synchronous error OBs |
2; OB 121, 122 |
Nesting depth |
per priority class |
16 |
additional within an error OB |
4 |
Counters, timers and their retentivity |
S7 counter |
Number |
512 |
of which retentive without battery |
adjustable |
Yes |
preset |
8 |
Retentivity |
adjustable |
Yes |
lower limit |
0 |
upper limit |
511 |
preset |
8 |
Counting range |
adjustable |
Yes |
lower limit |
0 |
upper limit |
999 |
IEC counter |
present |
Yes |
Type |
SFB |
Number |
Unlimited (limited only by RAM capacity) |
S7 times |
Number |
512 |
of which retentive without battery |
adjustable |
Yes |
lower limit |
0 |
upper limit |
511 |
Retentivity |
adjustable |
Yes |
lower limit |
0 |
upper limit |
511 |
preset |
No retentivity |
Time range |
lower limit |
10 ms |
upper limit |
9990 s |
IEC timer |
present |
Yes |
Type |
SFB |
Number |
Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area, total |
All, max. 256 KB |
Flag |
Number, max. |
4096 byte |
Retentivity available |
Yes; From MB 0 to MB 4095 |
Retentivity preset |
MB 0 to MB 15 |
Number of clock memories |
8; 1 memory byte |
Data blocks |
Number, max. |
2047; from DB 1 to DB 2047 |
Size, max. |
64 kbyte |
Retentivity adjustable |
Yes; via non-retain property on DB |
Retentivity preset |
Yes |
Local data |
per priority class, max. |
1024 byte |
Address area |
I/O address area |
Inputs |
8 kbyte |
Outputs |
8 kbyte |
of which distributed |
Inputs |
8 kbyte |
Outputs |
8 kbyte |
Process image |
Inputs |
1024 byte |
Outputs |
1024 byte |
Digital channels |
Inputs |
65536 |
Outputs |
65536 |
Inputs, of which central |
1024 |
Outputs, of which central |
1024 |
Analog channels |
Inputs |
4096 |
Outputs |
4096 |
Inputs, of which central |
256 |
Outputs, of which central |
256 |
Hardware configuration |
Expansion devices, max. |
3 |
Number of DP masters |
integrated |
2 |
via CP |
4 |
Number of operable FMs and CPs (recommended) |
FM |
8 |
CP, point-to-point |
8 |
CP, LAN |
10 |
Rack |
Racks, max. |
4 |
Modules per rack, max. |
8 |
Time of day |
Clock |
Hardware clock (real-time clock) |
Yes |
battery-backed and synchronizable |
Yes |
Deviation per day, max. |
10 s |
Backup time |
6 wk; At 40 °C ambient temperature |
Operating hours counter |
Number |
4 |
Number/Number range |
0 to 3 |
Range of values |
0 to 2^31 hours (when using SFC 101) |
Granularity |
1 hour |
retentive |
Yes; Must be restarted at each restart |
Clock synchronization |
supported |
Yes |
to MPI, master |
Yes |
to MPI, slave |
Yes |
to DP, master |
Yes; With DP slave only slave clock |
to DP, slave |
Yes |
in AS, master |
Yes |
in AS, slave |
Yes |
Digital inputs |
integrated channels (DI) |
0 |
Digital outputs |
integrated channels (DO) |
0 |
Analog inputs |
integrated channels (AI) |
0 |
Analog outputs |
integrated channels (AO) |
0 |
Interfaces |
Number of parallel interfaces |
0 |
Number of 20 mA interfaces (TTY) |
0 |
Number of RS 232 interfaces |
0 |
Number of RS 422 interfaces |
0 |
Number of other interfaces |
0 |
1. Interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
isolated |
Yes |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Functionality |
MPI |
Yes |
DP master |
Yes |
DP slave |
Yes |
Point-to-point connection |
No |
MPI |
Number of connections |
32 |
Transmission rate, max. |
12 Mbit/s |
Services |
PG/OP communication |
Yes |
Routing |
Yes |
Global data communication |
Yes |
S7 basic communication |
Yes |
S7 communication |
Yes |
S7 communication, as client |
No |
S7 communication, as server |
Yes |
DP master |
Transmission rate, max. |
12 Mbit/s |
Number of DP slaves, max. |
124 |
Services |
PG/OP communication |
Yes |
Routing |
Yes |
Global data communication |
No |
S7 basic communication |
Yes |
S7 communication |
Yes |
S7 communication, as client |
No |
S7 communication, as server |
Yes |
Equidistance mode support |
Yes |
Isochronous mode |
No |
SYNC/FREEZE |
Yes |
Activation/deactivation of DP slaves |
Yes |
DPV1 |
Yes |
Address area |
Inputs, max. |
244 byte |
Outputs, max. |
244 byte |
DP slave |
Transmission rate, max. |
12 Mbit/s |
Automatic baud rate search |
Yes; only with passive interface |
Address area, max. |
32 |
User data per address area, max. |
32 byte |
Services |
Routing |
Yes; Only with active interface |
Global data communication |
No |
S7 basic communication |
Yes |
S7 communication |
Yes |
S7 communication, as client |
No |
S7 communication, as server |
Yes |
Direct data exchange (slave-to-slave communication) |
Yes |
DPV1 |
No |
Transfer memory |
Inputs |
244 byte |
Outputs |
244 byte |
2. Interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
isolated |
Yes |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Functionality |
MPI |
No |
DP master |
Yes |
DP slave |
Yes |
Point-to-point connection |
No |
DP master |
Number of connections, max. |
32 |
Transmission rate, max. |
12 Mbit/s |
Number of DP slaves, max. |
124 |
Services |
PG/OP communication |
Yes |
Routing |
Yes |
Global data communication |
No |
S7 basic communication |
Yes |
S7 communication |
Yes |
S7 communication, as client |
No |
S7 communication, as server |
Yes |
Equidistance mode support |
Yes |
Isochronous mode |
Yes; OB 61 |
SYNC/FREEZE |
Yes |
Activation/deactivation of DP slaves |
Yes |
DPV1 |
Yes |
Address area |
Inputs, max. |
244 byte |
Outputs, max. |
244 byte |
DP slave |
Number of connections |
32 |
GSD file |
The latest GSD file is available at: http://www.siemens.com/profibus-gsd |
Transmission rate, max. |
12 Mbit/s |
Automatic baud rate search |
Yes; only with passive interface |
Address area, max. |
32 |
User data per address area, max. |
32 byte |
Services |
PG/OP communication |
Yes |
Routing |
Yes; with interface active |
Global data communication |
No |
S7 basic communication |
Yes |
S7 communication |
Yes |
S7 communication, as client |
No |
S7 communication, as server |
Yes |
Direct data exchange (slave-to-slave communication) |
Yes |
DPV1 |
No |
Transfer memory |
Inputs |
244 byte |
Outputs |
244 byte |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
supported |
Yes |
Number of GD loops, max. |
8 |
Number of GD packets, max. |
8 |
Number of GD packets, transmitter, max. |
8 |
Number of GD packets, receiver, max. |
8 |
Size of GD packets, max. |
22 byte |
Size of GD packet (of which consistent), max. |
22 byte |
S7 basic communication |
supported |
Yes |
User data per job, max. |
76 byte |
User data per job (of which consistent), max. |
76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
supported |
Yes |
as server |
Yes |
as client |
Yes; Via CP and loadable FB |
User data per job, max. |
180 byte; With PUT/GET |
User data per job (of which consistent), max. |
160 byte; as server |
S5 compatible communication |
supported |
Yes; via CP and loadable FC |
Number of connections |
overall |
32 |
usable for PG communication |
31 |
reserved for PG communication |
1 |
adjustable for PG communication, min. |
1 |
adjustable for PG communication, max. |
31 |
usable for OP communication |
31 |
reserved for OP communication |
1 |
adjustable for OP communication, min. |
1 |
adjustable for OP communication, max. |
31 |
usable for S7 basic communication |
30 |
reserved for S7 basic communication |
0 |
adjustable for S7 basic communication, min. |
0 |
adjustable for S7 basic communication, max. |
30 |
usable for routing |
8 |
S7 message functions |
Number of login stations for message functions, max. |
32; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages |
Yes |
simultaneously active Alarm-S blocks, max. |
60 |
Test commissioning functions |
Status block |
Yes |
Single step |
Yes |
Number of breakpoints |
2 |
Status/control |
Status/control variable |
Yes |
Variables |
Inputs, outputs, memory bits, DB, times, counters |
Number of variables, max. |
30 |
of which status variables, max. |
30 |
of which control variables, max. |
14 |
Forcing |
Forcing |
Yes |
Forcing, variables |
Inputs, outputs |
Number of variables, max. |
10 |
Diagnostic buffer |
present |
Yes |
Number of entries, max. |
100 |
adjustable |
No |
Configuration |
Configuration software |
STEP 7 |
Yes; V5.2 SP1 or higher |
Programming |
Command set |
see instruction list |
Nesting levels |
8 |
System functions (SFC) |
see instruction list |
System function blocks (SFB) |
see instruction list |
Programming language |
LAD |
Yes |
FBD |
Yes |
STL |
Yes |
SCL |
Yes |
CFC |
Yes |
GRAPH |
Yes |
HiGraph® |
Yes |
Know-how protection |
User program protection/password protection |
Yes |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
130 mm |
Weights |
Weight, approx. |
460 g |
Status |
Jul 5, 2014 |