SIMATIC S7-400, ANALOG INPUT SM 431, 8AI; 16 BIT RESOLUTION, U/I/THERMOEL., OPTIC. ISOLATED W. 1 POINT PER COMMON, DIAGN., ALARM, 20 MS MODULE UPDATE |
Input current |
from load voltage L+ (without load), max. |
400 mA |
from backplane bus 5 V DC, max. |
1 200 mA |
Power loss |
Power loss, typ. |
4.6 W |
Hardware configuration |
Slots |
● required slots |
1 |
Analog inputs |
Number of analog inputs |
8 |
Number of analog inputs for voltage/current measurement |
8 |
permissible input voltage for voltage input (destruction limit), max. |
35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. |
32 mA |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
● Thermocouple |
Yes |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), voltages |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
> 2000 ohms |
● -1 V to +1 V |
Yes |
● -10 V to +10 V |
Yes |
● -100 mV to +100 mV |
Yes |
● -2.5 V to +2.5 V |
Yes |
● -20 mV to +20 mV |
Yes |
● -250 mV to +250 mV |
Yes |
● -5 V to +5 V |
Yes |
● -50 mV to +50 mV |
Yes |
● -500 mV to +500 mV |
Yes |
● -80 mV to +80 mV |
Yes |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● -10 to +10 mA |
Yes |
● -20 to +20 mA |
Yes |
● -3.2 to +3.2 mA |
Yes |
● 4 to 20 mA |
Yes |
● Input resistance (4 to 20 mA) |
50 Ω |
● -5 to +5 mA |
Yes |
Input ranges (rated values), thermocouples |
● Type B |
Yes |
● Type E |
Yes |
● Type J |
Yes |
● Type K |
Yes |
● Type L |
Yes |
● Type N |
Yes |
● Type R |
Yes |
● Type S |
Yes |
● Type T |
Yes |
● Type U |
Yes |
Thermocouple (TC) |
Temperature compensation |
— internal temperature compensation |
Yes |
— external temperature compensation with compensations socket |
Yes |
— dynamic reference temperature value |
Yes |
Characteristic linearization |
● parameterizable |
Yes |
— for thermocouples |
Type B, E, J, K, L, N, R, S, T, U |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value generation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit |
● Integration time, parameterizable |
Yes |
● Basic conversion time, ms |
10 / 16,7 / 20 / 100 |
● Integration time, ms |
2,5 / 16,7 / 20 / 100 |
● Basic conversion time, including integration time, ms |
|
— additional conversion time for wire-break monitoring and resistance measurement |
1 ms (module) |
● Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 / 10 Hz |
Encoder |
Connection of signal encoders |
● for current measurement as 4-wire transducer |
Yes |
● for resistance measurement with four-wire connection |
Yes |
Errors/accuracies |
Operational error limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
0.3 % |
● Current, relative to input area, (+/-) |
0.5 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.1 % |
● Current, relative to input area, (+/-) |
0.17 % |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Parameterizable |
● Limit value alarm |
Yes |
Diagnostic messages |
● Diagnostics |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● Galvanic isolation analog inputs |
Yes; internal/external |
● between the channels |
Yes |
Permissible potential difference |
between the inputs (UCM) |
120 V AC |
Isolation |
Isolation tested with |
1500 V DC |
Dimensions |
Width |
25 mm |
Height |
290 mm |
Depth |
210 mm |
Weights |
Weight, approx. |
650 g |