SIMATIC S7-300, CPU 316-2DP CPU WITH INTEGRATED 24 V DC POWER SUPPLY, 128 KBYTE WORKING MEMORY 2ND INTERF. DP-MASTER/SLAVE |
Product type designation |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Input current |
Rated value at 24 V DC |
1 000 mA |
Inrush current, max. |
8 A |
Power losses |
Power loss, max. |
8 W |
Memory |
Work memory |
● Integrated |
128 kbyte; 128 KB / 42K instructions RAM (integrated) |
Load memory |
● expandable FEPROM |
Yes; Flash-EPROM |
● expandable FEPROM, max. |
4 Mbyte |
● integrated RAM, max. |
192 kbyte |
Backup |
● present |
Yes |
● with battery |
Yes; all blocks |
● without battery |
Yes; 4 KB: bit memory, counter, times and data |
CPU processing times |
for bit operations, typ. |
0.3 µs |
for bit operations, max. |
0.6 µs |
for word operations, typ. |
1 µs |
for fixed point arithmetic, typ. |
2 µs |
for floating point arithmetic, typ. |
50 µs |
for timer/counter operations, typ. |
12 µs |
CPU-blocks |
DB |
● Number, max. |
511 |
● Size, max. |
16 kbyte |
FB |
● Number, max. |
256 |
● Size, max. |
16 kbyte |
FC |
● Number, max. |
256 |
● Size, max. |
16 kbyte |
OB |
● Description |
see instruction list |
● Size, max. |
16 kbyte |
● Number of free cycle OBs |
1; OB 1 |
● Number of time alarm OBs |
1; OB 10 |
● Number of time interrupt OBs |
1; OB 35 |
● Number of process alarm OBs |
1; OB 40 |
● Number of startup OBs |
1; OB 100 |
Nesting depth |
● per priority class |
8 |
Counters, timers and their retentivity |
S7 counter |
● Number |
64 |
of which retentive with battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
63 |
of which retentive without battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
63 |
Counting range |
— lower limit |
1 |
— upper limit |
999 |
S7 times |
● Number |
128 |
of which retentive with battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
127 |
of which retentive without battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
127 |
Time range |
— lower limit |
10 ms |
— upper limit |
9 990 s |
Data areas and their retentivity |
Flag |
● Number, max. |
256 byte |
● Retentivity available |
Yes; MB 0 to MB 255 |
● of which retentive with battery |
0 to 2047 (M 0.0 to M 255.7, adjustable) |
● of which retentive without battery |
0 to 2047 (M 0.0 to M 255.7, adjustable) |
Address area |
I/O address area |
● Inputs |
2 kbyte |
● Outputs |
2 kbyte |
Process image |
● Inputs |
128 byte |
● Outputs |
128 byte |
Digital channels |
● Inputs |
16 384 |
● Outputs |
16 384 |
● Inputs, of which central |
1 024 |
● Outputs, of which central |
1 024 |
Analog channels |
● Inputs |
1 024 |
● Outputs |
1 024 |
● Inputs, of which central |
256 |
● Outputs, of which central |
128 |
Hardware configuration |
Number of modules per DP slave interface, max. |
64 |
Expansion devices, max. |
3 |
Connectable programming devices/PCs |
PGs/PCs with STEP 7 connectable via MPI interface |
Number of DP masters |
● Integrated |
1 |
● Via CP |
1; CP 342-5 |
Number of operable FMs and CPs (recommended) |
● FM |
8 |
● CP, point-to-point |
4 |
● CP, LAN |
2 |
Rack |
● Modules per rack, max. |
32 |
Time of day |
Clock |
● Hardware clock (real-time clock) |
Yes |
Interfaces |
MPI |
● Cable length, max. |
9 100 m; without repeaters: 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with 16 star hubs or OLMs) |
1st interface |
Functionality |
● MPI |
Yes |
MPI |
● Number of nodes, max. |
32 |
● Transmission rate, min. |
19.2 kbit/s |
● Transmission rate, max. |
187.5 kbit/s |
Services |
— PG/OP communication |
Yes |
— Global data communication |
Yes |
— S7 basic communication |
Yes |
— S7 communication |
Yes |
2nd interface |
Functionality |
● DP master |
Yes |
● DP slave |
Yes |
DP master |
● Number of DP slaves, max. |
124 |
Services |
— Equidistance mode support |
Yes |
— Activation/deactivation of DP slaves |
Yes |
— Direct data exchange (slave-to-slave communication) |
Yes; Transmitter and receiver |
User data per DP slave |
— User data per DP slave, max. |
244 byte |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
● supported |
Yes |
S7 basic communication |
● supported |
Yes |
S7 communication |
● supported |
Yes |
● as server |
Yes |
S5-compatible communication |
● supported |
Yes; via loadable blocks |
Standard communication (FMS) |
● supported |
Yes; via loadable blocks |
Number of connections |
● overall |
|
— of which dynamic |
8 |
— of which static |
4 |
Configuration |
Configuration software |
● STEP 7 |
Yes; V5.0 |
programming |
● Command set |
Binary logic operations, bracketed operations, result allocation, saving, counting, loading, transferring, comparing, shifting, rotating, complementation, calling blocks, fixed point arithmetic, floating point arithmetic, jump functions |
● Nesting levels |
8 |
● Program organization |
Linear, structured |
● System functions (SFC) |
Interrupt and error processing, copy data, clock functions, diagnostic functions, module parameterization, operating mode transitions |
Programming language |
— LAD |
Yes |
— FBD |
Yes |
— STL |
Yes |
— SCL |
Yes |
— CFC |
Yes |
— GRAPH |
Yes |
— HiGraph® |
Yes |
Software libraries |
— Process diagnostics |
Yes |
— Software controller |
Yes; depending on the required memory space and the resulting execution time |
Know-how protection |
● User program protection/password protection |
Yes |
Cycle time monitoring |
● lower limit |
1 ms |
● upper limit |
6 000 ms |
● can be set |
Yes |
● preset |
150 ms |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
130 mm |
Weights |
Weight, approx. |
530 g; Memory card 16 g |
last modified: |