6ES7331-1KF00-0AB0 SIMATIC S7-300, ANALOG INPUT

Product Code: 6ES7331-1KF00-0AB0

Availability: In Stock

Price: $337.71
  
 
Artikelnummer 6ES7331-1KF00-0AB0
SIMATIC S7-300, ANALOG INPUT SM 331, OPTICALLY ISOLATED, 8 AI, 13 BIT RESOLUTION, U/I/RESISTANCE, PT100, 66 MS MODULE UPDATE, 40 PIN
Input current
from backplane bus 5 V DC, max. 90 mA
Power losses
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 8
Number of analog inputs for resistance measurement 8
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 40 mA; Protection available against destruction
Input ranges
● Voltage Yes
● Current Yes
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) 100 kΩ
● 1 to 5 V Yes
● Input resistance (1 to 5 V) 100 kΩ
● -1 V to +1 V Yes
● Input resistance (-1 V to +1 V) 10 MΩ
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV Yes
● Input resistance (-50 mV to +50 mV) 10 MΩ
● -500 mV to +500 mV Yes
● Input resistance (-500 mV to +500 mV) 10 MΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 50 Ω
● -20 to +20 mA Yes
● Input resistance (-20 to +20 mA) 50 Ω
● 4 to 20 mA Yes
● Input resistance (4 to 20 mA) 50 Ω
Input ranges (rated values), resistance thermometer
● Pt 100 Yes; Standard/climate
● Input resistance (Pt 100) 10 MΩ
Input ranges (rated values), resistors
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 6000 ohms Yes
● Input resistance (0 to 6000 ohms) 10 MΩ
Thermocouple (TC)
Temperature compensation
— Parameterizable No
Characteristic linearization
● Parameterizable
— for resistance thermometer Pt100 (standard/climate)
Cable length
● Cable length, shielded, max. 200 m; 50 m at 50 mV
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit; Unipolar: 13/13 bits; bipolar: 12 bits + sign/12 bits + sign
● Integration time, ms 16,67 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz 60 / 50 Hz
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer Yes; with external supply
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes; with 3-wire compensation
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.6 %
● Current, relative to input area, (+/-) 0.6 %
● Resistance thermometer, relative to input area, (+/-) 0.6 %; +/-1,2 K
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.4 %
● Current, relative to input area, (+/-) 0.4 %
● Resistance thermometer, relative to input area, (+/-) 0.4 %; +/- 1 K
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm No
● Limit value alarm No
Diagnostic messages
● Diagnostics No
Galvanic isolation
Galvanic isolation analog inputs
● between the channels and the backplane bus Yes
Isolation
Isolation checked with 600 V DC
Connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 250 g
last modified: 14.10.2014