6ES7635-2EC01-0AE3 C7-635 KEYS, 24 DI, 16 DO, 5 AI, 2 AO

Product Code: 6ES7635-2EC01-0AE3

Availability: In Stock

Price: $1,527.55
  
 
C7-635 Touch

-
SIMATIC C7-635 KEYS, COMPACT UNIT WITH INTEGRATED COMPONENTS: S7-300 CPU314C-2 DP AND OP170B, 24 DI, 16 DO, 5 AI, 2 AO; MICRO MEMORY CARD AND CONNECTOR SET REQUIRED
Operator control and monitoring
Password protection Yes
Password levels 10
Text elements Yes
Info texts Yes
Alarms Yes; Fault messages, operating messages (no buffer)
Graphics object
Process images Yes
Graphics object Yes
Process images
Number of process images 100
Number of variables per image, max. 50
Number of variables in message text, max. 8
Operating/fault messages
Operating messages Yes
Number of entries in operational log, max. 128; not retentive
Operating messages, max. 2000; total number of operation and fault messages
Alarm messages Yes
Number of fault message, max. 2000; total number of operation and fault messages
Number of entries in fault message buffer, max. 128; not retentive
Recipes
Number of recipes, max. 20
Data records per recipe, max. 50; limited due to storage medium
Entries per data record, max. 60
Recipe data memory, max. 32 kbyte; expandable using Compact Flash Card (CF-Card)
Display
Design of display STN, CCFL backlit, 5.7" blue mode (4 blue tones)
Resolution (pixels)
horizontal image resolution 320
vertical image resolution 240
Backlighting
MTBF backlighting (at 20 °C) 50000 h
Control elements
Keyboard fonts
Number of operating cycles, keys 1000000
Number of function keys 10
Number of softkeys 14
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, typ. 350 mA; idling
Current consumption, max. 1 A
Inrush current, max. 2 A; for 70 ms
Digital inputs
from load voltage L+ (without load), max. 70 mA
Digital outputs
from load voltage L+, max. 20 mA; per group
Power loss
Power loss, typ. 14 W
Memory
Micro Memory Card Yes
Compact Flash Card Yes; Optional
Work memory
integrated 64 kbyte
expandable No
Load memory
Plug-in (MMC) Yes
Plug-in (MMC), max. 8 Mbyte
Backup
present Yes; Guaranteed by MMC (maintenance-free)
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
DB
Number, max. 511; DB 0 reserved
Size, max. 16 kbyte
FB
Number, max. 512; see instruction list
Size, max. 16 kbyte
FC
Number, max. 512; see instruction list
Size, max. 16 kbyte
OB
Number, max. see instruction list
Size, max. 16 kbyte
Nesting depth
per priority class 8
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 256
Retentivity
adjustable Yes
preset Z 0 to Z 7
Counting range
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
S7 times
Number 256
Retentivity
adjustable Yes
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. all
Flag
Number, max. 256 byte
Retentivity available Yes
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Data blocks
Number, max. 511
Size, max. 16 kbyte
Local data
per priority class, max. 510 byte
Address area
I/O address area
Inputs 1 kbyte
Outputs 1 kbyte
of which distributed
Inputs 1000 byte
Outputs 1000 byte
Process image
Inputs 128 byte
Outputs 128 byte
Default addresses of the integrated channels
Digital inputs 124.0 to 126.7
Digital outputs 124.0 to 125.7
Analog inputs 752 to 761
Analog outputs 752 to 755
Digital channels
Inputs 8192
Outputs 8192
Inputs, of which central 922
Outputs, of which central 922
Analog channels
Inputs 512
Outputs 512
Inputs, of which central 248
Outputs, of which central 248
Hardware configuration
Number of modules per system, max. 23
Number of DP masters
integrated 1
via CP 1
Number of operable FMs and CPs (recommended)
FM 8
CP, point-to-point 8
CP, LAN 10
Rack
Racks, max. 4
Modules per rack, max. 4; 4 in subrack 0; 8 in subracks 1 and 2; 7 in subrack 3
Time of day
Clock
Hardware clock (real-time clock) Yes
battery-backed and synchronizable Yes
Deviation per day, max. 10 s
Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
Number 1
Number/Number range 0
Range of values 0 to 2^31 hours (when using SFC 101)
Granularity 1 hour
retentive Yes; Must be restarted at each restart
Clock synchronization
supported Yes
to MPI, master Yes
to MPI, slave Yes
in AS, master Yes
Digital inputs
Number of digital inputs 24
of which inputs usable for technological functions 16
integrated channels (DI) 24
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
up to 40 °C, max. 12
vertical installation
up to 40 °C, max. 18
up to 50 °C, max. 12
45° mounting position
up to 45 °C, max. 12
Input voltage
Rated value, DC 24 V
for signal "0" -3 to +5 V
for signal "1" 15 to 30 V
Input current
for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizable Yes; 0.1 / 0.5 / 3 / 15 ms
Rated value 3 ms
for counter/technological functions
at "0" to "1", max. 8 µs
Cable length
Cable length, shielded, max. 1000 m; 100 m for technological functions
Cable length unshielded, max. 600 m
Technological functions
shielded, max. 50 m; at maximum count frequency
unshielded, max. Unshielded cables are not permissible for technological functions
Standard DI
shielded, max. 1000 m
unshielded, max. 600 m
Digital outputs
Number of digital outputs 16
of which high-speed outputs 4
integrated channels (DO) 16
Short-circuit protection Yes; Clocked electronically
Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-48 V)
Controlling a digital input Yes
Switching capacity of the outputs
Lamp load, max. 5 W
Load resistance range
lower limit 48 Ω
upper limit 4 kΩ
Output voltage
for signal "1", min. L+ (-0.8 V)
Output current
for signal "1" rated value 0.5 A
for signal "1" permissible range, min. 5 mA
for signal "1" permissible range, max. 0.6 A
for signal "1" minimum load current 5 mA
for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
for uprating No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 100 Hz
of the pulse outputs, with resistive load, max. 2.5 kHz
Total current of the outputs (per group)
all mounting positions
up to 40 °C, max. 4 A
up to 60 °C, max. 2 A
horizontal installation
up to 40 °C, max. 2 A
vertical installation
up to 40 °C, max. 3 A
up to 50 °C, max. 2 A
45° mounting position
up to 45 °C, max. 2 A
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Analog inputs
integrated channels (AI) 4; and 1x PT100
Number of analog inputs 4
Number of analog inputs for voltage/current measurement 4
Number of analog inputs for resistance/resistance thermometer measurement 1
Number of analog inputs for resistance measurement 1
permissible input voltage for current input (destruction limit), max. 2.5 V; continuous, max. 24 V momentarily
permissible input voltage for voltage input (destruction limit), max. 30 V; Permanent
permissible input current for voltage input (destruction limit), max. 0.5 mA; Permanent
permissible input current for current input (destruction limit), max. 50 mA; Permanent
Technical unit for temperature measurement adjustable Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges
Voltage Yes
Current Yes
Resistance thermometer Yes
Resistance Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) 100 kΩ
-10 V to +10 V Yes
Input resistance (-10 V to +10 V) 100 kΩ
Input ranges (rated values), currents
0 to 20 mA Yes
Input resistance (0 to 20 mA) 50 kΩ
-20 to +20 mA Yes
Input resistance (-20 to +20 mA) 50 kΩ
4 to 20 mA Yes
Input resistance (4 to 20 mA) 50 kΩ
Input ranges (rated values), resistance thermometers
Pt 100 Yes
Input resistance (Pt 100) 10 MΩ
Input ranges (rated values), resistors
No-load voltage, typ. 2.5 V
Measured current, typ. 1.8 to 3.3 mA
0 to 600 Ohm Yes
Input resistance (0 to 600 Ohm) 10 MΩ
Thermocouple (TC)
Temperature compensation
parameterizable No
Resistance thermometer (RTD)
Characteristic linearization
for resistance thermometer Pt 100
Characteristic linearization
parameterizable Yes; by software
Cable length
Cable length, shielded, max. 100 m
Analog outputs
integrated channels (AO) 2
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 55 mA
Current output, no-load voltage, max. 17 V
Output ranges, voltage
0 to 10 V Yes
-10 to +10 V Yes
Output ranges, current
0 to 20 mA Yes
-20 to +20 mA Yes
4 to 20 mA Yes
Connection of actuators
for voltage output two-wire connection Yes; Without compensation of the line resistances
for voltage output four-wire connection No
for current output two-wire connection Yes
Load impedance (in rated range of output)
with voltage outputs, min. 1 kΩ
with voltage outputs, capacitive load, max. 0.1 µF
with current outputs, max. 300 Ω
with current outputs, inductive load, max. 0.1 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA 16 V; Permanent
Current, max. 50 mA; Permanent
Cable length
Cable length, shielded, max. 200 m
Analog value generation
Measurement principle Actual value encryption (successive approximation)
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max. 12 bit
Integration time, parameterizable Yes; 2,5 / 16,6 / 20 ms
permissible input frequency, max. 400 Hz
Conversion time (per channel) 1 ms
Time constant of the input filter 0.38 ms
Basic execution time of the module (all channels released) 1 ms
Settling time
for resistive load 0.6 ms
for capacitive load 1 ms
for inductive load 0.5 ms
Encoder
Connection of signal encoders
for voltage measurement Yes
for current measurement as 2-wire transducer Yes; with external supply
for current measurement as 4-wire transducer Yes
for resistance measurement with two-wire connection Yes; Without compensation of the line resistances
for resistance measurement with three-wire connection No
for resistance measurement with four-wire connection No
Connectable encoders
2-wire sensor Yes
permissible quiescent current (2-wire sensor), max. 1.5 mA
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.06 %
Temperature error (relative to input range), (+/-) 0.0060 %/K
Crosstalk between the inputs, min. 50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.06 %
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.01 %/K
Crosstalk between the outputs, min. 60 dB
Operational error limit in overall temperature range
Voltage, relative to input area, (+/-) 1 %
Current, relative to input area, (+/-) 1 %
Resistance, relative to input area, (+/-) 5 %
Voltage, relative to output area, (+/-) 1 %
Current, relative to output area, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area, (+/-) 0.7 %
Current, relative to input area, (+/-) 0.7 %
Resistance, relative to input area, (+/-) 3 %
Resistance thermometer, relative to input area, (+/-) 3 %
Voltage, relative to output area, (+/-) 0.7 %
Current, relative to output area, (+/-) 0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min. 30 dB
Common mode interference, min. 40 dB
Interfaces
Number of printer interfaces 1; serial
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
MPI Yes
MPI
Number of connections 12
Transmission rate, max. 187.5 kbit/s
Services
PG/OP communication Yes
Routing Yes
Global data communication Yes
S7 basic communication Yes
S7 communication Yes
S7 communication, as client Yes; Via CP and loadable FB
S7 communication, as server Yes
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Number of connection resources 12
Functionality
MPI No
DP master Yes
DP slave Yes
DP master
Number of connections, max. 12
Number of connections (of which reserved), max. 1 for PG, 1 for OP
Transmission rate, max. 12 Mbit/s
Number of DP slaves, max. 32
Services
PG/OP communication Yes
Routing Yes
Global data communication No
S7 basic communication No
S7 communication No
S7 communication, as client No
S7 communication, as server No
Equidistance mode support Yes
SYNC/FREEZE Yes
Activation/deactivation of DP slaves Yes
Direct data exchange (slave-to-slave communication) Yes
Address area
Inputs, max. 1 kbyte
Outputs, max. 1 kbyte
User data per DP slave
Inputs, max. 244 byte
Outputs, max. 244 byte
DP slave
Number of connections 12
Transmission rate, max. 12 Mbit/s
Address area, max. 32
User data per address area, max. 32 byte
Services
PG/OP communication Yes
Routing Yes; Only with active interface
Global data communication No
S7 basic communication No
S7 communication No
Direct data exchange (slave-to-slave communication) Yes
DPV1 No
Transfer memory
Inputs 244 byte
Outputs 244 byte
Communication functions
PG/OP communication Yes
Global data communication
supported Yes
Number of GD packets, max. 4
Number of GD packets, transmitter, max. 4
Number of GD packets, receiver, max. 4
Size of GD packets, max. 22 byte
Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
supported Yes
User data per job, max. 76 byte
User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supported Yes
as server Yes
as client Yes; Via CP and loadable FB
User data per job, max. 180 kbyte; With PUT/GET
User data per job (of which consistent), max. 64 byte
S5 compatible communication
supported Yes; Via CP and loadable FB
Number of connections
overall 12
usable for PG communication 11
reserved for PG communication 1
adjustable for PG communication, min. 1
adjustable for PG communication, max. 11
usable for OP communication 11
reserved for OP communication 1
adjustable for OP communication, min. 1
adjustable for OP communication, max. 11
usable for S7 basic communication 8
reserved for S7 basic communication 8
adjustable for S7 basic communication, min. 0
adjustable for S7 basic communication, max. 8
usable for routing 4
Number of logical connections (also in network), max. 4; 1 fixed with integral CPU
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
Status/control variable Yes
Variables Inputs, outputs, memory bits, DB, times, counters
Number of variables, max. 30
of which status variables, max. 30
of which control variables, max. 14
Forcing
Forcing Yes
Diagnostic buffer
present Yes
Number of entries, max. 100
adjustable No
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Integrated Functions
Number of counters 4
Counting frequency (counter) max. 60 kHz
Frequency measurement Yes
Number of frequency meters Frequency meter up to max. 60 kHz
controlled positioning Yes
integrated function blocks (closed-loop control) Yes; PID controller
PID controller Yes
Number of pulse outputs 4; Pulse outputs up to 2.5 kHz
Limit frequency (pulse) 2.5 kHz
Galvanic isolation
Galvanic isolation digital inputs
between the channels No
between the channels, in groups of 16
between the channels and the backplane bus Yes
Galvanic isolation digital outputs
between the channels Yes
between the channels, in groups of 8
between the channels and the backplane bus Yes
Galvanic isolation analog inputs
Galvanic isolation analog inputs Yes; common for analog I/O
between the channels No
between the channels and the backplane bus Yes
Galvanic isolation analog outputs
Galvanic isolation analog outputs Yes; common for analog I/O
between the channels No
between the channels and the backplane bus Yes
Permissible potential difference
between different circuits 75 VDC / 60 VAC
between inputs and MANA (UCM) 8 V DC
between MANA and M internally (UISO) 75 VDC / 60 VAC
Isolation
Isolation tested with 500 V DC
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes; ±6 kV contact discharge acc. to IEC 61000-4-2, ESD; ±8 kV air discharge acc. to IEC 61000-4-2, ESD
Interference immunity to cable-borne interference
on the supply lines acc. to IEC 61000-4-4 Yes
Interference immunity on signal cables acc. to IEC 61000-4-4 Yes; ±2 kV to IEC 61000-4-4, Burst
Interference immunity against voltage surge
on the supply lines acc. to IEC 61000-4-5 Yes; Surge measurements with additional protection elements: ±1 kV (to IEC 61000-4-5; µs pulse / line to line);±2 kV (to IEC 61000-4-5; µs pulse / line to ground)
Interference immunity against high-frequency electromagnetic fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 80 MHz to 1 GHz (to IEC 61000-4-3); 10 V/m, pulse-modulated 50% duty cycle at 900 MHz and 1.89 GHz (to IEC61000-4-3)
Interference immunity against conducted variable disturbance induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 10 kHz to 80 MHz (acc. to IEC 61000-4-6)
Emission of radio interference acc. to EN 55 011
Emission of radio interference acc. to EN 55 011 (limit class A) Yes
Degree and class of protection
IP20 Yes; Housing
IP65 Yes; Front
Standards, approvals, certificates
CSA approval Yes
UL approval Yes
FM approval Yes
Ambient conditions
Environmental conditions Not suitable for open-air use
Operating temperature
45 degree installation, min. 0 °C
45 degree installation, max. 45 °C
horizontal installation, min. 0 °C
horizontal installation, max. 40 °C
vertical installation, min. 0 °C
vertical installation, max. 50 °C
Storage/transport temperature
min. -20 °C
max. 70 °C
Air pressure
Operation, min. 795 hPa
Operation, max. 1080 hPa
Storage/transport, min. 660 hPa
Storage/transport, max. 1080 hPa
Relative humidity
Operation, min. 5 %
Operation, max. 95 %
Storage/transport, min. 5 %
Storage/transport, max. 95 %
Vibrations
Operation, tested according to IEC 60068-2-6 Yes; 10 to 58 Hz: Amplitude 0.075 mm; 58 to 150 Hz: Acceleration 9.8 m/s2
Transport, tested acc. to IEC 60068-2-6 Yes; 5 to 9 Hz: amplitude 3.5 mm; 9 to 500 Hz: acceleration 9.8 m/s (storage/transport in the packaging)
Shock test
tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Shock testing
Operation, tested according to IEC 60068-2-29 Yes; Half-sine: 150 m/s2 (15 g), 11 ms, 18 shocks
Storage/transport, tested acc. to IEC 60068-2-29 Yes; 250 m/s2 (25 g), 6 ms, 1000 shocks
Fire resistance
Terminal strips FV2 (tested to IEC 60707)
Basic strips in housing FV0
Configuration
Configuration software
STEP 7 Yes; V5.1 SP3, STEP 7 Lite
ProTool Yes; or SIMATIC ProTool/Pro Configuration, Version 6.0 SP1 or higher
ProTool/Lite Yes
ProTool/Pro Yes; Configuration also with WinCC flexible
WinCC flexible Compact Yes
WinCC flexible Standard Yes
WinCC flexible Advanced Yes
Programming
Command set see instruction list
Nesting levels 8
System functions (SFC) see instruction list
System function blocks (SFB) see instruction list
Programming language
LAD Yes
FBD Yes
STL Yes
SCL Yes
CFC Yes
GRAPH Yes
HiGraph® Yes
Know-how protection
User program protection/password protection Yes
Languages
Online languages
Number of online/runtime languages 3
Dimensions
Width 260 mm
Height 274 mm
Depth 80 mm
Mounting cutout/device depth (W x H x D)
Mounting cutout, width 231 mm
Mounting cutout, height 257 mm
Weights
Weight, approx. 1500 g
Status Jul 7, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: