6ES7636-2EC00-0AE3 SIMATIC C7-636 KEYS,

Product Code: 6ES7636-2EC00-0AE3

Availability: In Stock

Price: $2,411.20
  
 
Artikelnummer 6ES7636-2EC00-0AE3
SIMATIC C7-636 KEYS, COMPACT UNIT WITH INTEGRATED COMPONENTS: S7-300 CPU315-2 DP AND OP270B, 24 DI, 16 DO, 5 AI, 2 AO; MICRO MEMORY CARD AND CONNECTOR SET REQUIRED
Operator control and monitoring
Password protection Yes
Password levels 10
Text elements Yes
Info texts Yes
Alarms Yes; Fault messages, operating messages
Graphics object
● Process images Yes
● Graphics object Yes
● Semigraphic Yes
● Pixel graphics Yes
Process images
● Number of process images 300
● Number of variables per image, max. 200
● Number of variables in message text, max. 8
Operating / fault messages
● Operating messages Yes
— Number of entries in operational log, max. Message archive limited by storage medium
● Fault messages Yes
— Number of entries in fault message buffer, max. Message archive limited by storage medium
Recipes
● Number of recipes, max. 300
● Data records per recipe, max. 500
● Entries per data record, max. 1 000
Display
Design of display CSTN, CCFL backlit; 5.7" color (256 colors)
Resolution (pixels)
● Horizontal image resolution 320
● Vertical image resolution 240
Backlighting
● MTBF backlighting (at 20 °C) 40 000 h
Control elements
Keyboard
● Type Membrane keyboard
● Number of function keys 24; 18 with LED
● Number of softkeys 14
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, typ. 450 mA; idling
Current consumption, max. 1.3 A
Inrush current, max. 3 A; 3 A for 10 ms, then 2 A for 70 ms
Power losses
Power loss, typ. 19 W
Memory
Micro Memory Card Yes
Work memory
● Integrated 128 kbyte
● expandable No
Load memory
● pluggable (MMC) Yes
● pluggable (MMC), max. 8 Mbyte
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● with battery Yes; Option for the panel
● without battery Yes; Program and data of the CPU
Battery
Backup battery
● Backup battery
— Backup battery (optional) Yes
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
DB
● Number, max. 1 023; DB 0 reserved
● Size, max. 16 kbyte
FB
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
FC
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
OB
● Number, max. see instruction list
● Size, max. 16 kbyte
Nesting depth
● per priority class 8
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
of which retentive without battery
— can be set Yes
— lower limit 0
— upper limit 256
Retentivity
— can be set Yes
— preset Z 0 to Z 7
Counting range
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
of which retentive without battery
— can be set Yes; Default: no retentivity
— lower limit 0
— upper limit 256
Retentivity
— can be set Yes
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. all
Flag
● Number, max. 2 048 byte
● Retentivity available Yes; MB 0 to MB 255
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 1 023
● Size, max. 16 kbyte
Local data
● per priority class, max. 1 024 byte; max. 510 bytes per block
Address area
I/O address area
● Inputs 2 kbyte
● Outputs 2 kbyte
of which, distributed
— Inputs 2 000 byte
— Outputs 2 000 byte
Process image
● Inputs 128 byte
● Outputs 128 byte
Default addresses of the integrated channels
— Digital inputs 124.0 to 126.7
— Digital outputs 124.0 to 125.7
— Analog inputs 752
— Analog outputs 761
Digital channels
● Inputs 16 384
● Outputs 16 384
● Inputs, of which central 992
● Outputs, of which central 992
Analog channels
● Inputs 1 024
● Outputs 1 024
● Inputs, of which central 248
● Outputs, of which central 248
Hardware configuration
Number of modules per system, max. 23
Number of DP masters
● Integrated 1
● Via CP 1
Number of operable FMs and CPs (recommended)
● FM 8
● CP, point-to-point 8
● CP, LAN 10
Expansion modules
● Number of expansion modules, max. 4; max. 2 flat structure, max. 4 deep structure
Rack
● Racks, max. 4
● Modules per rack, max. 8; Modules in subrack 0: 4 max.; modules in subracks 1 and 2: 8 max.; modules in subrack 3: 7 max.
● Rack, number of rows, max. 4
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Deviation per day, max. 10 s
● Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● in AS, master Yes
Digital inputs
Number of digital inputs 24
● of which, inputs usable for technological functions 16
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max. 12
vertical installation
— up to 40 °C, max. 18
Input voltage
● Rated value, DC 24 V
● for signal "0" -3 to +5V
● for signal "1" 15 to 30 V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— Parameterizable Yes; 0.1 / 0.3 / 3 / 15 ms
— Rated value 3 ms
for counter/technological functions
— at "0" to "1", max. 8 µs
Cable length
● Cable length, shielded, max. 1 000 m; 100 m for technological functions
● Cable length unshielded, max. 600 m
Technological functions
— shielded, max. 50 m; at maximum count frequency
— Unshielded, max. not allowed
Standard DI
— shielded, max. 1 000 m
— Unshielded, max. 600 m
Digital outputs
Number of digital outputs 16
● of which high-speed outputs 4
short-circuit protection Yes; Clocked electronically
● Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-48 V)
Controlling a digital input Yes
Switching capacity of the outputs
● Lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 4 kΩ
Output voltage
● for signal "1", min. L+ (-0.8 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, min. 5 mA
● for signal "1" permissible range, max. 0.6 A
● for signal "1" permissible range for 0 to 40 °C, max. 0.5 A
● for signal "1" permissible range for 40 to 60 °C, max. 0.5 A; Up to 50 °C
● for signal "1" minimum load current 5 mA
● for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
● for increased power No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 100 Hz
● of the pulse outputs, with resistive load, max. 2.5 kHz
Aggregate current of outputs (per group)
all mounting positions
— up to 40 °C, max. 3 A
— up to 60 °C, max. 2 A; Up to 50 °C
horizontal installation
— up to 40 °C, max. 2 A
vertical installation
— up to 40 °C, max. 3 A
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Analog inputs
Number of analog inputs 4
Integrated channels (AI) 4; + 1 AI
Number of analog inputs for voltage/current measurement 4
Number of analog inputs for resistance/resistance thermometer measurement 1
permissible input frequency for current input (destruction limit), max. 2.5 V; max. 2.5 V permanent; max. 24 V for short time
permissible input voltage for voltage input (destruction limit), max. 30 V; Permanent
permissible input current for voltage input (destruction limit), max. 0.5 mA; Permanent
permissible input current for current input (destruction limit), max. 50 mA; Permanent
Technical unit for temperature measurement adjustable Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges
● Voltage Yes
● Current Yes
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 50 Ω
● -20 to +20 mA Yes
● Input resistance (-20 to +20 mA) 50 Ω
● 4 to 20 mA Yes
● Input resistance (4 to 20 mA) 50 Ω
Input ranges (rated values), resistance thermometer
● Pt 100 Yes
● Input resistance (Pt 100) 10 MΩ
Input ranges (rated values), resistors
● No-Load voltage, typ. 2.5 V
● Measured current, typ. 1.8 to 3.3 mA
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 10 MΩ
Thermocouple (TC)
Temperature compensation
— Parameterizable No
Characteristic linearization
● Parameterizable Yes; by software
— for resistance thermometer Pt 100
Cable length
● Cable length, shielded, max. 100 m
Analog outputs
Number of analog outputs 2
Integrated channels (AO) 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 55 mA
Current output, no-load voltage, max. 17 V
Output ranges, voltage
● 0 to 10 V Yes
● -10 to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 to +20 mA Yes
● 4 to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes; Without compensation of the line resistances
● for voltage output four-wire connection No
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 0.1 µF
● with current outputs, max. 300 Ω
● with current outputs, inductive load, max. 0.1 mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs towards MANA 16 V; Permanent
● Current, max. 50 mA; Permanent
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Measurement principle Measurement principle momentary value encoding (successive approximation)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit
● Integration time, parameterizable Yes; 2,5 / 16,6 / 20 ms
● permissible input frequency, max. 400 Hz
● Conversion time (per channel) 1 ms
● Time constant of the input filter 0.38 ms
● Basic execution time of the module (all channels released) 1 ms
Settling time
● for resistive load 0.6 ms
● for capacitive load 1 ms
● for inductive load 0.5 ms
Encoder
Connectable encoders
● 2-wire sensor Yes
— Permissible quiescent current (2-wire sensor), max. 1.5 mA
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.06 %
Temperature error (relative to input range), (+/-) 0.006 %/K
Crosstalk between the inputs, min. 50 dB; at Ucm = 0 V
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.06 %
Output ripple (based on output area, bandwidth 0 to 50 kHz), (+/-) 0.1 %
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.01 %/K
Crosstalk between the outputs, min. 60 dB
Repeat accuracy in steady state at 25 °C (relative to output area), (+/-) 0.06 %
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 1 %
● Current, relative to input area, (+/-) 1 %
● Resistance, relative to input area, (+/-) 5 %
● Voltage, relative to output area, (+/-) 1 %
● Current, relative to output area, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.7 %
● Current, relative to input area, (+/-) 0.7 %
● Resistance, relative to input area, (+/-) 3 %
● Resistance thermometer, relative to input area, (+/-) 3 %
● Voltage, relative to output area, (+/-) 0.7 %
● Current, relative to output area, (+/-) 0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 30 dB
● Common mode interference, min. 40 dB
Interfaces
Number of printer interfaces 1; serial
MPI
● Cable length, max. 50 m; without repeater
1st interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● DP master No
● DP slave No
MPI
● Number of connections 16
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client Yes; Via CP and loadable FB
— S7 communication, as server Yes
2nd interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Number of connection resources 16
Functionality
● MPI No
● DP master Yes
● DP slave Yes
DP master
● Number of connections, max. 16; For PG/OP communication
● Number of connections (of which reserved), max. 1 for PG, 1 for OP
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 125
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— S7 communication, as client No
— S7 communication, as server No
— Equidistance mode support Yes
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Direct data exchange (slave-to-slave communication) Yes
Address area
— Inputs, max. 244 byte
— Outputs, max. 244 byte
DP slave
● Number of connections 16
● Transmission rate, max. 12 Mbit/s
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— Direct data exchange (slave-to-slave communication) Yes
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● As client Yes; Via CP and loadable FB
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 64 byte
S5-compatible communication
● supported Yes; via CP and loadable FC
Standard communication (FMS)
● supported No
Number of connections
● overall 16
● usable for PG communication 15
— reserved for PG communication 1
— Adjustable for PG communication, min. 1
— Adjustable for PG communication, max. 15
● usable for OP communication 15
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 15
● usable for S7 basic communication 12
— Reserved for S7 basic communication 12
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 12
S7 message functions
Number of login stations for message functions, max. 16
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— can be set No
Interrupts/diagnostics/status information
Alarms
● Alarms Yes; No interrupts when used as standard I/O; when using the technological functions, see the manual S7-300 Programmable Controller, CPU31xC Technological Functions
Diagnostic messages
● Diagnostic functions No; No interrupts when used as standard I/O; when using the technological functions, see the manual S7-300 Programmable Controller, CPU31xC Technological Functions
Integrated Functions
Number of counters 4; 4 channels in total
Counter frequency (counter) max. 60 kHz
Frequency meter Yes
Frequency measurement Yes
Number of frequency meters 4; 4 channels in total
controlled positioning Yes
Integrated function blocks (closed-loop control) Yes
PID controller Yes
Pulse outputs Yes
Number of pulse outputs 4; 4 channels in total
Limit frequency (pulse) 2.5 kHz
Galvanic isolation
Galvanic isolation digital inputs
● Galvanic isolation digital inputs Yes
● between the channels No
● between the channels and the backplane bus Yes
Galvanic isolation digital outputs
● Galvanic isolation digital outputs Yes
● between the channels Yes
● between the channels, in groups of 8
● between the channels and the backplane bus Yes
Galvanic isolation analog inputs
● Galvanic isolation analog inputs Yes
● between the channels No
● between the channels and the backplane bus Yes
Galvanic isolation analog outputs
● Galvanic isolation analog outputs Yes
● between the channels No
● between the channels and the backplane bus Yes
Permissible potential difference
between different circuits 75 VDC / 60 VAC
between inputs and MANA (UCM) 8 V DC
between MANA and M internally (UISO) 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes; ±6 kV contact discharge acc. to IEC 61000-4-2, ESD; ±8 kV air discharge acc. to IEC 61000-4-2, ESD
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes; ±2 kV to IEC 61000-4-4, burst; surge measurements with additional protective elements
● Interference immunity on signal lines acc. to IEC 61000-4-4 Yes
Surge immunity
● on the supply lines acc. to IEC 61000-4-5 Yes; ±1 kV acc. to IEC 61000-4-5, µs pulse/line to line; ±2 kV acc. to IEC 61000-4-5, µs pulse/line to ground
Immunity against high-frequency electromagnetic fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 80 MHz to 1 GHz (to IEC 61000-4-3); 10 V/m, pulse-modulated 50% duty cycle at 900 MHz and 1.89 GHz (to IEC61000-4-3)
Immunity against conducted interference induced by high-frequency fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes; 10 V/m, with 80% amplitude modulation at 1 kHz
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes
Degree and class of protection
Degree of protection to EN 60529
● IP20 Yes; Housing
● IP65 Yes; Front
Standards, approvals, certificates
CSA approval Yes
UL approval Yes
FM approval Yes
Ambient conditions
Environmental conditions Not suitable for open-air use
Operating temperature
● 45 degree installation, min. 0 °C
● 45 degree installation, max. 45 °C
● horizontal installation, min. 0 °C
● horizontal installation, max. 40 °C
● vertical installation, min. 0 °C
● vertical installation, max. 50 °C
Air pressure
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
● permissible range, min. 795 hPa
● permissible range, max. 1 080 hPa
Relative humidity
● Operation, min. 5 %
● Operation, max. 85 %; at <40 °C (no condensation)
● Storage/transport, max. 85 %; at <40 °C (no condensation)
Vibrations
● Operation, checked according to IEC 60068-2-6 Yes; Operation 10 to 58 Hz, amplitude 0.075 mm; 58 to 150 Hz, acceleration 9.8 m/s2
● Transport tested checked to IEC 60068-2-6 Yes; 5 to 9 Hz: Amplitude 3.5 mm; 9 to 500 Hz: Acceleration 9.8 m/s2
Shock test
● checked according to IEC 60068-2-29 Yes; checked according to IEC 60068-2-29; operation: Half-sine: 150 m/s2 (15 g), 11 ms, 18 shocks; storage/transport: 250 m/s2 (25 g), 6 ms, 1000 shocks
Shock testing
● Operation, checked according to IEC 60068-2-29 Yes; Half-sine: 150 m/s2 (15 g), 11 ms, 18 shocks
● Storage/transport, checked to IEC 60068-2-29 Yes; 250 m/s2 (25 g), 6 ms, 1000 shocks
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 HSP or higher
● ProTool Yes; as of V6.0 SP2 with Setup C7-636
● ProTool/Lite Yes; Version 6.0 SP2 or higher and Setup C7-636
● ProTool/Pro Yes; Version 6.0 SP2 or higher and Setup C7-636
● WinCC flexible Compact Yes
● WinCC flexible Standard Yes
● WinCC flexible Advanced Yes
programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
Languages
Online languages
● Number of online/runtime languages 5
Dimensions
Width 260 mm
Height 274 mm
Depth 80 mm
Mounting cutout/device depth (W x H x T)
● Mounting cutout, width 231 mm; Tolerance: +1 mm
● Mounting cutout, height 257 mm; Tolerance: +1 mm
Weights
Weight, approx. 1 750 g
last modified: 25.09.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: