6ES7355-0VH10-0AE0 SIMATIC S7-300, CONROL MODULE

Product Code: 6ES7355-0VH10-0AE0

Availability: In Stock

Price: $615.13
  
 
FM 355S control module

-
SIMATIC S7-300, CONROL MODULE FM 355 C, 4 CHANNELS, CONTIN. 4 AI + 8 DI + 4 AO INCL. MULTI-LANG CONFIG. PACK., MANUAL AND GETTING STARTED (GER/EN/FR/IT) ON CD-ROM
General information
Consisting of MLFB SWR:6ES73550VH100AE0_01; SWR:6ES73550VH100AE0_02; SWR:6ES73550VH100AE0_03; SWR:6ES73550VH100AE0_04; SWR:6ES73550VH100AE0_05; SWR:6ES73550VH100AE0_06; SWR:6ES73550VH100AE0_07;
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 310 mA; Typ. 260 mA
from backplane bus 5 V DC, max. 75 mA; typ. 50 mA
Power losses
Power loss, typ. 6.5 W
Power loss, max. 7.8 W
Digital inputs
Number of digital inputs 8
Input characteristic curve in accordance with IEC 61131, type 2 Yes
Input voltage
Rated value, DC 24 V
for signal "0" -3 to +5 V
for signal "1" 13 to 30 V
Input current
for signal "1", typ. 7 mA
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Analog inputs
Number of analog inputs 4
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 40 mA
Input ranges
Voltage Yes
Current Yes
Thermocouple Yes
Resistance thermometer Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) 100 kΩ
-1.75 to +11.75 V Yes
Input resistance (-1.75 to +11.75 V) 100 kΩ
-80 mV to +80 mV Yes
Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), currents
0 to 20 mA Yes
Input resistance (0 to 20 mA) 50 Ω
0 to 23.5 mA Yes
Input resistance (0 to 23.5 mA) 50 kΩ
-3.5 to +23.5 mA Yes
Input resistance (-3.5 to +23.5 mA) 50 Ω
4 to 20 mA Yes
Input resistance (4 to 20 mA) 50 kΩ
Input ranges (rated values), thermoelements
Type B Yes
Input resistance (Type B) 10 MΩ
Type J Yes
Input resistance (type J) 10 MΩ
Type K Yes
Input resistance (Type K) 10 MΩ
Type R Yes
Input resistance (Type R) 10 MΩ
Type S Yes
Input resistance (Type S) 10 MΩ
Input ranges (rated values), resistance thermometers
Pt 100 Yes
Input resistance (Pt 100) 10 MΩ
Thermocouple (TC)
Characteristic linearization
for thermocouples Type B, J, K, R, S
Temperature compensation
internal temperature compensation Yes
external temperature compensation with Pt100 Yes
Resistance thermometer (RTD)
Characteristic linearization
for resistance thermometer Pt100 (standard)
Characteristic linearization
Parameterizable Yes
Cable length
Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
0 to 10 V Yes
-10 to +10 V Yes
Output ranges, current
0 to 20 mA Yes
4 to 20 mA Yes
Connection of actuators
for voltage output two-wire connection Yes
for current output two-wire connection Yes
Load impedance (in rated range of output)
with voltage outputs, min. 1 kΩ
with voltage outputs, capacitive load, max. 1 µF
with current outputs, max. 500 Ω
with current outputs, inductive load, max. 1 mH
Cable length
Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog value creation
Measurement principle integrating
Integrations and conversion time/resolution per channel
Resolution with overrange (bit including sign), max. 14 bit; 12 or 14 bit, parameterizable
Conversion time (per channel) 16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz; for 14 bit: 100 ms for 50 and 60 Hz
Settling time
for resistive load 0.2 ms
for capacitive load 3.3 ms
for inductive load 0.5 ms
Encoder
Connection of signal encoders
for voltage measurement Yes
for current measurement as 4-wire transducer Yes
Connectable encoders
2-wire sensor Yes
Permissible quiescent current (2-wire sensor), max. 1.5 mA
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.05 %
Temperature error (relative to input range), (+/-) 0.0050 %/K
Linearity error (relative to output range), (+/-) 0.05 %
Temperature error (relative to output range), (+/-) 0.02 %/K
Operational limit in overall temperature range
Voltage, relative to input area, (+/-) 0.6 %; +/-0.6 to +/-1%
Current, relative to input area, (+/-) 0.6 %; +/-0.6 to +/-1%
Resistance thermometer, relative to input area, (+/-) 0.6 %; +/-0.6 to +/-1%
Voltage, relative to output area, (+/-) 0.5 %
Current, relative to output area, (+/-) 0.6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area, (+/-) 0.4 %; 80 mV: +/-0.6%; 250 to 1000 mV: +/-0.4%; 2.5 to 10 V: +/-0.6%; 3.2 to 20 mA: +/-0.5%
Current, relative to input area, (+/-) 0.4 %; +/-0.4 to +/-0.6 %
Resistance thermometer, relative to input area, (+/-) 0.4 %; +/-0.4 to +/-0.6 %
Voltage, relative to output area, (+/-) 0.3 %
Current, relative to output area, (+/-) 0.5 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min. 40 dB
common mode voltage (USS < 2.5 V) , min. 70 dB
Interrupts/diagnostics/status information
Substitute values connectable Yes; Parameterizable
Control technology
Number of closed-loop controllers 4
Galvanic isolation
Galvanic isolation controller
between the channels No
between the channels and the backplane bus Yes; Optocoupler
Permissible potential difference
between inputs and MANA (UCM) 2.5 V DC
between M internally and the inputs 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Connection method
required front connector 2x 20-pin
Dimensions
Width 80 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 470 g
Status Jun 16, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good