6ES7414-2XG03-0AB0 CPU414-2, MPI/DP, 256KB

Product Code: 6ES7414-2XG03-0AB0

Availability: In Stock

Price: $2,784.53
  
 
Artikelnummer 6ES7414-2XG03-0AB0
Input current
from backplane bus 24 V DC, max. Total current consumption of the components connected to the MPI/DP interfaces, but no more than 150 mA per interface
Memory
Load memory
● expandable FEPROM with Memory Card (FLASH)
● expandable RAM with Memory Card (RAM)
Backup
● with battery all data
Battery
Backup battery
● Feeding of external backup voltage to CPU 5 to 15 VDC
CPU-blocks
DB
● Number, max. DB 0 reserved
OB
● Number, max. see instruction list
Counters, timers and their retentivity
S7 counter
Retentivity
— preset Z 0 to Z 7
IEC counter
● Type SFB
S7 times
Retentivity
— preset No retentivity
IEC timer
● Type SFB
Data areas and their retentivity
retentive data area, total Total working and load memory (with backup battery)
Flag
● Retentivity available from MB 0 to MB 8191
● Retentivity preset MB 0 to MB 15
● Number of clock memories 1 memory byte
Data blocks
● Number, max. DB 0 reserved
Address area
Process image
● Inputs, adjustable adjustable at the expense of the code area of the RAM
● Outputs, adjustable adjustable at the expense of the code area of the RAM
Hardware configuration
Expansion devices, max. of which 6 ER with K-bus
connectable OPs 31 without message processing, 8 with message processing
Multicomputing 4 CPUs max. (with UR1 or UR2)
Interface modules
● Number of connectable IM 463s, max. IM 463-2
Number of DP masters
● Mixed mode IM + CP permitted IM 467 cannot be used jointly with CP 443-5 Ext.
Number of operable FMs and CPs (recommended)
● FM Limited by number of slots and number of connections
● CP, point-to-point limited by number of slots
● CP, LAN limited by number of connections
● PROFIBUS and Ethernet CPs incl. CP 443-5 Ext. and IM 467
1st interface
Physics RS 485 / PROFIBUS
Number of connection resources MPI: 32, DP: 16
DP slave
Services
— PG/OP communication with interface active
— Routing with interface active
2nd interface
Physics RS 485 / PROFIBUS
Number of connection resources 16
DP master
Address area
— Address area, max. 6 Kbytes/6 Kbytes
DP slave
Services
— Routing with interface active
Isochronous mode
shortest clock pulse 2.5 ms without using the SFCs 126 / 127
Communication functions
S5-compatible communication
● supported via CP and FC AG_SEND and FC AG_RECV
Standard communication (FMS)
● supported Via CP and loadable FB
Number of connections
● overall of which one is reserved for PG and OP
last modified: 08.09.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: