General information |
Hardware product version |
02 |
Firmware version |
V2.3.0 |
Engineering with |
● Programming package |
STEP 7 V5.3 or higher |
Supply voltage |
external protection for power supply lines (recommendation) |
2 A min. |
Memory |
Backup |
● present |
Guaranteed by MMC (maintenance-free) |
● without battery |
Program and data |
CPU-blocks |
Number of blocks (total) |
(DBs, FCs, FBs OBs, SDBs); the maximum number of loadable blocks can be reduced by the MMC being used. |
DB |
● Number, max. |
Number band: 1 to 2047 |
FB |
● Number, max. |
Number range: 0 to 2047 |
FC |
● Number, max. |
Number range: 0 to 2047 |
OB |
● Number, max. |
see instruction list |
● Number of free cycle OBs |
OB 1 |
● Number of time alarm OBs |
OB 10 |
● Number of delay alarm OBs |
OB 20, 21 |
● Number of time interrupt OBs |
OB 32, 33, 34, 35 |
● Number of process alarm OBs |
OB 40 |
● Number of startup OBs |
OB 100 |
● Number of asynchronous error OBs |
OB 80 |
● Number of synchronous error OBs |
OB 121, 122 |
Counters, timers and their retentivity |
S7 counter |
of which retentive without battery |
— preset |
Z 0 to Z 7 |
IEC counter |
● Type |
SFB |
● Number |
Unlimited (limited only by RAM capacity) |
S7 times |
Retentivity |
— preset |
No retentivity |
IEC timer |
● Type |
SFB |
● Number |
Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area, total |
All, max. 256 KB |
Flag |
● Retentivity available |
From MB 0 to MB 4095 |
● Retentivity preset |
MB 0 to MB 15 |
● Number of clock memories |
1 memory byte |
Data blocks |
● Number, max. |
from DB 1 to DB 2047 |
● Retentivity adjustable |
via non-retain property on DB |
● Retentivity preset |
Yes |
Time of day |
Clock |
● Backup time |
At 40 °C ambient temperature |
Operating hours counter |
● Number/Number range |
0 to 3 |
● Range of values |
0 to 2^31 hours (when using SFC 101) |
● Granularity |
1 hour |
● retentive |
Must be restarted at each restart |
1. Interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
DP slave |
● automatic baud rate search |
only with passive interface |
Services |
— Routing |
with interface active |
2. Interface |
Interface type |
PROFINET |
Physics |
RJ45 |
automatic detection of transmission rate |
10/100 Mbit/s |
Functionality |
● PROFINET IO Controller |
Firmware Status V2.3 or higher |
PROFINET IO Controller |
● Updating time |
1 to 512 ms (minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the volume of configured user data) |
Services |
— S7 communication |
with loadable FBs, max. configurable connections: 16 |
— Open IE communication |
via TCP/IP |
Communication functions |
S7 basic communication |
● User data per job (of which consistent), max. |
76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
● as client |
via integrated PROFINET interface and loadable FB or via CP and loadable FB |
● User data per job, max. |
See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) |
S5 compatible communication |
● supported |
via CP and loadable FC |
Open IE communication |
● TCP/IP |
via integrated PROFINET interface and loadable FBs |
PROFINET CBA (at set setpoint communication load) |
HMI variables via PROFINET (acyclic) |
— Number of stations that can log on for HMI variables (PN OPC/iMap) |
2x PN OPC/1x iMap |
PROFIBUS proxy functionality |
— Data length per connection, max. |
Slave-dependent |
S7 message functions |
Number of login stations for message functions, max. |
Depending on the configured connections for PG/OP and S7 basic communication |
Test commissioning functions |
Status/control |
● Variables |
Inputs, outputs, memory bits, DB, times, counters |
Forcing |
● Forcing, variables |
Inputs, outputs |
Configuration |
Configuration software |
● STEP 7 |
V5.3 or higher |
Programming |
● Command set |
see instruction list |
● System functions (SFC) |
see instruction list |
● System function blocks (SFB) |
see instruction list |
last modified: |
21.08.2014 |