SIMATIC S7-300, CPU 312 CPU WITH MPI INTERFACE, INTEGRATED 24 V DC POWER SUPPLY 32 KBYTE WORKING MEMORY, MICRO MEMORY CARD NECESSARY |
General information |
Hardware product version |
01 |
Firmware version |
V3.3 |
Engineering with |
● Programming package |
STEP 7 V5.5 + SP1 or higher or STEP7 V5.2 + SP1 or higher with HSP 218 |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
19.2 V |
permissible range, upper limit (DC) |
28.8 V |
External protection for supply cables (recommendation) |
2 A min. |
Mains buffering |
● Mains/voltage failure stored energy time |
5 ms |
● Repeat rate, min. |
1 s |
Input current |
Current consumption (rated value) |
650 mA |
Current consumption (in no-load operation), typ. |
140 mA |
Inrush current, typ. |
3.5 A |
I²t |
1 A²·s |
Power losses |
Power loss, typ. |
4 W |
Memory |
Type of memory |
other |
Work memory |
● Integrated |
32 kbyte |
● expandable |
No |
● Size of retentive memory for retentive data blocks |
32 kbyte |
Load memory |
● pluggable (MMC) |
Yes |
● pluggable (MMC), max. |
8 Mbyte |
● Data management on MMC (after last programming), min. |
10 y |
Backup |
● present |
Yes; Guaranteed by MMC (maintenance-free) |
● without battery |
Yes; Program and data |
CPU processing times |
for bit operations, typ. |
0.1 µs |
for word operations, typ. |
0.24 µs |
for fixed point arithmetic, typ. |
0.32 µs |
for floating point arithmetic, typ. |
1.1 µs |
CPU-blocks |
Number of blocks (total) |
1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB |
● Number, max. |
1 024; Number range: 1 to 16000 |
● Size, max. |
32 kbyte |
FB |
● Number, max. |
1 024; Number range: 0 to 7999 |
● Size, max. |
32 kbyte |
FC |
● Number, max. |
1 024; Number range: 0 to 7999 |
● Size, max. |
32 kbyte |
OB |
● Description |
see instruction list |
● Size, max. |
32 kbyte |
● Number of free cycle OBs |
1; OB 1 |
● Number of time alarm OBs |
1; OB 10 |
● Number of delay alarm OBs |
2; OB 20, 21 |
● Number of time interrupt OBs |
4; OB 32, 33, 34, 35 |
● Number of process alarm OBs |
1; OB 40 |
● Number of startup OBs |
1; OB 100 |
● Number of asynchronous error OBs |
4; OB 80, 82, 85, 87 |
● Number of synchronous error OBs |
2; OB 121, 122 |
Nesting depth |
● per priority class |
16 |
● additional within an error OB |
4 |
Counters, timers and their retentivity |
S7 counter |
● Number |
256 |
Retentivity |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
255 |
— preset |
Z 0 to Z 7 |
Counting range |
— lower limit |
0 |
— upper limit |
999 |
IEC counter |
● present |
Yes |
● Type |
SFB |
● Number |
Unlimited (limited only by RAM capacity) |
S7 times |
● Number |
256 |
Retentivity |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
255 |
— preset |
No retentivity |
Time range |
— lower limit |
10 ms |
— upper limit |
9 990 s |
IEC timer |
● present |
Yes |
● Type |
SFB |
● Number |
Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area, total |
All (incl. memory bits, times, counters) |
Flag |
● Number, max. |
256 byte |
● Retentivity available |
Yes; MB 0 to MB 255 |
● Retentivity preset |
MB 0 to MB 15 |
● Number of clock memories |
8; 1 memory byte |
Data blocks |
● Number, max. |
1 024; Number range: 1 to 16000 |
● Size, max. |
32 kbyte |
● Retentivity adjustable |
Yes; via non-retain property on DB |
● Retentivity preset |
Yes |
Local data |
● per priority class, max. |
32 kbyte; Max. 2 KB per block |
Address area |
I/O address area |
● Inputs |
1 024 byte |
● Outputs |
1 024 byte |
Process image |
● Inputs |
1 024 byte |
● Outputs |
1 024 byte |
● Inputs, adjustable |
1 024 byte |
● Outputs, adjustable |
1 024 byte |
● Inputs, default |
128 byte |
● Outputs, default |
128 byte |
Digital channels |
● Inputs |
256 |
● Outputs |
256 |
● Inputs, of which central |
256 |
● Outputs, of which central |
256 |
Analog channels |
● Inputs |
64 |
● Outputs |
64 |
● Inputs, of which central |
64 |
● Outputs, of which central |
64 |
Hardware configuration |
Expansion devices, max. |
0 |
Number of DP masters |
● Integrated |
0 |
● Via CP |
4 |
Number of operable FMs and CPs (recommended) |
● FM |
8 |
● CP, point-to-point |
8 |
● CP, LAN |
4 |
Rack |
● Racks, max. |
1 |
● Modules per rack, max. |
8 |
Time of day |
Clock |
● Software clock |
Yes |
● battery-backed and synchronizable |
No; Buffered: No, Can be synchronized: Yes |
● Deviation per day, max. |
10 s; Typ.: 2 s |
● Behavior of the clock following POWER-ON |
The clock continues at the time of day it had when power was switched off |
Operating hours counter |
● Number |
1 |
● Number/Number range |
0 |
● Range of values |
0 to 2^31 hours (when using SFC 101) |
● Granularity |
1 hour |
● retentive |
Yes; Must be restarted at each restart |
Clock synchronization |
● supported |
Yes |
● to MPI, master |
Yes |
● to MPI, slave |
Yes |
● in AS, master |
Yes |
● in AS, slave |
No |
Digital inputs |
Number of digital inputs |
0 |
Digital outputs |
Number of digital outputs |
0 |
Analog inputs |
Number of analog inputs |
0 |
Analog outputs |
Number of analog outputs |
0 |
Interfaces |
Number of USB interfaces |
0 |
Number of parallel interfaces |
0 |
Number of 20 mA interfaces (TTY) |
0 |
Number of RS 232 interfaces |
0 |
Number of RS 422 interfaces |
0 |
Number of other interfaces |
0 |
1st interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
Isolated |
No |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Functionality |
● MPI |
Yes |
● DP master |
No |
● DP slave |
No |
● Point-to-point connection |
No |
MPI |
● Transmission rate, max. |
187.5 kbit/s |
Services |
— PG/OP communication |
Yes |
— Routing |
No |
— Global data communication |
Yes |
— S7 basic communication |
Yes |
— S7 communication |
Yes; Only server, configured on one side |
— S7 communication, as client |
No |
— S7 communication, as server |
Yes |
Communication functions |
PG/OP communication |
Yes |
Data record routing |
No |
Global data communication |
● supported |
Yes |
● Number of GD loops, max. |
8 |
● Number of GD packets, max. |
8 |
● Number of GD packets, transmitter, max. |
8 |
● Number of GD packets, receiver, max. |
8 |
● Size of GD packets, max. |
22 byte |
● Size of GD packet (of which consistent), max. |
22 byte |
S7 basic communication |
● supported |
Yes |
● User data per job, max. |
76 byte |
● User data per job (of which consistent), max. |
76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
● supported |
Yes |
● as server |
Yes |
● As client |
Yes; Via CP and loadable FB |
● User data per job, max. |
180 byte; With PUT/GET |
● User data per job (of which consistent), max. |
240 byte; as server |
S5-compatible communication |
● supported |
Yes; via CP and loadable FC |
Number of connections |
● overall |
6 |
● usable for PG communication |
5 |
— reserved for PG communication |
1 |
— Adjustable for PG communication, min. |
1 |
— Adjustable for PG communication, max. |
5 |
● usable for OP communication |
5 |
— reserved for OP communication |
1 |
— adjustable for OP communication, min. |
1 |
— adjustable for OP communication, max. |
5 |
● usable for S7 basic communication |
2 |
— Reserved for S7 basic communication |
0 |
— adjustable for S7 basic communication, min. |
0 |
— adjustable for S7 basic communication, max. |
2 |
S7 message functions |
Number of login stations for message functions, max. |
6; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages |
Yes |
simultaneously active Alarm-S blocks, max. |
300 |
Test commissioning functions |
Status block |
Yes; Up to 2 simultaneously |
Single step |
Yes |
Number of breakpoints |
4 |
Status/control |
● Status/control variable |
Yes |
● Variables |
Inputs, outputs, memory bits, DB, times, counters |
● Number of variables, max. |
30 |
● of which status variables, max. |
30 |
● of which control variables, max. |
14 |
Forcing |
● Forcing |
Yes |
● Force, variables |
Inputs, outputs |
● Number of variables, max. |
10 |
Diagnostic buffer |
● present |
Yes |
● Number of entries, max. |
500 |
— can be set |
No |
— Of which powerfail-proof |
100; Only the last 100 entries are retained |
● Number of entries readable in RUN, max. |
499 |
— can be set |
Yes; From 10 to 499 |
— preset |
10 |
Service data |
● Can be read out |
Yes |
Ambient conditions |
Operating temperature |
● Min. |
0 °C |
● max. |
60 °C |
Configuration |
Configuration software |
● STEP 7 |
Yes; V5.2 SP1 or higher with HW update |
programming |
● Command set |
see instruction list |
● Nesting levels |
8 |
● System functions (SFC) |
see instruction list |
● System function blocks (SFB) |
see instruction list |
Programming language |
— LAD |
Yes |
— FBD |
Yes |
— STL |
Yes |
— SCL |
Yes |
— GRAPH |
Yes |
— HiGraph® |
Yes |
Know-how protection |
● User program protection/password protection |
Yes |
● Block encryption |
Yes; With S7 block Privacy |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
130 mm |
Weights |
Weight, approx. |
270 g |
last modified: |
25.09.2014 |