Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
from backplane bus 5 V DC, max. |
240 mA |
from sensor current supply or external current supply (24 V DC), max. |
128 mA |
Power losses |
Power loss, typ. |
9 W |
Digital inputs |
Number of digital inputs |
32 |
Input voltage |
● Rated value, DC |
24 V |
Input current |
● for signal "1", typ. |
4 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", max. |
4.5 ms |
Digital outputs |
Number of digital outputs |
32 |
short-circuit protection |
No |
Output voltage |
● for signal "0", max. |
0.1 V |
Output current |
● for signal "1" rated value |
750 mA |
Aggregate current of outputs (per group) |
all mounting positions |
— maximum current per conductor/group |
0.75 A |
Relay outputs |
Switching capacity of contacts |
— with inductive load, max. |
0.75 A |
— on lamp load, max. |
5 W |
— with resistive load, max. |
0.75 A |
Cable length |
● Cable length, shielded, max. |
500 m |
● Cable length unshielded, max. |
150 m |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— Permissible quiescent current (2-wire sensor), max. |
1 mA |
Galvanic isolation |
Galvanic isolation digital inputs |
● Galvanic isolation digital inputs |
Yes |
● between the channels, in groups of |
16 |
Galvanic isolation digital outputs |
● Galvanic isolation digital outputs |
Yes |
● between the channels, in groups of |
16 |
Connection method |
Plug-in I/O terminals |
Yes |
Dimensions |
Width |
196 mm |
Height |
80 mm |
Depth |
62 mm |
Weights |
Weight, approx. |
500 g |
last modified: |