SIMATIC S7-300, CPU 312 IFM FOR EXPANDED TEMPERATURE RANGE CENTRAL PROCESSING UNIT WITH 10 DI/6 DO, 1 X 20 PIN., COUNTER, FREQUENCY MEASUREMENT INTEGRATED POWER SUPPLY 24 V DC 6 KBYTES WORKING MEMORY |
Supply voltage |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Power loss |
Power loss, typ. |
9 W; incl. integrated inputs/outputs |
Digital inputs |
Number of digital inputs |
10; of which 4 channels can be used for process alarms or integrated functions |
Input voltage |
● Rated value, DC |
24 V |
● for signal "1" |
15 to 30 V |
Input current |
● for signal "1", typ. |
7 mA; Min. 2 mA |
Cable length |
● Cable length, shielded, max. |
1 000 m; 100 m for alarm and counter inputs |
Digital outputs |
Number of digital outputs |
6 |
Short-circuit protection |
Yes; Clocked electronically |
Output voltage |
● for signal "1", min. |
L+ (-0.8 V) |
Output current |
● for signal "0" residual current, max. |
0.5 mA |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz |
Cable length |
● Cable length, shielded, max. |
1 000 m |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Ambient conditions |
Operating temperature |
● min. |
-25 °C |
● max. |
60 °C |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
130 mm |
Weights |
Weight, approx. |
450 g |
last modified: |