6ES7134-4GB62-0AB0 ET200S, EL-MOD., 2AI HS I-4WIRE, 0-20MA

Product Code: 6ES7134-4GB62-0AB0

Availability: In Stock

Price: $169.88
  
 
Artikelnummer 6ES7134-4GB62-0AB0
SIMATIC DP, ELECTRONIC MODULE ET 200S: 2AI HIGH SPEED I-4WIRE 4 - 20MA; 16BIT, 15 MM WIDTH, FOR 4-WIRE TRANSDUCER, CYCLE TIME OF MODULE: 0.1MS, WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Short-circuit protection Yes
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 80 mA; without load
from backplane bus 3.3 V DC, max. 10 mA
Output voltage
Power supply to the transmitters
● present Yes
● short-circuit proof Yes
Encoder supply
Number of outputs 2
Output voltage 24 V
Short-circuit protection Yes
Output current
● Output current, rated value 80 mA; Per channel
● Output current, permissible range 0 to 90 mA
Power loss
Power loss, typ. 1.9 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input current for current input (destruction limit), max. 30 mA
Cycle time (all channels) max. 250 µs
Input ranges
● Voltage No
● Current Yes
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 106 Ω
● -20 to +20 mA Yes
● 4 to 20 mA Yes
Cable length
● Cable length, shielded, max. 200 m
Analog value generation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
Smoothing of measured values
● parameterizable Yes
● Step: None Yes; 1 x cycle time
● Step: Low Yes; 4 x cycle time
● Step: Medium Yes; 16 x cycle time
● Step: High Yes; 32 x cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer No
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.03 %
Temperature error (relative to input range), (+/-) 0.01 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.1 %
Operational error limit in overall temperature range
● Current, relative to input area, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input area, (+/-) 0.2 %
Isochronous mode
Isochronous mode (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Alarms
● Hardware interrupt Yes
Diagnostic messages
● Diagnostic functions Yes
● Diagnostic information readable Yes
● Wire-break Yes; Measuring range 4 to 20 mA only
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Diagnostics wire break At 4 to 20 mA
Measurement type/range 4 to 20 mA, 0 to 20 mA, +/-20 mA
Group diagnostics Yes
Overflow/underflow Yes
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ Yes
Permissible potential difference
between MANA and M internally (UISO) 75 VDC / 60 VAC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 45 g
last modified: 21.08.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: