SIMATIC S7-300, CPU 314 IFM COMPACT CPU WITH MPI, FOR EXPANDED TEMPERATURE RANGE, 16DI/16DO, 4AI/1AO, 2 X 40 PIN, INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
Rated value at 24 V DC |
1 000 mA |
Inrush current, max. |
8 A |
Power losses |
Power loss, typ. |
16 W |
Memory |
Work memory |
● Integrated |
32 kbyte; 32 KB/10 K instructions RAM (integrated); 1 instruction means 3 bytes on average |
Load memory |
● integrated RAM, max. |
48 kbyte |
Backup |
● with battery |
Yes; all blocks |
● without battery |
Yes; 144 bytes: Bit memories, counters, timers and data |
CPU processing times |
for bit operations, typ. |
0.3 µs |
for bit operations, max. |
0.6 µs |
for word operations, typ. |
1 µs |
for fixed point arithmetic, typ. |
2 µs |
for floating point arithmetic, typ. |
50 µs |
for timer/counter operations, typ. |
12 µs |
CPU-blocks |
DB |
● Number, max. |
127 |
● Size, max. |
8 kbyte |
FB |
● Number, max. |
128 |
● Size, max. |
8 kbyte |
FC |
● Number, max. |
128 |
● Size, max. |
8 kbyte |
OB |
● Description |
see instruction list |
● Size, max. |
8 kbyte |
● Number of free cycle OBs |
1; OB 1 |
● Number of time alarm OBs |
1; OB 10 |
● Number of time interrupt OBs |
1; OB 35 |
● Number of process alarm OBs |
1; OB 40 |
● Number of startup OBs |
1; OB 100 |
Nesting depth |
● per priority class |
8 |
Counters, timers and their retentivity |
S7 counter |
● Number |
64 |
of which retentive with battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
63 |
of which retentive without battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
63 |
Counting range |
— lower limit |
1 |
— upper limit |
999 |
S7 times |
● Number |
128 |
of which retentive with battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
71 |
of which retentive without battery |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
71 |
Time range |
— lower limit |
10 ms |
— upper limit |
9 990 s |
Data areas and their retentivity |
Flag |
● Number, max. |
256 byte |
● Retentivity available |
Yes; MB 0 to MB 255 |
● of which retentive with battery |
0 to 2047 (M 0.0 to M 255.7, adjustable) |
● of which retentive without battery |
0 to 1152 (M 0.0 toM 143.7, adjustable) |
Address area |
I/O address area |
● Inputs |
512 byte |
● Outputs |
512 byte |
Process image |
● Inputs |
128 byte |
● Outputs |
128 byte |
Digital channels |
● Inputs |
992 |
● Outputs |
992 |
Analog channels |
● Inputs |
248 |
● Outputs |
124 |
Addressing volume |
● Inputs |
122 byte |
● Outputs |
122 byte |
Address space per module |
● Address space per module, max. |
512 byte; 512 byte / 512 byte |
Hardware configuration |
Number of modules per DP slave interface, max. |
16 |
Expansion devices, max. |
3 |
Connectable programming devices/PCs |
PGs/PCs with STEP 7 connectable via MPI interface |
Number of DP masters |
● Via CP |
1; CP 342-5 |
Number of operable FMs and CPs (recommended) |
● FM |
4 |
● CP, point-to-point |
2 |
● CP, LAN |
1 |
Rack |
● Modules per rack, max. |
31 |
Time of day |
Clock |
● Hardware clock (real-time clock) |
Yes |
Digital inputs |
Number of digital inputs |
20; of which 4 channels can be used for process alarms or integrated functions |
Input voltage |
● Rated value (DC) |
24 V |
● for signal "0" |
-3 to +5V |
● for signal "1" |
15 to 30 V |
Input current |
● for signal "1", typ. |
7 mA; Min. 2 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", max. |
5 ms; typically 3 ms |
for interrupt inputs |
— at "0" to "1", max. |
50 µs |
for counter/technological functions |
— at "0" to "1", max. |
50 µs |
Cable length |
● Cable length, shielded, max. |
1 000 m; 100 m for alarm and counter inputs |
● Cable length unshielded, max. |
600 m |
Digital outputs |
Number of digital outputs |
16 |
short-circuit protection |
Yes; Clocked electronically |
Limitation of inductive shutdown voltage to |
30 V |
Output voltage |
● for signal "1", min. |
L+ (-0.8 V) |
Output current |
● for signal "1" permissible range for 0 to 40 °C, max. |
500 mA |
● for signal "1" permissible range for 40 to 60 °C, max. |
500 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
500 mA |
● for signal "1" minimum load current |
5 mA |
● for signal "0" residual current, max. |
0.5 mA |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 40 °C, max. |
4 A |
— up to 60 °C, max. |
2 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Analog inputs |
Number of analog inputs |
4 |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
Input ranges (rated values), currents |
● -20 to +20 mA |
Yes |
● Input resistance (-20 to +20 mA) |
105.5 kΩ |
Analog outputs |
Number of analog outputs |
1 |
Output ranges, voltage |
● -10 to +10 V |
Yes |
Output ranges, current |
● -20 to +20 mA |
Yes |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
12 bit |
● Conversion time (per channel) |
100 µs; for each output 400 µs, analog outputs 40 µs |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— Permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Errors/accuracies |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.9 % |
● Current, relative to input area, (+/-) |
0.9 % |
● Voltage, relative to output area, (+/-) |
0.9 % |
● Current, relative to output area, (+/-) |
0.9 % |
Interfaces |
PROFIBUS DP |
● Number of stations per segment, max. |
16 |
MPI |
● Cable length, max. |
9 100 m; Distance between 2 neighboring nodes, max. - without repeaters: 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with 16 star hubs or OLMs) |
1st interface |
Functionality |
● MPI |
Yes |
MPI |
● Number of nodes, max. |
32; 32 nodes on MPI bus; PG/PC, OP, additional S7-300/400, C7; per CPU max. 4 static and 4 dynamic connections |
● Transmission rate, max. |
187.5 kbit/s |
Services |
— PG/OP communication |
Yes |
— Global data communication |
Yes |
— S7 basic communication |
Yes |
— S7 communication |
Yes |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
● supported |
Yes |
S7 basic communication |
● supported |
Yes |
S7 communication |
● supported |
Yes |
● as server |
Yes |
S5-compatible communication |
● supported |
Yes; via loadable blocks |
Standard communication (FMS) |
● supported |
Yes; via loadable blocks |
Number of connections |
● overall |
|
— of which dynamic |
8 |
— of which static |
4 |
Integrated Functions |
Number of counters |
2; 1 counter with 4 inputs or 2 counters with 2 inputs and 2 direction-dependent comparators for each counter; counter frequency 10 kHz; 32 bit (incl. sign) |
Counter frequency (counter) max. |
10 kHz |
Frequency measurement |
Yes; 1 channel to max. 10 kHz; measurement times 0.1 s, 1 s, 10 s; meas. procedure: calculation of pulse number per meas. time |
controlled positioning |
Yes; 1 channel; position detection via a 24 V asymmetrical incremental encoder; 3 digital inputs are occupied by the encoder (track A, track B, reference point); simple evaluation of the counting pulses (10 kHz) |
PID controller |
Yes; PID closed-loop control function blocks: Continuous controller outputs, binary controller outputs, automatic/manual mode, setpoint limitation |
Galvanic isolation |
Galvanic isolation digital inputs |
● between the channels, in groups of |
16; Special inputs in groups of 4, inputs in groups of 16 |
● between the channels and the backplane bus |
Yes |
Galvanic isolation digital outputs |
● between the channels, in groups of |
8 |
● between the channels and the backplane bus |
Yes |
Galvanic isolation analog inputs |
● between the channels, in groups of |
4 |
● between the channels and the backplane bus |
Yes |
Galvanic isolation analog outputs |
● between the channels, in groups of |
1 |
● between the channels and the backplane bus |
Yes |
Ambient conditions |
Operating temperature |
● Min. |
-25 °C |
● max. |
60 °C |
Configuration |
Configuration software |
● STEP 7 |
Yes; V5.0 SP1 |
programming |
● Command set |
Binary logic operations, bracketed operations, result allocation, saving, counting, loading, transferring, comparing, shifting, rotating, complementation, calling blocks, fixed point arithmetic, floating point arithmetic, jump functions |
● Nesting levels |
8 |
● Program processing |
free cycle (OB 1), time-controlled (OB 35), clock-time controlled (OB 10), interrupt controlled (OB 40), startup (OB 100) |
● Program organization |
Linear, structured |
● System functions (SFC) |
Interrupt and error processing, copy data, clock functions, diagnostic functions, module parameterization, operating mode transitions |
Programming language |
— SCL |
Yes |
— GRAPH |
Yes |
Software libraries |
— Process diagnostics |
Yes |
— Software controller |
Yes; depending on the required memory space and the resulting execution time |
Know-how protection |
● User program protection/password protection |
Yes |
Cycle time monitoring |
● lower limit |
1 ms |
● upper limit |
6 000 ms |
● can be set |
Yes |
● preset |
150 ms |
Dimensions |
Width |
160 mm |
Height |
125 mm |
Depth |
130 mm |
Weights |
Weight, approx. |
900 g |
last modified: |
13.10.2014 |