6ES7317-6FF03-0AB0 CPU317F-2DP, 1024 KB

Product Code: 6ES7317-6FF03-0AB0

Availability: In Stock

Price: $2,240.64
  
 
CPU 317F-2 DP

-
SIMATIC S7-300, CPU 317F-2DP, CENTRAL PROCESSING UNIT WITH 1024 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, MICRO MEMORY CARD NECESSARY FOR USE WITH SOFTWARE OPTION S7 DISTRIBUTED SAFETY V5.2 SP1 AND HIGHER
General information
Hardware product version 01
Firmware version V2.6
Engineering with
Programming package STEP 7 V5.2 SP1 or higher with hardware update; S7 Distributed Safety V5.2 SP1 or higher
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2 A min.
Input current
Current consumption (in no-load operation), typ. 100 mA
Inrush current, typ. 2.5 A
I²t 1 A²·s
Power loss
Power loss, typ. 4 W
Memory
Type of memory other
Work memory
integrated 1024 kbyte
expandable No
Load memory
Plug-in (MMC) Yes
Plug-in (MMC), max. 8 Mbyte
Data management on MMC (after last programming), min. 10 a
Backup
present Yes; Guaranteed by MMC (maintenance-free)
without battery Yes; Program and data
CPU processing times
for bit operations, typ. 0.05 µs
for bit operations, max. 0.05 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 0.2 µs
for floating point arithmetic, typ. 1 µs
CPU-blocks
Number of blocks (total) 2048; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max. 2047; Number band: 1 to 2047
Size, max. 64 kbyte
FB
Number, max. 2048; Number range: 0 to 2047
Size, max. 64 kbyte
FC
Number, max. 2048; Number range: 0 to 2047
Size, max. 64 kbyte
OB
Description see instruction list
Size, max. 64 kbyte
Number of free cycle OBs 1; OB 1
Number of time alarm OBs 1; OB 10
Number of delay alarm OBs 2; OB 20, 21
Number of time interrupt OBs 4; OB 32, 33, 34, 35
Number of process alarm OBs 1; OB 40
Number of DPV1 alarm OBs 3; OB 55, 56, 57
Number of isochronous mode OBs 1; OB 61
Number of startup OBs 1; OB 100
Number of asynchronous error OBs 5; OB 80, 82, 85, 86, 87
Number of synchronous error OBs 2; OB 121, 122
Nesting depth
per priority class 16
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 512
of which retentive without battery
adjustable Yes
preset 8
Retentivity
adjustable Yes
lower limit 0
upper limit 511
preset 8
Counting range
adjustable Yes
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
S7 times
Number 512
of which retentive without battery
adjustable Yes
lower limit 0
upper limit 511
Retentivity
adjustable Yes
lower limit 0
upper limit 511
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, max. 256 KB
Flag
Number, max. 4096 byte
Retentivity available Yes; From MB 0 to MB 4095
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Data blocks
Number, max. 2047; from DB 1 to DB 2047
Size, max. 64 kbyte
Retentivity adjustable Yes; via non-retain property on DB
Retentivity preset Yes
Local data
per priority class, max. 1024 byte
Address area
I/O address area
Inputs 8 kbyte
Outputs 8 kbyte
of which distributed
Inputs 8 kbyte
Outputs 8 kbyte
Process image
Inputs 1024 byte
Outputs 1024 byte
Digital channels
Inputs 65536
Outputs 65536
Inputs, of which central 1024
Outputs, of which central 1024
Analog channels
Inputs 4096
Outputs 4096
Inputs, of which central 256
Outputs, of which central 256
Hardware configuration
Expansion devices, max. 3
Number of DP masters
integrated 2
via CP 4
Number of operable FMs and CPs (recommended)
FM 8
CP, point-to-point 8
CP, LAN 10
Rack
Racks, max. 4
Modules per rack, max. 8
Time of day
Clock
Hardware clock (real-time clock) Yes
battery-backed and synchronizable Yes
Deviation per day, max. 10 s
Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
Number 4
Number/Number range 0 to 3
Range of values 0 to 2^31 hours (when using SFC 101)
Granularity 1 hour
retentive Yes; Must be restarted at each restart
Clock synchronization
supported Yes
to MPI, master Yes
to MPI, slave Yes
to DP, master Yes; With DP slave only slave clock
to DP, slave Yes
in AS, master Yes
in AS, slave Yes
Digital inputs
integrated channels (DI) 0
Digital outputs
integrated channels (DO) 0
Analog inputs
integrated channels (AI) 0
Analog outputs
integrated channels (AO) 0
Interfaces
Number of parallel interfaces 0
Number of 20 mA interfaces (TTY) 0
Number of RS 232 interfaces 0
Number of RS 422 interfaces 0
Number of other interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
MPI Yes
DP master Yes
DP slave Yes
Point-to-point connection No
MPI
Number of connections 32
Transmission rate, max. 12 Mbit/s
Services
PG/OP communication Yes
Routing Yes
Global data communication Yes
S7 basic communication Yes
S7 communication Yes
S7 communication, as client No
S7 communication, as server Yes
DP master
Transmission rate, max. 12 Mbit/s
Number of DP slaves, max. 124
Services
PG/OP communication Yes
Routing Yes
Global data communication No
S7 basic communication Yes
S7 communication Yes
S7 communication, as client No
S7 communication, as server Yes
Equidistance mode support Yes
Isochronous mode No
SYNC/FREEZE Yes
Activation/deactivation of DP slaves Yes
DPV1 Yes
Address area
Inputs, max. 244 byte
Outputs, max. 244 byte
DP slave
Transmission rate, max. 12 Mbit/s
Automatic baud rate search Yes; only with passive interface
Address area, max. 32
User data per address area, max. 32 byte
Services
Routing Yes; Only with active interface
Global data communication No
S7 basic communication Yes
S7 communication Yes
S7 communication, as client No
S7 communication, as server Yes
Direct data exchange (slave-to-slave communication) Yes
DPV1 No
Transfer memory
Inputs 244 byte
Outputs 244 byte
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
MPI No
DP master Yes
DP slave Yes
Point-to-point connection No
DP master
Number of connections, max. 32
Transmission rate, max. 12 Mbit/s
Number of DP slaves, max. 124
Services
PG/OP communication Yes
Routing Yes
Global data communication No
S7 basic communication Yes
S7 communication Yes
S7 communication, as client No
S7 communication, as server Yes
Equidistance mode support Yes
Isochronous mode Yes; OB 61
SYNC/FREEZE Yes
Activation/deactivation of DP slaves Yes
DPV1 Yes
Address area
Inputs, max. 244 byte
Outputs, max. 244 byte
DP slave
Number of connections 32
GSD file The latest GSD file is available at: http://www.siemens.com/profibus-gsd
Transmission rate, max. 12 Mbit/s
Automatic baud rate search Yes; only with passive interface
Address area, max. 32
User data per address area, max. 32 byte
Services
PG/OP communication Yes
Routing Yes; with interface active
Global data communication No
S7 basic communication Yes
S7 communication Yes
S7 communication, as client No
S7 communication, as server Yes
Direct data exchange (slave-to-slave communication) Yes
DPV1 No
Transfer memory
Inputs 244 byte
Outputs 244 byte
Communication functions
PG/OP communication Yes
Global data communication
supported Yes
Number of GD loops, max. 8
Number of GD packets, max. 8
Number of GD packets, transmitter, max. 8
Number of GD packets, receiver, max. 8
Size of GD packets, max. 22 byte
Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
supported Yes
User data per job, max. 76 byte
User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supported Yes
as server Yes
as client Yes; Via CP and loadable FB
User data per job, max. 180 byte; With PUT/GET
User data per job (of which consistent), max. 160 byte; as server
S5 compatible communication
supported Yes; via CP and loadable FC
Number of connections
overall 32
usable for PG communication 31
reserved for PG communication 1
adjustable for PG communication, min. 1
adjustable for PG communication, max. 31
usable for OP communication 31
reserved for OP communication 1
adjustable for OP communication, min. 1
adjustable for OP communication, max. 31
usable for S7 basic communication 30
reserved for S7 basic communication 0
adjustable for S7 basic communication, min. 0
adjustable for S7 basic communication, max. 30
usable for routing 8
S7 message functions
Number of login stations for message functions, max. 32; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 60
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
Status/control variable Yes
Variables Inputs, outputs, memory bits, DB, times, counters
Number of variables, max. 30
of which status variables, max. 30
of which control variables, max. 14
Forcing
Forcing Yes
Forcing, variables Inputs, outputs
Number of variables, max. 10
Diagnostic buffer
present Yes
Number of entries, max. 100
adjustable No
Configuration
Configuration software
STEP 7 Yes; V5.2 SP1 or higher
Programming
Command set see instruction list
Nesting levels 8
System functions (SFC) see instruction list
System function blocks (SFB) see instruction list
Programming language
LAD Yes
FBD Yes
STL Yes
SCL Yes
CFC Yes
GRAPH Yes
HiGraph® Yes
Know-how protection
User program protection/password protection Yes
Dimensions
Width 80 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 460 g
Status Jul 5, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: