6ES7317-6TJ10-0AB0 SIMATIC S7-300, CPU 317T-2 DP,

Product Code: 6ES7317-6TJ10-0AB0

Availability: In Stock

Price: $2,759.87
  
 
Artikelnummer 6ES7317-6TJ10-0AB0
General information
Hardware product version 02
Firmware version CPU: V2.1.0, integrated technology: V3.0.1
Engineering with
● Programming package STEP 7 V 5.2 SP1 or higher with HF1 and S7-Technology option package
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2 A min.
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection No
Input current
Current consumption (in no-load operation), typ. 200 mA
Inrush current, max. 2.5 A
I²t 1 A²·s
Power loss
Power loss, typ. 6 W
Memory
Work memory
● integrated 512 kbyte
● expandable No
Load memory
● Plug-in (MMC) Yes; min. 4 MB required
● Plug-in (MMC), max. 8 Mbyte
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
Battery
Backup battery
● Backup time, max. 10 y; Data retention on the MMC (after last programming)
CPU processing times
for bit operations, typ. 0.05 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 0.2 µs
for floating point arithmetic, typ. 1 µs
CPU-blocks
DB
● Number, max. 2 047; DB 0 reserved
● Size, max. 64 kbyte
FB
● Number, max. 2 048; see instruction list
● Size, max. 64 kbyte
FC
● Number, max. 2 048; see instruction list
● Size, max. 64 kbyte
OB
● Number, max. see instruction list
● Size, max. 64 kbyte
Nesting depth
● per priority class 16
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 512
of which retentive without battery
— adjustable Yes
— preset Z 0 to Z 7
Counting range
— adjustable Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 512
Retentivity
— adjustable Yes
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total 2048 (DBs, FCs, FBs). The maximum number of loadable blocks can be reduced by the MMC that you use.
Flag
● Number, max. 4 096 byte
● Retentivity available Yes; From MB 0 to MB 4095
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 2 047; DB 0 reserved
● Size, max. 64 kbyte
● Retentivity adjustable Yes
Local data
● per priority class, max. 1 024 byte
Address area
I/O address area
● Inputs 8 kbyte
● Outputs 8 kbyte
of which distributed
— Inputs 8 kbyte
— Outputs 8 kbyte
Process image
● Inputs 256 byte
● Outputs 256 byte
Digital channels
● Inputs 65 636
● Outputs 65 636
● Inputs, of which central 256
● Outputs, of which central 256
Analog channels
● Inputs 4 096
● Outputs 4 096
● Inputs, of which central 64
● Outputs, of which central 64
Hardware configuration
Number of DP masters
● integrated 2
● via CP 2
Number of operable FMs and CPs (recommended)
● FM 8
● CP, point-to-point 8
● CP, LAN 10
Rack
● Racks, max. 1
● Modules per rack, max. 8
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Deviation per day, max. 10 s
● Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
● Number 4
● Number/Number range 0 to 3
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● in AS, master Yes
● in AS, slave Yes
Digital inputs
Number of digital inputs 4
Functions technological functions, e.g. reference point detection (BERO); digital inputs can also be used (with restrictions) in STEP 7 user program.
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 4
— up to 60 °C, max. 4
Input voltage
● Rated value, DC 24 V
● for signal "0" -3 to +5V
● for signal "1" 15 to 30 V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for counter/technological functions
— at "0" to "1", max. 10 µs; Typical
— at "1" to "0", max. 10 µs; Typical
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Digital outputs
Number of digital outputs 8
Functions For technology functions, e.g. high-speed cam switch signals
Short-circuit protection Yes
● Response threshold, typ. 1,0 A
Limitation of inductive shutdown voltage to 2L+ (-48 V)
Controlling a digital input No
Switching capacity of the outputs
● Lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 4 kΩ
Output voltage
● for signal "0", max. 3 V
● for signal "1", min. 2L+ (-2,5 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range for 0 to 60 °C, min. 5 mA
● for signal "1" permissible range for 0 to 60 °C, max. 0.6 A
● for signal "0" residual current, max. 0.3 mA
Parallel switching of 2 outputs
● for uprating No
● for redundant control of a load No
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.2 Hz; to IEC 947-5-1, DC-13
● on lamp load, max. 100 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 4 A
— up to 60 °C, max. 3 mA
all other mounting positions
— up to 40 °C, max. 3 mA
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor No
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● DP master Yes
● DP slave Yes
● Point-to-point connection No
MPI
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client Yes; Via CP and loadable FB
— S7 communication, as server Yes
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— Equidistance mode support Yes
— SYNC/FREEZE Yes
— DPV1 Yes
Address area
— Inputs, max. 244 kbyte
— Outputs, max. 244 kbyte
DP slave
● Transmission rate, max. 12 Mbit/s
● automatic baud rate search No
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI No
● DP master Yes; DP(DRIVE)-Master
● DP slave No
● Point-to-point connection No
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32
Services
— PG/OP communication No
— Routing No
— Global data communication No
— S7 basic communication No
— S7 communication No
— Equidistance mode support Yes
— SYNC/FREEZE No
— Activation/deactivation of DP slaves No
— DPV1 No
Address area
— Inputs, max. 244 kbyte
— Outputs, max. 244 kbyte
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD loops, max. 8
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● as client Yes; Via CP and loadable FB
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 160 byte; as server
S5 compatible communication
● supported Yes; via CP and loadable FC
Number of connections
● overall 32
● usable for PG communication 31
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 31
● usable for OP communication 31
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 31
● usable for S7 basic communication 30
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 30
S7 message functions
Number of login stations for message functions, max. 32; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 60
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— adjustable No
Interrupts/diagnostics/status information
Alarms
● Alarms No
Diagnostic messages
● Diagnostic functions No
Diagnostics indication LED
● Status indicator digital output (green) Yes
● Status indicator digital input (green) Yes
Galvanic isolation
Galvanic isolation digital inputs
● between the channels and the backplane bus Yes
Galvanic isolation digital outputs
● between the channels and the backplane bus Yes
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation tested with 500 V DC
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 or higher and S7 Technology option package
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
Dimensions
Width 160 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 750 g
last modified: 21.08.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: