6ES7134-4GB01-0AB0 ET200S, EL-MOD., 2AI STD I-2DMU, 0-20MA,

Product Code: 6ES7134-4GB01-0AB0

Availability: In Stock

Price: $76.72
  
 
Artikelnummer 6ES7134-4GB01-0AB0
SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AI STAND. I-2DMU 15 MM WIDE, 4 .. 20MA; 13 BIT FOR 2-WIRE TRANSDUCER CYCLE TIME 65 MS/CHANNEL WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes; Destruction limit 35 mA per channel
Input current
from load voltage L+ (without load), max. 80 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 0.6 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input current for current input (destruction limit), max. 40 mA
Cycle time (all channels) max. Number of active channels per module x basic conversion time
Input ranges
● Voltage No
● Current Yes
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), currents
● 4 to 20 mA Yes; on 50 ohms
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit; 4 to 20 mA: 13 bits
● Integration time, ms 16,7 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz 60 / 50 Hz
● Conversion time (per channel) 65 ms; 55 / 65 ms
Smoothing of measured values
● Parameterizable Yes; In four stages by means of digital filtering
● Step: None Yes; 1 x cycle time
● Step: low Yes; 4 x cycle time
● Step: Medium Yes; 32 x cycle time
● Step: High Yes; 64 x cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.05 %
Operational limit in overall temperature range
● Current, relative to input area, (+/-) 0.6 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input area, (+/-) 0.4 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostic messages
● Wire break Yes
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 4 byte
Measurement type/range deactivated / 4 to 20 mA
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ No
Isolation
Isolation checked with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
last modified: 13.10.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: