6ES7134-4GB50-0AB0 ET200S, EL-MOD., 2AI HS I-2DMU, 0-20MA

Product Code: 6ES7134-4GB50-0AB0

Availability: In Stock

Price: $154.13
  
 

SIMATIC DP, ELECTRONIC MODULE 2AI HIGH SPEED I-2WIRE FOR ET 200S, 15 MM WIDE, 4 .. 20MA; 12 BIT, FOR 2-WIRE TRANSDUCER, CYCLE TIME OF THE MODULE: 1MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC) 24 V; From power module
Input current
from load voltage L+ (without load), max. 35 mA
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, typ. 0.8 W
Address area
Address space per module
Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input current for current input (destruction limit), max. 35 mA
Cycle time (all channels) max. 1 ms
Input ranges
Current Yes
Input ranges (rated values), currents
4 to 20 mA Yes
Cable length
Cable length, shielded, max. 200 m
Analog value generation
Measurement principle Actual value encryption
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max. 12 bit
Conversion time (per channel) 0.1 ms
Smoothing of measured values
parameterizable Yes
Step: None Yes
Step: Low Yes
Step: Medium Yes
Step: High Yes
Encoder
Connection of signal encoders
Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.01 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.1 %
Operational error limit in overall temperature range
Current, relative to input area, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
Current, relative to input area, (+/-) 0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min. 70 dB
Interrupts/diagnostics/status information
Diagnostic messages
Wire-break Yes
Group error Yes
Overflow/underflow Yes
Diagnostics indication LED
Group error SF (red) Yes
Parameter
Remark 4 byte
Diagnostics wire break Disable / enable
Measurement type/range deactivated / 4 to 20 mA
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Galvanic isolation
Galvanic isolation analog inputs
between the channels No
between the channels and the backplane bus Yes
between the channels and the load voltage L+ No
Permissible potential difference
between MANA and M internally (UISO) 75 VDC / 60 VAC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
Status Aug 30, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: