6ES7315-6FF01-0AB0 CPU315F, 192KO

Product Code: 6ES7315-6FF01-0AB0

Availability: In Stock

Price: $1,055.59
  
 
Artikelnummer 6ES7315-6FF01-0AB0
SIMATIC S7-300, CPU 315F CENTRAL UNIT FOR S7-300F, 192 KB WORKING MEM., 40MM WIDE, 384 BYTES PAE/384 BYTES PAA, 2 INTERFACES: 1 MPI UND 1 DP INTEGRATED 24V DC POWER SUPPLY, MICRO MEMORY CARD REQUIRED
Product type designation
General information
Hardware product version 01
Firmware version V2.6
Engineering with
● Programming package STEP 7 V5.2 SP1 or higher with HSP 0126
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
External protection for supply cables (recommendation) 2 A min.
Input current
Current consumption (in no-load operation), typ. 60 mA
Inrush current, typ. 2.5 A
I²t 0.5 A²·s
Power losses
Power loss, typ. 2.5 W
Memory
Type of memory other
Work memory
● Integrated 192 kbyte; The number of F-instructions compared to a standard program is limited due to the F-specific overheads; depending on the type of programming, about 36 K F-instructions are possible.
● expandable No
Load memory
● pluggable (MMC) Yes
● pluggable (MMC), max. 8 Mbyte
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 6 µs
CPU-blocks
Number of blocks (total) 1 024; DBs, FCs, FBs
DB
● Number, max. 1 023; DB 0 reserved
● Size, max. 16 kbyte
FB
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
FC
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
OB
● Size, max. 16 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 1; OB 20
● Number of time interrupt OBs 1; OB 35
● Number of process alarm OBs 1; OB 40
● Number of DPV1 alarm OBs 3; OB 55, 56, 57
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 5; OB 80, 82, 85, 86, 87
● Number of synchronous error OBs 1; OB 121, 122
Nesting depth
● per priority class 8
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
of which retentive without battery
— can be set Yes
— preset Z 0 to Z 7
Counting range
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
Retentivity
— can be set Yes
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
Data areas and their retentivity
retentive data area, total all standard data
Flag
● Number, max. 2 048 byte
● Retentivity available Yes; MB 0 to MB 2047
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 1 023; DB 0 reserved
● Size, max. 16 kbyte
Local data
● per priority class, max. 1 024 byte
Address area
I/O address area
● Inputs 2 kbyte
● Outputs 2 kbyte
of which, distributed
— Inputs 2 kbyte
— Outputs 2 kbyte
Process image
● Inputs 384 byte
● Outputs 384 byte
Digital channels
● Inputs 16 384
● Outputs 16 384
● Inputs, of which central 1 024
● Outputs, of which central 1 024
Analog channels
● Inputs 1 024
● Outputs 1 024
● Inputs, of which central 256
● Outputs, of which central 256
Hardware configuration
Number of DP masters
● Integrated 1
● Via CP 1
Number of operable FMs and CPs (recommended)
● FM 8
● CP, point-to-point 8
● CP, LAN 10
Rack
● Racks, max. 4
● Modules per rack, max. 8
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Deviation per day, max. 10 s
● Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes; With DP slave only slave clock
● to DP, slave Yes
● in AS, master Yes
Digital inputs
integrated channels (DI) 0
Digital outputs
integrated channels (DO) 0
Analog inputs
Integrated channels (AI) 0
Analog outputs
Integrated channels (AO) 0
Interfaces
Number of parallel interfaces 0
Number of 20 mA interfaces (TTY) 0
Number of RS 232 interfaces 0
Number of RS 422 interfaces 0
Number of other interfaces 0
1st interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● DP master No
● DP slave No
● Point-to-point connection No
MPI
● Number of connections 16
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client Yes; Via CP and loadable FB
— S7 communication, as server Yes
2nd interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI No
● DP master Yes
● DP slave Yes
● Point-to-point connection No
DP master
● Number of connections, max. 16
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 125
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— Equidistance mode support Yes
— SYNC/FREEZE Yes
— DPV1 Yes
Address area
— Inputs, max. 244 kbyte
— Outputs, max. 244 kbyte
DP slave
● Number of connections 16
● GSD file The latest GSD file is available at: http://www.siemens.com/profibus-gsd
● Transmission rate, max. 12 Mbit/s
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— PG/OP communication Yes
— Routing Yes; with interface active
— Global data communication No
— S7 basic communication No
— S7 communication, as client No
— S7 communication, as server No
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● As client Yes; Via CP and loadable FB
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 64 byte; as server
S5-compatible communication
● supported Yes; via CP and loadable FC
Number of connections
● overall 16
● usable for PG communication 15
— reserved for PG communication 1
— Adjustable for PG communication, min. 1
— Adjustable for PG communication, max. 15
● usable for OP communication 15
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 15
● usable for S7 basic communication 12
— Reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 12
S7 message functions
Number of login stations for message functions, max. 16; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
● Force, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— can be set No
Configuration
Configuration software
● STEP 7 Yes; V5.1 SP6 or higher
programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
Know-how protection
● User program protection/password protection Yes
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 290 g
last modified: 14.10.2014