6ES7151-8AB00-0AB0 ET200S, IM151-8 PN/DP CPU, 128 KB

Product Code: 6ES7151-8AB00-0AB0

Availability: In Stock

Price: $383.60
  
 
Artikelnummer 6ES7151-8AB00-0AB0
SIMATIC DP, IM151-8 PN/DP CPU FOR ET200S, 128 KB WORKING MEMORY, INT. PROFINET INTERFACE (WITH THREE RJ45 PORTS) AS IO-CONTROLER, W/O BATTERY MMC REQUIRED
Product type designation
General information
Hardware product version 01
Firmware version V2.7
Engineering with
● Programming package STEP7 V5.4 SP4 or higher
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; against destruction
External protection for supply cables (recommendation) 24 V DC/16 A miniature circuit breaker with type B and C tripping characteristics. Note: The 24 V DC/16 A miniature circuit breaker with type B tripping characteristics trips before the device protection fuse. The 24 V DC/16 A miniature circuit breaker with type C tripping characteristics trips
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Inrush current, max. 1.8 A; Typical
I²t 0.21 A²·s
from supply voltage 1L+, max. 380 mA; 460 mA with DP master module
Output current
Current output to backplane bus (DC 5 V), max. 700 mA
Power losses
Power loss, typ. 5.5 W
Memory
Work memory
● Integrated 128 kbyte; For program and data
● expandable No
● Size of retentive memory for retentive data blocks 64 kbyte
Load memory
● pluggable (MMC) Yes
● pluggable (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
Backup
● present Yes; Ensured by SIMATIC Micro Memory Card (maintenance-free)
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
● Number, max. 511; Number range: 1 to 511
● Size, max. 64 kbyte
FB
● Number, max. 1 024; Number range: 0 to 2047
● Size, max. 64 kbyte
FC
● Number, max. 1 024; Number range: 0 to 2047
● Size, max. 64 kbyte
OB
● Description See S7-300 operation list
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 1; OB 20
● Number of time interrupt OBs 1; OB 35
● Number of process alarm OBs 1; OB 40
● Number of DPV1 alarm OBs 3; OB 55, 56, 57
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for centralized I/O and PROFINET IO)
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 16
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
of which retentive without battery
— can be set Yes
— lower limit 0
— upper limit 255
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
— preset Z 0 to Z 7
Counting range
— can be set Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
of which retentive without battery
— can be set Yes
— lower limit 0
— upper limit 255
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
Flag
● Number, max. 256 byte
● Retentivity available Yes
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 511; Number range: 1 to 511
● Size, max. 64 kbyte
● Retentivity adjustable Yes; via non-retain property on DB
● Retentivity preset Yes
Local data
● per priority class, max. 510 byte; per priority class
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
of which, distributed
— Inputs 2 048 byte
— Outputs 2 048 byte
Process image
● Inputs, adjustable 2 048 byte
● Outputs, adjustable 2 048 byte
● Inputs, default 128 byte
● Outputs, default 128 byte
Subprocess images
● Number of subprocess images, max. none
Digital channels
● Inputs 16 336
● Outputs 16 336
● Inputs, of which central 496
● Outputs, of which central 496
Analog channels
● Inputs 1 021
● Outputs 1 021
● Inputs, of which central 124
● Outputs, of which central 124
Hardware configuration
Number of modules per system, max. 63; Centralized
Mounting rail
● Number of mounting rails that can be used 1
● Max. length of mounting rail Station width: <= 1 m or < 2 m
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Deviation per day, max. 10 s
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Behavior of the clock following expiry of backup period Clock continues to run with the time at which the power failure occurred
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master No
● to MPI, slave No
● to DP, master Yes; With DP master module
● to DP, slave Yes; With DP master module
● in AS, master No
● in AS, slave No
● on Ethernet via NTP Yes; As client
Interfaces
Number of USB interfaces 0
Number of parallel interfaces 0
Number of other interfaces 0
PROFINET IO
● Number of PROFINET interfaces 1
WLAN
● Number of wireless interfaces 0
1st interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
Integrated switch Yes
Number of ports 3; RJ45
Automatic detection of transmission speed Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
● MPI No
● DP master No
● DP slave No
● PROFINET IO Device No
● PROFINET IO Controller Yes
● PROFINET CBA Yes
● Open IE communication Yes
● Web server Yes
— Number of HTTP clients 5
● Point-to-point connection No
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s; full duplex
● Number of connectable IO devices, max. 128
● Max. number of connectable IO devices for RT 128
— of which in line, max. 128
● Number of IO devices with IRT and the option "high flexibility" 128
— of which in line, max. 61
● IRT, supported Yes
● Prioritized startup supported Yes
— Number of IO Devices, max. 32
● Activation/deactivation of IO Devices Yes
— Maximum number of IO devices that can be activated/deactivated at the same time. 8
● IO Devices changing during operation (partner ports), supported Yes
— Max. number of IO devices per tool 8
● Device replacement without swap medium Yes
● Send cycles Adjustable: 250 µs, 500 µs and 1 ms
● Updating time Minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the number of configured user data items.
● Updating times 250 µs - 128 ms (with signal cycle 250 µs); 500 µs - 256 ms (with signal cycle 500 µs); 1 ms - 512 ms (with signal cycle 1 ms)
Services
— PG/OP communication Yes
— Routing Yes; With DP master module
— S7 communication Yes; with loadable FBs
— Isochronous mode No
— Open IE communication Yes; Via TCP/IP, ISO on TCP, and UDP
Address area
— Inputs, max. 2 kbyte
— Outputs, max. 2 kbyte
— User data consistency, max. 254 byte; with PROFINET I/O
PROFINET CBA
● acyclic transmission Yes
● Cyclic transmission Yes
Open IE communication
● Open IE communication, supported Yes; Via TCP/IP, ISO on TCP, and UDP
● Number of connections, max. 8
● Local port numbers used at the system end 0, 20, 21, 23, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535
2nd interface
Interface type External interface via master module 6ES7138-4HA00-0AB0
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. No
Functionality
● MPI No
● DP master Yes
● DP slave No
● PROFINET IO Controller No
● PROFINET IO Device No
● PROFINET CBA No
● Open IE communication No
● Web server No
● Point-to-point connection No
DP master
● Number of connections, max. 12; Notice: 12 connections per CPU, not per interface
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32; Per station
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Equidistance mode support Yes
— Isochronous mode No
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Number of DP slaves that can be simultaneously activated/deactivated, max. 8
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 Yes
Address area
— Inputs, max. 2 048 byte
— Outputs, max. 2 048 byte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Communication functions
PG/OP communication Yes
Data record routing Yes; With DP master module
Global data communication
● supported No
S7 basic communication
● supported Yes; I blocks
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte
S7 communication
● supported Yes
● as server Yes
● As client Yes; via integrated PROFINET interface and loadable FBs
● User data per job, max. 180 byte
● User data per job (of which consistent), max. 64 byte
S5-compatible communication
● supported No
Standard communication (FMS)
● supported No
Open IE communication
● TCP/IP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 8
— Data length for connection type 01H, max. 1 460 byte
— Data length for connection type 11H, max. 8 192 byte
● ISO-on-TCP (RFC1006) Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 8
— Data length, max. 8 192 byte
● UDP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 8
— Data length, max. 1 472 byte
Web server
● supported Yes
● Number of HTTP clients 5
PROFINET CBA (at set setpoint communication load)
● Setpoint for the CPU communication load 50 %
● Number of remote interconnection partners 32
● Number of functions, master/slave 30
● Total of all Master/Slave connections 1 000
● Data length of all incoming connections master/slave, max. 4 000 byte
● Data length of all outgoing connections master/slave, max. 4 000 byte
● Number of device-internal and PROFIBUS interconnections 500
● Data length of device-internal und PROFIBUS interconnections, max. 4 000 byte
● Data length per connection, max. 1 400 byte
Remote interconnections with acyclic transmission
— Sampling frequency: Sampling time, min. 500 ms
— Number of incoming interconnections 100
— Number of outgoing interconnections 100
— Data length of all incoming interconnections, max. 2 000 byte
— Data length of all outgoing interconnections, max. 2 000 byte
— Data length per connection, max. 1 400 byte
Remote interconnections with cyclic transmission
— Transmission frequency: Transmission interval, min. 1 ms
— Number of incoming interconnections 200
— Number of outgoing interconnections 200
— Data length of all incoming interconnections, max. 2 000 byte
— Data length of all outgoing interconnections, max. 2 000 byte
— Data length per connection, max. 250 byte
HMI variables via PROFINET (acyclic)
— Number of stations that can log on for HMI variables (PN OPC/iMap) 3; 2x PN OPC/1x iMap
— HMI variable updating 500 ms
— Number of HMI variables 200
— Data length of all HMI variables, max. 2 000 byte
PROFIBUS proxy functionality
— supported Yes
— Number of linked PROFIBUS devices 16
— Data length per connection, max. 240 byte; Slave-dependent
Number of connections
● overall 12
● usable for PG communication 11
— reserved for PG communication 1
— Adjustable for PG communication, min. 1
— Adjustable for PG communication, max. 11
● usable for OP communication 11
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 11
● usable for S7 basic communication 10
— Reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 10
● usable for S7 communication 10; with loadable FBs
— Adjustable for S7 communication, max. 10
● Max. total number of instances 32
● usable for routing 4; With DP master module
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes; ALARM_S, ALARM_SC, ALARM_SQ, ALARM_D, ALARM_DQ
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
● Force, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 500
— can be set No
— Of which powerfail-proof 100; Only the last 100 entries are retained
Interrupts/diagnostics/status information
Alarms
● Alarms Yes
Diagnostic messages
● Diagnostic functions Yes
Diagnostics indication LED
● Bus activity PROFINET P1-LINK (green) Yes
● Bus activity PROFINET P2-LINK (green) Yes
● Bus activity PROFINET P3-LINK (green) Yes
● Bus error (red) Yes
● Maintenance information MT (yellow) Yes
● Group error SF (red) Yes
● Monitoring 24 V voltage supply ON (green) Yes
Galvanic isolation
between load voltage and all other switching components Yes
between PROFIBUS DP and all other circuit components Yes
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Degree and class of protection
IP (rear) IP20
Configuration
Configuration software
● STEP 7 Yes; V5.4 SP4
programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes; Optional
— CFC Yes; Optional
— GRAPH Yes; Optional
— HiGraph® Yes; Optional
Know-how protection
● User program protection/password protection Yes
Cycle time monitoring
● lower limit 1 ms
● upper limit 6 000 ms
● can be set Yes
● preset 150 ms
Dimensions
Width 120 mm; DP master module: 35 mm
Height 119.5 mm
Depth 75 mm
Weights
Weight, approx. 320 g; DP master module: Approx. 100 g
last modified: 13.10.2014