6ES7314-1AG14-0AB0 CPU314, 128 KB

Product Code: 6ES7314-1AG14-0AB0

Availability: In Stock

Price: $362.37
  
 
Artikelnummer 6ES7314-1AG14-0AB0
SIMATIC S7-300, CPU 314 CPU WITH MPI INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 128 KBYTE WORKING MEMORY, MICRO MEMORY CARD NECESSARY
General information
Hardware product version 01
Firmware version V3.3
Engineering with
● Programming package STEP 7 V5.5 + SP1 or higher or STEP7 V5.2 + SP1 or higher with HSP 218
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
External protection for supply cables (recommendation) 2 A min.
Mains buffering
● Mains/voltage failure stored energy time 5 ms
● Repeat rate, min. 1 s
Input current
Current consumption (rated value) 650 mA
Current consumption (in no-load operation), typ. 140 mA
Inrush current, typ. 3.5 A
I²t 1 A²·s
Power losses
Power loss, typ. 4 W
Memory
Type of memory other
Work memory
● Integrated 128 kbyte
● expandable No
● Size of retentive memory for retentive data blocks 64 kbyte
Load memory
● pluggable (MMC) Yes
● pluggable (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● without battery Yes; Program and data
CPU processing times
for bit operations, typ. 0.06 µs
for word operations, typ. 0.12 µs
for fixed point arithmetic, typ. 0.16 µs
for floating point arithmetic, typ. 0.59 µs
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
● Number, max. 1 024; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
FC
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
OB
● Description see instruction list
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 2; OB 20, 21
● Number of time interrupt OBs 4; OB 32, 33, 34, 35
● Number of process alarm OBs 1; OB 40
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 4; OB 80, 82, 85, 87
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 16
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
— preset Z 0 to Z 7
Counting range
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, max. 64 KB
Flag
● Number, max. 256 byte
● Retentivity available Yes; MB 0 to MB 255
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 1 024; Number range: 1 to 16000
● Size, max. 64 kbyte
● Retentivity adjustable Yes; via non-retain property on DB
● Retentivity preset Yes
Local data
● per priority class, max. 32 kbyte; Max. 2 KB per block
Address area
I/O address area
● Inputs 1 024 byte
● Outputs 1 024 byte
Process image
● Inputs 1 024 byte
● Outputs 1 024 byte
● Inputs, adjustable 1 024 byte
● Outputs, adjustable 1 024 byte
● Inputs, default 128 byte
● Outputs, default 128 byte
Digital channels
● Inputs 1 024
● Outputs 1 024
● Inputs, of which central 1 024
● Outputs, of which central 1 024
Analog channels
● Inputs 256
● Outputs 256
● Inputs, of which central 256
● Outputs, of which central 256
Hardware configuration
Expansion devices, max. 3
Number of DP masters
● Integrated 0
● Via CP 4
Number of operable FMs and CPs (recommended)
● FM 8
● CP, point-to-point 8
● CP, LAN 10
Rack
● Racks, max. 4
● Modules per rack, max. 8
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Deviation per day, max. 10 s; Typ.: 2 s
● Backup time 6 wk; At 40 °C ambient temperature
● Behavior of the clock following POWER-ON Clock continues running after POWER OFF
● Behavior of the clock following expiry of backup period Clock continues to run with the time at which the power failure occurred
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● in AS, master Yes
● in AS, slave No
Digital inputs
Number of digital inputs 0
Digital outputs
Number of digital outputs 0
Analog inputs
Number of analog inputs 0
Analog outputs
Number of analog outputs 0
Interfaces
Number of USB interfaces 0
Number of parallel interfaces 0
Number of 20 mA interfaces (TTY) 0
Number of RS 232 interfaces 0
Number of RS 422 interfaces 0
Number of other interfaces 0
1st interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● DP master No
● DP slave No
● Point-to-point connection No
MPI
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing No
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes; Only server, configured on one side
— S7 communication, as client No
— S7 communication, as server Yes
Communication functions
PG/OP communication Yes
Data record routing No
Global data communication
● supported Yes
● Number of GD loops, max. 8
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● As client Yes; Via CP and loadable FB
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 240 byte; as server
S5-compatible communication
● supported Yes; via CP and loadable FC
Number of connections
● overall 12
● usable for PG communication 11
— reserved for PG communication 1
— Adjustable for PG communication, min. 1
— Adjustable for PG communication, max. 11
● usable for OP communication 11
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 11
● usable for S7 basic communication 8
— Reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 8
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status block Yes; Up to 2 simultaneously
Single step Yes
Number of breakpoints 4
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
● Force, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 500
— can be set No
— Of which powerfail-proof 100; Only the last 100 entries are retained
● Number of entries readable in RUN, max. 499
— can be set Yes; From 10 to 499
— preset 10
Service data
● Can be read out Yes
Ambient conditions
Operating temperature
● Min. 0 °C
● max. 60 °C
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 or higher with HW update
programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
● Block encryption Yes; With S7 block Privacy
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 280 g
last modified: 25.09.2014