SIMATIC S7-300, CPU 313C-2 PTP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED INTERFACE RS485, INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD REQUIRED |
|
General information |
Hardware product version |
01 |
Firmware version |
V2.0.0 |
Engineering with |
Programming package |
STEP 7 V5.2 SP1 or higher (with STEP 7 V5.1 SP3 or higher, please use predecessor CPU) |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Load voltage L+ |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Input current |
Current consumption (in no-load operation), typ. |
100 mA |
Inrush current, typ. |
11 A |
from supply voltage L+, max. |
700 mA |
Power loss |
Power loss, typ. |
10 W |
Memory |
Work memory |
integrated |
32 kbyte; For program and data |
expandable |
No |
Load memory |
Plug-in (MMC) |
Yes |
Plug-in (MMC), max. |
8 Mbyte |
Data management on MMC (after last programming), min. |
10 a |
Backup |
present |
Yes; Guaranteed by MMC (maintenance-free) |
without battery |
Yes; Program and data |
CPU processing times |
for bit operations, typ. |
0.1 µs |
for bit operations, max. |
0.2 µs |
for word operations, typ. |
0.2 µs |
for fixed point arithmetic, typ. |
2 µs |
for floating point arithmetic, typ. |
3 µs |
CPU-blocks |
Number of blocks (total) |
1024; (DBs, FCs, FBs OBs, SDBs); the maximum number of loadable blocks can be reduced by the MMC being used. |
DB |
Number, max. |
511; Number range: 1 to 511 |
Size, max. |
16 kbyte |
FB |
Number, max. |
512; Number range: 0 to 2047 |
Size, max. |
16 kbyte |
FC |
Number, max. |
512; Number range: 0 to 2047 |
Size, max. |
16 kbyte |
OB |
Number, max. |
see instruction list |
Size, max. |
16 kbyte |
Number of free cycle OBs |
1; OB 1 |
Number of time alarm OBs |
1; OB 10 |
Number of delay alarm OBs |
1; OB 20 |
Number of time interrupt OBs |
1; OB 35 |
Number of process alarm OBs |
1; OB 40 |
Number of startup OBs |
1; OB 100 |
Number of asynchronous error OBs |
1; OB 80 |
Number of synchronous error OBs |
2; OB 121, 122 |
Nesting depth |
per priority class |
8 |
additional within an error OB |
4 |
Counters, timers and their retentivity |
S7 counter |
Number |
256 |
of which retentive without battery |
adjustable |
Yes |
lower limit |
0 |
upper limit |
256 |
Counting range |
lower limit |
0 |
upper limit |
999 |
IEC counter |
present |
Yes |
Type |
SFB |
Number |
Unlimited (limited only by RAM capacity) |
S7 times |
Number |
256 |
Retentivity |
adjustable |
Yes |
lower limit |
0 |
upper limit |
256 |
preset |
No retentivity |
Time range |
lower limit |
10 ms |
upper limit |
9990 s |
IEC timer |
present |
Yes |
Type |
SFB |
Number |
Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area, total |
all |
Flag |
Number, max. |
256 byte |
Retentivity available |
Yes; MB 0 to MB 255 |
Retentivity preset |
MB 0 to MB 15 |
Number of clock memories |
8; 1 memory byte |
Data blocks |
Number, max. |
511; from DB1 to DB511 |
Size, max. |
16 kbyte |
Retentivity adjustable |
No |
Retentivity preset |
Yes |
Local data |
per priority class, max. |
510 byte |
Address area |
I/O address area |
Inputs |
1 kbyte |
Outputs |
1 kbyte |
Process image |
Inputs |
128 byte |
Outputs |
128 byte |
Default addresses of the integrated channels |
Digital inputs |
124.0 to 125.7 |
Digital outputs |
124.0 to 125.7 |
Digital channels |
Inputs |
1008 |
Outputs |
1008 |
Inputs, of which central |
992 |
Outputs, of which central |
992 |
Analog channels |
Inputs |
248 |
Outputs |
124 |
Inputs, of which central |
248 |
Outputs, of which central |
248 |
Hardware configuration |
Expansion devices, max. |
3 |
Number of DP masters |
integrated |
No |
via CP |
4 |
Number of operable FMs and CPs (recommended) |
FM |
8 |
CP, point-to-point |
8 |
CP, LAN |
6 |
Rack |
Racks, max. |
4 |
Modules per rack, max. |
8; In rack 3 max. 7 |
Time of day |
Clock |
Hardware clock (real-time clock) |
Yes |
battery-backed and synchronizable |
Yes |
Deviation per day, max. |
10 s |
Backup time |
6 wk; At 40 °C ambient temperature |
Operating hours counter |
Number |
1 |
Number/Number range |
0 |
Range of values |
0 to 2^31 hours (when using SFC 101) |
Granularity |
1 hour |
retentive |
Yes; Must be restarted at each restart |
Clock synchronization |
supported |
Yes |
to MPI, master |
Yes |
to MPI, slave |
Yes |
in AS, master |
Yes |
Digital inputs |
Number of digital inputs |
16 |
integrated channels (DI) |
16 |
Input voltage |
Rated value, DC |
24 V |
for signal "0" |
-3 to +5 V |
for signal "1" |
15 to 30 V |
Input current |
for signal "1", typ. |
8 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
parameterizable |
Yes; 0.1 / 0.3 / 3 / 15 ms |
for counter/technological functions |
at "0" to "1", max. |
8 µs |
Cable length |
Cable length, shielded, max. |
1000 m; 100 m for technological functions |
Cable length unshielded, max. |
600 m |
Digital outputs |
Number of digital outputs |
16 |
integrated channels (DO) |
16 |
Short-circuit protection |
Yes; Clocked electronically |
Limitation of inductive shutdown voltage to |
L+ (-48 V) |
Output voltage |
for signal "1", min. |
L+ (-0.8 V) |
Output current |
for signal "1" permissible range for 0 to 40 °C, max. |
500 mA |
for signal "1" permissible range for 0 to 60 °C, max. |
500 mA |
for signal "1" minimum load current |
5 mA |
for signal "0" residual current, max. |
0.5 mA |
Switching frequency |
with resistive load, max. |
100 Hz |
with inductive load, max. |
0.5 Hz |
Total current of the outputs (per group) |
all mounting positions |
up to 40 °C, max. |
8 A |
up to 60 °C, max. |
4 A |
Cable length |
Cable length, shielded, max. |
1000 m |
Cable length unshielded, max. |
600 m |
Analog inputs |
integrated channels (AI) |
none |
Encoder |
Connectable encoders |
2-wire sensor |
Yes |
permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Interfaces |
MPI |
Cable length, max. |
50 m; without repeater |
Point-to-point |
Cable length, max. |
1200 m |
Integrated protocol driver |
3964 (R) |
Yes |
ASCII |
Yes |
Transmission rate, RS 422/485 |
with 3964 (R) protocol, max. |
19.2 kbit/s |
with ASCII protocol, max. |
19.2 kbit/s |
1. Interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
isolated |
No |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Functionality |
MPI |
Yes |
DP master |
No |
DP slave |
No |
Point-to-point connection |
No |
MPI |
Number of connections |
8 |
Transmission rate, max. |
187.5 kbit/s |
Services |
PG/OP communication |
Yes |
Routing |
No |
Global data communication |
Yes |
S7 basic communication |
Yes |
S7 communication |
Yes |
S7 communication, as client |
No |
S7 communication, as server |
Yes |
2. Interface |
Interface type |
Integrated RS 422/ 485 interface |
Physics |
RS 422/RS 485 (X.27) |
isolated |
Yes |
Power supply to interface (15 to 30 V DC), max. |
No |
Number of connection resources |
none |
Functionality |
MPI |
No |
DP master |
No |
DP slave |
No |
Point-to-point connection |
Yes |
DP master |
Transmission rate, max. |
- |
Number of DP slaves, max. |
- |
DP slave |
Number of connections |
- |
GSD file |
- |
Transmission rate, max. |
- |
Point-to-point connection |
Transmission rate, max. |
38.4 kbit/s half duplex; 19.2 kbit/s full duplex |
Cable length, max. |
1200 m |
Interface from the user program controllable |
Yes |
Interface can trigger alarm/interrupt in the user program |
Yes; Message on break - identification |
Protocol driver |
3964 (R); ASCII |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
supported |
Yes |
Number of GD loops, max. |
4 |
Number of GD packets, max. |
4 |
Number of GD packets, transmitter, max. |
4 |
Number of GD packets, receiver, max. |
4 |
Size of GD packets, max. |
22 byte |
Size of GD packet (of which consistent), max. |
22 byte |
S7 basic communication |
supported |
Yes; Server |
User data per job, max. |
76 byte |
User data per job (of which consistent), max. |
76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
supported |
Yes |
as server |
Yes |
as client |
Yes; Via CP and loadable FB |
User data per job, max. |
180 byte; With PUT/GET |
User data per job (of which consistent), max. |
64 byte |
S5 compatible communication |
supported |
Yes; via CP and loadable FC |
Number of connections |
overall |
8 |
usable for PG communication |
7 |
reserved for PG communication |
1 |
adjustable for PG communication, min. |
1 |
adjustable for PG communication, max. |
7 |
usable for OP communication |
7 |
reserved for OP communication |
1 |
adjustable for OP communication, min. |
1 |
adjustable for OP communication, max. |
7 |
usable for S7 basic communication |
4 |
reserved for S7 basic communication |
4 |
adjustable for S7 basic communication, min. |
0 |
adjustable for S7 basic communication, max. |
4 |
usable for routing |
No |
S7 message functions |
Number of login stations for message functions, max. |
8; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages |
Yes |
simultaneously active Alarm-S blocks, max. |
20 |
Test commissioning functions |
Status block |
Yes |
Single step |
Yes |
Number of breakpoints |
2 |
Status/control |
Status/control variable |
Yes |
Variables |
Inputs, outputs, memory bits, DB, times, counters |
Number of variables, max. |
30 |
of which status variables, max. |
30 |
of which control variables, max. |
14 |
Forcing |
Forcing |
Yes |
Forcing, variables |
Inputs, outputs |
Number of variables, max. |
10 |
Integrated Functions |
Number of counters |
3; 3 channels (see "Technological Functions" manual) |
Counting frequency (counter) max. |
30 kHz |
Frequency measurement |
Yes |
Number of frequency meters |
3; 3 channels up to max. 30 kHz (see "Technological Functions" manual) |
controlled positioning |
No |
integrated function blocks (closed-loop control) |
PID controller (see "Technological Functions" manual) |
PID controller |
Yes |
Number of pulse outputs |
3; 3 channels pulse width modulation up to max. 2.5 kHz (see "Technological Functions" manual) |
Limit frequency (pulse) |
2.5 kHz |
Galvanic isolation |
Galvanic isolation digital inputs |
Galvanic isolation digital inputs |
Yes |
between the channels, in groups of |
16 |
between the channels and the backplane bus |
Yes |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs |
Yes |
between the channels, in groups of |
8 |
between the channels and the backplane bus |
Yes |
Configuration |
Configuration software |
STEP 7 |
Yes; V5.1 SP2 |
Programming |
Command set |
see instruction list |
Nesting levels |
8 |
System functions (SFC) |
see instruction list |
System function blocks (SFB) |
see instruction list |
Programming language |
LAD |
Yes |
FBD |
Yes |
STL |
Yes |
SCL |
Yes |
GRAPH |
Yes |
HiGraph® |
Yes |
Know-how protection |
User program protection/password protection |
Yes |
Dimensions |
Width |
120 mm |
Height |
125 mm |
Depth |
130 mm |
Weights |
Weight, approx. |
566 g |
Status |
Jul 5, 2014 |