6ES7132-1JH00-0XB0 ET200L, EL-BLOCK, 16RO, AC 120V, RELAY

Product Code: 6ES7132-1JH00-0XB0

Availability: In Stock

Price: $449.36
  
 

SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 16 RELAY OUTPUT, 120V AC CAN BE PLUGGED INTO TB16L AC
General information
Vendor identification (VendorID) 0026h
Supply voltage
24 V DC Yes
Reverse polarity protection Yes
Mains buffering
Mains buffering, min. 20 ms
Power losses
Power loss, typ. 25.6 W
Hardware configuration
Rack
Required terminal block TB 16L AC
Digital outputs
Number of digital outputs 16; Relays
Size of motor starter, max. Size 5 to NEMA (up to 40 °C); size 4 to NEMA (up to 60 °C)
Controlling a digital input Yes
Switching capacity of the outputs
Lamp load, max. 50 W
Output voltage
Rated value (AC) 120 V
for signal "1", min. Ua - 1 V
Output current
for signal "1" rated value 2000 mA; Pilot mode
for signal "1" permissible range, min. 10 mA
for signal "1" permissible range, max. 2 A
for signal "1" permissible range for 0 to 60 °C, max. 2 A
for signal "0" residual current, max. 0 mA
Output delay with resistive load
"0" to "1", max. 10 ms
"1" to "0", max. 10 ms
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 10 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 1 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 60 °C, max. 2 A
horizontal installation
up to 40 °C, max. 2000 mA
up to 60 °C, max. 1000 mA
all other mounting positions
up to 40 °C, max. 1 A
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Interfaces
PROFIBUS DP
Transmission rate, max. 1.5 Mbit/s; 9,6 / 19,2 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 3 / 6 Mbit/s
SYNC capability Yes
Direct data exchange (slave-to-slave communication) Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC)
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Alarms
Alarms No
Diagnostic messages
Diagnostic functions Yes
Diagnostics indication LED
Bus fault BF (red) Yes
Status indicator digital output (green) Yes
Status indicator digital input (green) Yes
Monitoring 24 V voltage supply ON (green) Yes
Galvanic isolation
between PROFIBUS DP and all other circuit components Yes
Galvanic isolation digital outputs
between the channels Yes
between the channels and PROFIBUS DP Yes
Isolation
Isolation checked with 1500 V AC
Degree and class of protection
IP20 Yes
Ambient conditions
Operating temperature
horizontal installation, min. 0 °C
horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 5 %
max. relative humidity 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection
Dimensions
Width 191 mm
Height 61 mm
Depth 85.5 mm
Weights
Weight, approx. 302 g