6ES7355-2SH00-0AE0 SIMATIC S7-300, TEMPERATURE

Product Code: 6ES7355-2SH00-0AE0

Availability: In Stock

Price: $491.83
  
 
Artikelnummer 6ES7355-2SH00-0AE0
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 270 mA
from backplane bus 5 V DC, max. 75 mA
Power losses
Power loss, typ. 5.5 W
Power loss, max. 6.9 W
Digital inputs
Number of digital inputs 8
Input characteristic curve in accordance with IEC 61131, type 2 Yes
Input voltage
● Rated value, DC 24 V
Input current
● for signal "1", typ. 7 mA
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Digital outputs
Number of digital outputs 8
short-circuit protection Yes
Controlling a digital input Yes
Switching capacity of the outputs
● Lamp load, max. 5 W
Load resistance range
● lower limit 240 Ω
● upper limit 4 kΩ
Output current
● for signal "1" rated value 0.1 A
● for signal "1" permissible range for 0 to 60 °C, min. 5 mA
● for signal "1" permissible range for 0 to 60 °C, max. 150 mA
● for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
● for logic links Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 100 Hz
Aggregate current of outputs (per group)
all mounting positions
— up to 60 °C, max. 400 mA
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Analog inputs
Number of analog inputs 4
permissible input voltage for voltage input (destruction limit), max. 20 V
permissible input current for current input (destruction limit), max. 40 mA
Input ranges
● Voltage Yes
● Current Yes
● Thermocouple Yes
● Resistance thermometer Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) 100 kΩ
● -1.75 to +11.75 V Yes
● Input resistance (-1.75 to +11.75 V) 100 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 50 Ω
● 0 to 23.5 mA Yes
● Input resistance (0 to 23.5 mA) 50 Ω
● -3.5 to +23.5 mA Yes
● Input resistance (-3.5 to +23.5 mA) 50 Ω
● 4 to 20 mA Yes
● Input resistance (4 to 20 mA) 50 Ω
Input ranges (rated values), thermoelements
● Type B Yes
● Input resistance (Type B) 10 MΩ
● Type E Yes
● Input resistance (Type E) 10 MΩ
● Type J Yes
● Input resistance (type J) 10 MΩ
● Type K Yes
● Input resistance (Type K) 10 MΩ
● Type R Yes
● Input resistance (Type R) 10 MΩ
● Type S Yes
● Input resistance (Type S) 10 MΩ
Input ranges (rated values), resistance thermometer
● Pt 100 Yes
● Input resistance (Pt 100) 10 MΩ
Thermocouple (TC)
Temperature compensation
— internal temperature compensation Yes
— external temperature compensation with Pt100 Yes
Characteristic linearization
● Parameterizable Yes
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 14 bit
● Conversion time (per channel) 100 ms
Settling time
● for resistive load 0.1 ms
● for capacitive load 3.3 ms
● for inductive load 0.5 ms
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 4-wire transducer Yes
Connectable encoders
● 2-wire sensor Yes
— Permissible quiescent current (2-wire sensor), max. 1.5 mA
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.05 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.06 %
● Current, relative to input area, (+/-) 0.06 %
● Resistance thermometer, relative to input area, (+/-) 0.06 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.04 %
● Current, relative to input area, (+/-) 0.04 %
● Resistance thermometer, relative to input area, (+/-) 0.04 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 40 dB
● common mode voltage (USS < 2.5 V) , min. 70 dB
Interrupts/diagnostics/status information
Substitute values connectable Yes
Control technology
Number of closed-loop controllers 4
Galvanic isolation
Galvanic isolation controller
● between the channels No
● between the channels and the backplane bus Yes
Dimensions
Width 80 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 470 g
last modified: 16.09.2014