SIMATIC S7-300, DIGITAL OUTPUT SM 322, OPTICALLY ISOLATED 16 DO, 120/230V AC, 1 A, 1 X 20 PIN |
Supply voltage |
Load voltage L1 |
● Rated value (AC) |
230 V; 120/230 V AC |
● permissible range, lower limit (AC) |
79 V |
● permissible range, upper limit (AC) |
264 V |
Input current |
from load voltage L+ (without load), max. |
2 mA |
from load voltage L1 (without load), max. |
3 mA |
from backplane bus 5 V DC, max. |
200 mA |
Power losses |
Power loss, typ. |
8.6 W |
Digital outputs |
Number of digital outputs |
16 |
Switching capacity of the outputs |
● Lamp load, max. |
50 W |
Output current |
● for signal "1" rated value |
1 A |
● for signal "1" permissible range for 0 to 40 °C, max. |
1 A |
● for signal "1" minimum load current |
10 mA |
● for signal "1" permissible surge current, max. |
20 A; with 2 half waves |
● for signal "0" residual current, max. |
2 mA |
Switching frequency |
● with resistive load, max. |
10 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
1 Hz |
Aggregate current of outputs (per group) |
horizontal installation |
— up to 40 °C, max. |
4 A |
— up to 60 °C, max. |
2 A |
vertical installation |
— up to 40 °C, max. |
2 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
No |
Diagnostic messages |
● Diagnostics |
Yes |
● Wire break |
No |
● Short circuit |
No |
● Fuse blown |
Yes |
● Missing load voltage |
No |
Diagnostics indication LED |
● Rated load voltage PWR (green) |
No |
● Fuse OK FSG (green) |
Yes; Red LED for fuse |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels, in groups of |
8 |
● between the channels and the backplane bus |
Yes; Optocoupler |
Isolation |
Isolation checked with |
4000 VDC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
275 g |
last modified: |