SIMATIC S7/PCS7, SM 321 DIGITAL INPUT MODULE, 16 DI, 24V DC, 1 X 40 PIN, CAPABLE OF DIAGNOSTICS, FOR CONTACTS (CONNECTED/ UNCONNECTED), NAMUR SENSOR, 3/4-WIRE-BERO, WITH FLUTTER MONITORING, PULSE LENGTHENING, WIRE BREAK DETECTION, IM153-2 INTERFACE MOD. REQUIRED |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
Input current |
from load voltage L+ (without load), max. |
100 mA |
from backplane bus 5 V DC, max. |
100 mA |
from supply voltage L+, max. |
4 A |
Power losses |
Power loss, typ. |
11 W |
Time stamping |
Time stamping, supported |
Yes |
Accuracy |
1 ms |
Digital inputs |
Number of digital inputs |
16 |
Input characteristic curve in accordance with IEC 61131, type 1 |
No |
Input characteristic curve in accordance with IEC 61131, type 2 |
Yes |
Number of simultaneously controllable inputs |
horizontal installation |
— up to 60 °C, max. |
16 |
vertical installation |
— up to 40 °C, max. |
16 |
Input voltage |
● Type of input voltage |
DC |
● Rated value, DC |
8.2 V; 8.2V/18V |
Input current |
● for signal "1", typ. |
10 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", min. |
2.5 ms |
— at "0" to "1", max. |
3.5 ms |
Cable length |
● Cable length, shielded, max. |
400 m; max. 200m with 8.2 V sensor, max. 400m with 18 V sensor |
● Cable length unshielded, max. |
Not permitted |
Interrupts/diagnostics/status information |
Alarms |
● Alarms |
Yes |
● Diagnostic alarm |
Yes |
● Hardware interrupt |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostics |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
● Status indicator digital input (green) |
Yes |
Galvanic isolation |
Galvanic isolation digital inputs |
● between the channels |
Yes |
● between the channels, in groups of |
8 |
● between the channels and the backplane bus |
Yes |
Permissible potential difference |
between different circuits |
75 VDC / 60 VAC |
Isolation |
Isolation checked with |
600 V DC |
Ambient conditions |
Operating temperature |
● Min. |
0 °C |
● max. |
60 °C |
Extended ambient conditions |
● at cold restart, minimum |
0 °C |
Connection method |
required front connector |
1x 40-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
last modified: |
08.09.2014 |