SIMATIC S7-300, CPU 314C-2DP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 48 KBYTE WORKING MEMORY, MICRO MEMORY CARD REQUIRED |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
Rated value at 24 V DC |
1 000 mA |
Inrush current, max. |
11 A |
Power losses |
Power loss, typ. |
14 W |
Memory |
Work memory |
● Integrated |
48 kbyte; For program and data |
● expandable |
No |
Load memory |
● expandable FEPROM |
Yes; with Micro Memory Card (MMC) |
● expandable FEPROM, max. |
4 Mbyte |
Backup |
● present |
Yes; Guaranteed by MMC (maintenance-free) |
● without battery |
Yes; Program and data |
CPU processing times |
for bit operations, typ. |
0.1 µs |
for word operations, typ. |
0.5 µs |
for fixed point arithmetic, typ. |
1 µs |
for floating point arithmetic, typ. |
15 µs |
CPU-blocks |
DB |
● Number, max. |
127; DB 0 reserved |
● Size, max. |
16 kbyte |
FB |
● Number, max. |
128 |
● Size, max. |
16 kbyte |
FC |
● Number, max. |
128 |
● Size, max. |
16 kbyte |
OB |
● Size, max. |
16 kbyte |
● Number of time alarm OBs |
1 |
● Number of delay alarm OBs |
1 |
● Number of time interrupt OBs |
1 |
● Number of process alarm OBs |
1 |
Nesting depth |
● per priority class |
8 |
● additional within an error OB |
4 |
Counters, timers and their retentivity |
S7 counter |
● Number |
256 |
of which retentive without battery |
— can be set |
Yes; Z 0 to Z 255 |
— lower limit |
0 |
— upper limit |
256 |
Counting range |
— lower limit |
1 |
— upper limit |
999 |
IEC counter |
● present |
Yes |
● Type |
SFB |
S7 times |
● Number |
256 |
Retentivity |
— can be set |
Yes; T 0 to T 255 |
— lower limit |
0 |
— upper limit |
256 |
Time range |
— lower limit |
10 ms |
— upper limit |
9 990 s |
IEC timer |
● present |
Yes |
● Type |
SFB |
Data areas and their retentivity |
Flag |
● Number, max. |
256 byte |
● Retentivity available |
Yes; MB 0 to MB 255 |
Address area |
I/O address area |
● Inputs |
1 kbyte |
● Outputs |
1 kbyte |
Process image |
● Inputs |
128 byte |
● Outputs |
128 byte |
Digital channels |
● Inputs |
992 |
● Outputs |
992 |
Analog channels |
● Inputs |
248 |
● Outputs |
124 |
Hardware configuration |
Expansion devices, max. |
3 |
Number of DP masters |
● Integrated |
1 |
● Via CP |
1 |
Number of operable FMs and CPs (recommended) |
● FM |
8 |
● CP, point-to-point |
4 |
● CP, LAN |
2 |
Rack |
● Racks, max. |
4 |
● Modules per rack, max. |
8; In rack 3 max. 7 |
Time of day |
Clock |
● Hardware clock (real-time clock) |
Yes |
● battery-backed and synchronizable |
Yes |
Operating hours counter |
● Number |
1 |
Clock synchronization |
● supported |
Yes |
Digital inputs |
Number of digital inputs |
24 |
Input voltage |
● Rated value, DC |
24 V |
● for signal "0" |
-3 to +5V |
● for signal "1" |
15 to 30 V |
Input current |
● for signal "1", typ. |
8 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— Parameterizable |
Yes; 0.1 / 0.3 / 3 / 15 ms |
for counter/technological functions |
— at "0" to "1", max. |
8 µs |
Cable length |
● Cable length, shielded, max. |
1 000 m; 100 m for technological functions |
● Cable length unshielded, max. |
600 m |
Digital outputs |
Number of digital outputs |
16 |
short-circuit protection |
Yes; Clocked electronically |
Limitation of inductive shutdown voltage to |
L+ (-48 V) |
Output voltage |
● for signal "1", min. |
L+ (-0.8 V) |
Output current |
● for signal "1" permissible range for 0 to 40 °C, max. |
500 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
500 mA |
● for signal "1" minimum load current |
5 mA |
● for signal "0" residual current, max. |
0.5 mA |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 40 °C, max. |
8 A |
— up to 60 °C, max. |
4 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Analog inputs |
Number of analog inputs |
4 |
Number of analog inputs for voltage/current measurement |
4 |
Number of analog inputs for resistance/resistance thermometer measurement |
1 |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
● Resistance thermometer |
Yes |
● Resistance |
Yes |
Input ranges (rated values), voltages |
● 0 to +10 V |
Yes |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● -20 to +20 mA |
Yes |
● 4 to 20 mA |
Yes |
Input ranges (rated values), resistance thermometer |
● Pt 100 |
Yes |
Input ranges (rated values), resistors |
● 0 to 600 ohms |
Yes |
Analog outputs |
Number of analog outputs |
2 |
Output ranges, voltage |
● 0 to 10 V |
Yes |
● -10 to +10 V |
Yes |
Output ranges, current |
● 0 to 20 mA |
Yes |
● -20 to +20 mA |
Yes |
● 4 to 20 mA |
Yes |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
12 bit |
● Integration time, parameterizable |
Yes; 2,5 / 16,6 / 20 ms |
● Conversion time (per channel) |
1 ms |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— Permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Errors/accuracies |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.7 % |
● Current, relative to input area, (+/-) |
0.7 % |
● Resistance thermometer, relative to input area, (+/-) |
3 % |
● Voltage, relative to output area, (+/-) |
0.7 % |
● Current, relative to output area, (+/-) |
0.7 % |
Interfaces |
MPI |
● Cable length, max. |
50 m; without repeater |
1st interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
Isolated |
No |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Functionality |
● MPI |
Yes |
● DP master |
No |
● DP slave |
No |
● Point-to-point connection |
No |
MPI |
● Number of connections |
12 |
● Transmission rate, max. |
187.5 kbit/s |
Services |
— PG/OP communication |
Yes |
— Global data communication |
Yes |
— S7 basic communication |
Yes |
— S7 communication |
Yes |
— S7 communication, as client |
No |
— S7 communication, as server |
Yes |
2nd interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
Isolated |
Yes |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Functionality |
● MPI |
No |
● DP master |
Yes |
● DP slave |
Yes |
● Point-to-point connection |
No |
DP master |
● Number of connections, max. |
12; For PG/OP communication |
● Transmission rate, max. |
12 Mbit/s |
● Number of DP slaves, max. |
32 |
Services |
— PG/OP communication |
Yes |
— Global data communication |
No |
— S7 basic communication |
No |
— S7 communication |
No |
— S7 communication, as client |
No |
— S7 communication, as server |
No |
— Equidistance mode support |
Yes |
— SYNC/FREEZE |
Yes |
— Direct data exchange (slave-to-slave communication) |
Yes |
— DPV1 |
No |
Address area |
— Inputs, max. |
1 kbyte |
— Outputs, max. |
1 kbyte |
User data per DP slave |
— Inputs, max. |
244 byte |
— Outputs, max. |
244 byte |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
● supported |
Yes |
● Number of GD packets, transmitter, max. |
4 |
● Number of GD packets, receiver, max. |
4 |
● Size of GD packets, max. |
22 byte |
S7 basic communication |
● supported |
Yes |
● User data per job, max. |
76 byte |
S7 communication |
● User data per job, max. |
64 kbyte |
Number of connections |
● overall |
12 |
● usable for PG communication |
11 |
— reserved for PG communication |
1 |
— Adjustable for PG communication, max. |
11 |
● usable for OP communication |
11 |
— reserved for OP communication |
1 |
— adjustable for OP communication, max. |
11 |
● usable for S7 basic communication |
8 |
— Reserved for S7 basic communication |
8 |
— adjustable for S7 basic communication, max. |
8 |
● usable for routing |
4 |
S7 message functions |
Number of login stations for message functions, max. |
7 |
Integrated Functions |
Number of counters |
4 |
Counter frequency (counter) max. |
60 kHz |
Frequency measurement |
Yes |
controlled positioning |
Yes |
PID controller |
Yes |
Number of pulse outputs |
4 |
Limit frequency (pulse) |
2.5 kHz |
Galvanic isolation |
Galvanic isolation digital inputs |
● Galvanic isolation digital inputs |
Yes |
● between the channels, in groups of |
16 |
● between the channels and the backplane bus |
Yes |
Galvanic isolation digital outputs |
● Galvanic isolation digital outputs |
Yes |
● between the channels, in groups of |
8 |
● between the channels and the backplane bus |
Yes |
Galvanic isolation analog inputs |
● Galvanic isolation analog inputs |
Yes; common for analog I/O |
Galvanic isolation analog outputs |
● Galvanic isolation analog outputs |
Yes; common for analog I/O |
Configuration |
Configuration software |
● STEP 7 |
Yes; V5.1 SP2 |
programming |
● Nesting levels |
8 |
Programming language |
— LAD |
Yes |
— FBD |
Yes |
— STL |
Yes |
— SCL |
Yes |
— CFC |
Yes |
— GRAPH |
Yes |
— HiGraph® |
Yes |
Know-how protection |
● User program protection/password protection |
Yes |
Dimensions |
Width |
120 mm |
Height |
125 mm |
Depth |
130 mm |
Weights |
Weight, approx. |
680 g |
last modified: |
25.09.2014 |