6ES7143-3BH00-0XA0 ET200ECO, BM143, 8DI/DO, 2A

Product Code: 6ES7143-3BH00-0XA0

Availability: In Stock

Price: $135.63
  
 
Artikelnummer 6ES7143-3BH00-0XA0
SIMATIC DP, BASIC MODULE BM143 ET 200ECO: 8DI/8DO, 2A; 8 X M12,DOUBLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY
General information
Vendor identification (VendorID) 80DCh
Supply voltage
Load voltage 1L+
● Rated value (DC) 24 V
● Reverse polarity protection No
Load voltage 2L+
● Rated value (DC) 24 V
● Reverse polarity protection No
Input current
from load voltage 2L+ (without load), max. 60 mA; Typical
from supply voltage 1L+, max. 70 mA; Typical
Encoder supply
Number of outputs 8
Output voltage 24 V DC
short-circuit protection Yes; Electronic
Output current
● Rated value 0.75 A; up to 55°C max. 0.75 A (summation current)
Power losses
Power loss, typ. 5 W
Digital inputs
Number of digital inputs 8
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
● Number of simultaneously controllable inputs 8; All mounting positions up to 55 °C
Input voltage
● Type of input voltage DC
● Rated value, DC 24 V
● for signal "0" -3 to +5V
● for signal "1" 13 to 30 V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max. 3 ms; Typical
— at "1" to "0", max. 3 ms; Typical
Digital outputs
Number of digital outputs 8
short-circuit protection Yes
● Response threshold, typ. 4 A per channel
Limitation of inductive shutdown voltage to 2L+ (-44 V)
Controlling a digital input Yes
Switching capacity of the outputs
● Lamp load, max. 10 W
Load resistance range
● lower limit 12 Ω
● upper limit 4 kΩ
Output voltage
● for signal "1", min. 2L+ (-0,8 V)
Output current
● for signal "1" rated value 2 A
● for signal "1" permissible range for 0 to 55 °C, min. 5 mA
● for signal "1" permissible range for 0 to 55 °C, max. 2.4 A
● for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
● for increased power No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz; to IEC 947-5-1, DC-13
● on lamp load, max. 1 Hz
Aggregate current of outputs (per group)
all mounting positions
— up to 55 °C, max. 4 A; 4 A each for sockets X1, X3, X5, X7 and 4 A each for sockets X2, X4, X6, X8; note the current carrying capacity of the cable
Cable length
● Cable length unshielded, max. 30 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— Permissible quiescent current (2-wire sensor), max. 1.5 mA
Interfaces
PROFIBUS DP
● Transmission rate, max. 12 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 3 / 6 / 12 Mbit/s
Protocols
PROFIBUS DP Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms
● Alarms No
Diagnostic messages
● Diagnostics Yes; Diagnostic information readable
Diagnostics indication LED
● Group error SF (red) Yes
● Status indicator digital output (green) Yes
● Status indicator digital input (green) Yes
● Channel error indicator F (red) No
Galvanic isolation
between PROFIBUS DP and all other circuit components Yes
Galvanic isolation digital inputs
● between the channels No
Galvanic isolation digital outputs
● between the channels No
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 60 mm
Height 210 mm
Depth 28 mm
Weights
Weight, approx. 210 g
last modified: 08.09.2014