6ES7331-1KF01-0AB0 SM331, 8AI, 13BIT

Product Code: 6ES7331-1KF01-0AB0

Availability: In Stock

Price: $258.25
  
 
Artikelnummer 6ES7331-1KF01-0AB0
SIMATIC S7-300, ANALOG INPUT SM 331, OPTICALLY ISOLATED, 8 AI, 13 BIT RESOLUTION, U/I/RESISTANCE/PT100, NI100, NI1000, LG-NI1000, 66 MS MODULE UPDATE, 1 X 40 PIN
Analog inputs
Number of analog inputs 8
Input ranges
● Voltage Yes
● Current Yes
● Thermocouple No
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) 100 kΩ
● 1 to 5 V Yes
● Input resistance (1 to 5 V) 100 kΩ
● 1 to 10 V No
● -1 V to +1 V Yes
● Input resistance (-1 V to +1 V) 100 kΩ
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V No
● -250 mV to +250 mV No
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV Yes
● Input resistance (-50 mV to +50 mV) 100 kΩ
● -500 mV to +500 mV Yes
● Input resistance (-500 mV to +500 mV) 100 kΩ
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 50 Ω
● -10 to +10 mA No
● -20 to +20 mA Yes
● Input resistance (-20 to +20 mA) 50 Ω
● -3.2 to +3.2 mA No
● 4 to 20 mA Yes
● Input resistance (4 to 20 mA) 50 Ω
Input ranges (rated values), thermoelements
● Type B No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Ni 100 Yes; Standard/climate
● Input resistance (Ni 100) 100 MΩ
● Ni 1000 Yes
● Input resistance (Ni 1000) 100 MΩ
● LG-Ni 1000 Yes; Standard/climate
● Input resistance (LG-Ni 1000) 100 MΩ
● Ni 120 No
● Ni 200 No
● Ni 500 No
● Pt 100 Yes; Standard/climate
● Input resistance (Pt 100) 100 MΩ
● Pt 1000 No
● Pt 200 No
● Pt 500 No
Input ranges (rated values), resistors
● 0 to 150 ohms No
● 0 to 300 ohms No
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 100 MΩ
● 0 to 6000 ohms Yes
● Input resistance (0 to 6000 ohms) 100 MΩ
Characteristic linearization
● Parameterizable Yes
— for resistance thermometer yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con.
Analog value creation
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit
● Integration time, parameterizable Yes; 60 / 50 ms
● Basic conversion time, ms 66 / 55 ms
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer Yes; with external supply
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm No
● Limit value alarm No
Diagnostic messages
● Diagnostic functions No
● Diagnostic information readable No
● Diagnostics No
● Group error No
Diagnostics indication LED
● Group error SF (red) No
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
Connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 250 g
last modified: 25.09.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good