6ES7332-5RD00-0AB0 SIMATIC S7,SM 332 ANALOG OUTPUT

Product Code: 6ES7332-5RD00-0AB0

Availability: In Stock

Price: $458.27
  
 
Artikelnummer 6ES7332-5RD00-0AB0
SIMATIC S7, ANALOG OUTPUT SM 332, OPTICALLY ISOLATED, 4 AO, 0/4 UP TO 20 MA, 20 PIN, FOR SIGNALS FROM HAZARDOUSAREAS CAPABLE OF DIANOST., PTB-TESTED
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 180 mA
from backplane bus 5 V DC, max. 80 mA
Power loss
Power loss, typ. 4 W
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 70 mA
Current output, no-load voltage, max. 14 V
Output ranges, current
● 0 to 20 mA Yes
● 4 to 20 mA Yes
Connection of actuators
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with current outputs, max. 500 Ω
Cable length
● Cable length, shielded, max. 200 m
Analog value generation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 15 bit
● Basic conversion time, ms 2,5 ms
Errors/accuracies
Operational error limit in overall temperature range
● Current, relative to output area, (+/-) 0.55 %
Basic error limit (operational limit at 25 °C)
● Current, relative to output area, (+/-) 0.2 %
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic functions Yes
● Diagnostic information readable Yes
● Overrange Yes
● Wire-break in actuator cable Yes
● Group error Yes
Diagnostics indication LED
● Short-circuit per channel (red) Yes
● Short-circuit group error (red) Yes
Ex(i) characteristics
Module for Ex(i) protection Yes
Galvanic isolation
Galvanic isolation analog outputs
● Galvanic isolation analog outputs Yes
Permissible potential difference
between outputs and MANA (UCM) 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
between the outputs (UCM) 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Standards, approvals, certificates
Use in hazardous areas
● Type of protection acc. to EN 50020 (CENELEC) [EEx ib] IIC
● Type of protection acc. to FM Class I, Division 2, Group A, B, C, D T4
● Test number PTB Ex-96.D.2026X
Ambient conditions
Operating temperature
● max. 60 °C
Connection method
required front connector 20-pin
Weights
Weight, approx. 280 g