SIMATIC S7-300, DIGITAL OUTPUT SM 322, OPTICALLY ISOLATED, 32 DO, AC 120V/230V, 1A, DOUBLE WIDTH HOUSING, 2 X 20 PIN |
Supply voltage |
Load voltage L1 |
● Rated value (AC) |
120 V; 120/230 V AC |
● permissible range, lower limit (AC) |
79 V |
● permissible range, upper limit (AC) |
264 V |
Input current |
from load voltage L1 (without load), max. |
10 mA |
from backplane bus 5 V DC, max. |
190 mA |
Power losses |
Power loss, typ. |
25 W |
Digital outputs |
Number of digital outputs |
32 |
Switching capacity of the outputs |
● Lamp load, max. |
50 W |
Output voltage |
● for signal "1", min. |
L1 (-0.8 V) |
Output current |
● for signal "1" rated value |
1 A |
● for signal "1" permissible range for 0 to 40 °C, max. |
1 A |
● for signal "1" minimum load current |
10 mA |
● for signal "1" permissible surge current, max. |
10 A; per group (for 2 AC cycles) |
● for signal "0" residual current, max. |
2 mA |
Switching frequency |
● with resistive load, max. |
10 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
1 Hz |
Aggregate current of outputs (per group) |
horizontal installation |
— up to 40 °C, max. |
4 A |
— up to 60 °C, max. |
3 A |
vertical installation |
— up to 40 °C, max. |
4 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
No |
Diagnostic messages |
● Diagnostics |
Yes |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels, in groups of |
8 |
● between the channels and the backplane bus |
Yes; Optocoupler |
Isolation |
Isolation checked with |
4000 VDC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
117 mm |
Weights |
Weight, approx. |
500 g |
last modified: |
25.09.2014 |