6ES7313-6BE01-0AB0 CPU313C-2 PTP, 16DI/16DO, 32KB

Product Code: 6ES7313-6BE01-0AB0

Availability: In Stock

Price: $687.74
  
 
CPU 313C-2 PtP

-
SIMATIC S7-300, CPU 313C-2 PTP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED INTERFACE RS485, INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD REQUIRED
General information
Hardware product version 01
Firmware version V2.0.0
Engineering with
Programming package STEP 7 V5.2 SP1 or higher (with STEP 7 V5.1 SP3 or higher, please use predecessor CPU)
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (in no-load operation), typ. 100 mA
Inrush current, typ. 11 A
from supply voltage L+, max. 700 mA
Power loss
Power loss, typ. 10 W
Memory
Work memory
integrated 32 kbyte; For program and data
expandable No
Load memory
Plug-in (MMC) Yes
Plug-in (MMC), max. 8 Mbyte
Data management on MMC (after last programming), min. 10 a
Backup
present Yes; Guaranteed by MMC (maintenance-free)
without battery Yes; Program and data
CPU processing times
for bit operations, typ. 0.1 µs
for bit operations, max. 0.2 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1024; (DBs, FCs, FBs OBs, SDBs); the maximum number of loadable blocks can be reduced by the MMC being used.
DB
Number, max. 511; Number range: 1 to 511
Size, max. 16 kbyte
FB
Number, max. 512; Number range: 0 to 2047
Size, max. 16 kbyte
FC
Number, max. 512; Number range: 0 to 2047
Size, max. 16 kbyte
OB
Number, max. see instruction list
Size, max. 16 kbyte
Number of free cycle OBs 1; OB 1
Number of time alarm OBs 1; OB 10
Number of delay alarm OBs 1; OB 20
Number of time interrupt OBs 1; OB 35
Number of process alarm OBs 1; OB 40
Number of startup OBs 1; OB 100
Number of asynchronous error OBs 1; OB 80
Number of synchronous error OBs 2; OB 121, 122
Nesting depth
per priority class 8
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 256
of which retentive without battery
adjustable Yes
lower limit 0
upper limit 256
Counting range
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
S7 times
Number 256
Retentivity
adjustable Yes
lower limit 0
upper limit 256
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total all
Flag
Number, max. 256 byte
Retentivity available Yes; MB 0 to MB 255
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Data blocks
Number, max. 511; from DB1 to DB511
Size, max. 16 kbyte
Retentivity adjustable No
Retentivity preset Yes
Local data
per priority class, max. 510 byte
Address area
I/O address area
Inputs 1 kbyte
Outputs 1 kbyte
Process image
Inputs 128 byte
Outputs 128 byte
Default addresses of the integrated channels
Digital inputs 124.0 to 125.7
Digital outputs 124.0 to 125.7
Digital channels
Inputs 1008
Outputs 1008
Inputs, of which central 992
Outputs, of which central 992
Analog channels
Inputs 248
Outputs 124
Inputs, of which central 248
Outputs, of which central 248
Hardware configuration
Expansion devices, max. 3
Number of DP masters
integrated No
via CP 4
Number of operable FMs and CPs (recommended)
FM 8
CP, point-to-point 8
CP, LAN 6
Rack
Racks, max. 4
Modules per rack, max. 8; In rack 3 max. 7
Time of day
Clock
Hardware clock (real-time clock) Yes
battery-backed and synchronizable Yes
Deviation per day, max. 10 s
Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
Number 1
Number/Number range 0
Range of values 0 to 2^31 hours (when using SFC 101)
Granularity 1 hour
retentive Yes; Must be restarted at each restart
Clock synchronization
supported Yes
to MPI, master Yes
to MPI, slave Yes
in AS, master Yes
Digital inputs
Number of digital inputs 16
integrated channels (DI) 16
Input voltage
Rated value, DC 24 V
for signal "0" -3 to +5 V
for signal "1" 15 to 30 V
Input current
for signal "1", typ. 8 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizable Yes; 0.1 / 0.3 / 3 / 15 ms
for counter/technological functions
at "0" to "1", max. 8 µs
Cable length
Cable length, shielded, max. 1000 m; 100 m for technological functions
Cable length unshielded, max. 600 m
Digital outputs
Number of digital outputs 16
integrated channels (DO) 16
Short-circuit protection Yes; Clocked electronically
Limitation of inductive shutdown voltage to L+ (-48 V)
Output voltage
for signal "1", min. L+ (-0.8 V)
Output current
for signal "1" permissible range for 0 to 40 °C, max. 500 mA
for signal "1" permissible range for 0 to 60 °C, max. 500 mA
for signal "1" minimum load current 5 mA
for signal "0" residual current, max. 0.5 mA
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
Total current of the outputs (per group)
all mounting positions
up to 40 °C, max. 8 A
up to 60 °C, max. 4 A
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Analog inputs
integrated channels (AI) none
Encoder
Connectable encoders
2-wire sensor Yes
permissible quiescent current (2-wire sensor), max. 1.5 mA
Interfaces
MPI
Cable length, max. 50 m; without repeater
Point-to-point
Cable length, max. 1200 m
Integrated protocol driver
3964 (R) Yes
ASCII Yes
Transmission rate, RS 422/485
with 3964 (R) protocol, max. 19.2 kbit/s
with ASCII protocol, max. 19.2 kbit/s
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
MPI Yes
DP master No
DP slave No
Point-to-point connection No
MPI
Number of connections 8
Transmission rate, max. 187.5 kbit/s
Services
PG/OP communication Yes
Routing No
Global data communication Yes
S7 basic communication Yes
S7 communication Yes
S7 communication, as client No
S7 communication, as server Yes
2. Interface
Interface type Integrated RS 422/ 485 interface
Physics RS 422/RS 485 (X.27)
isolated Yes
Power supply to interface (15 to 30 V DC), max. No
Number of connection resources none
Functionality
MPI No
DP master No
DP slave No
Point-to-point connection Yes
DP master
Transmission rate, max. -
Number of DP slaves, max. -
DP slave
Number of connections -
GSD file -
Transmission rate, max. -
Point-to-point connection
Transmission rate, max. 38.4 kbit/s half duplex; 19.2 kbit/s full duplex
Cable length, max. 1200 m
Interface from the user program controllable Yes
Interface can trigger alarm/interrupt in the user program Yes; Message on break - identification
Protocol driver 3964 (R); ASCII
Communication functions
PG/OP communication Yes
Global data communication
supported Yes
Number of GD loops, max. 4
Number of GD packets, max. 4
Number of GD packets, transmitter, max. 4
Number of GD packets, receiver, max. 4
Size of GD packets, max. 22 byte
Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
supported Yes; Server
User data per job, max. 76 byte
User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supported Yes
as server Yes
as client Yes; Via CP and loadable FB
User data per job, max. 180 byte; With PUT/GET
User data per job (of which consistent), max. 64 byte
S5 compatible communication
supported Yes; via CP and loadable FC
Number of connections
overall 8
usable for PG communication 7
reserved for PG communication 1
adjustable for PG communication, min. 1
adjustable for PG communication, max. 7
usable for OP communication 7
reserved for OP communication 1
adjustable for OP communication, min. 1
adjustable for OP communication, max. 7
usable for S7 basic communication 4
reserved for S7 basic communication 4
adjustable for S7 basic communication, min. 0
adjustable for S7 basic communication, max. 4
usable for routing No
S7 message functions
Number of login stations for message functions, max. 8; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 20
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
Status/control variable Yes
Variables Inputs, outputs, memory bits, DB, times, counters
Number of variables, max. 30
of which status variables, max. 30
of which control variables, max. 14
Forcing
Forcing Yes
Forcing, variables Inputs, outputs
Number of variables, max. 10
Integrated Functions
Number of counters 3; 3 channels (see "Technological Functions" manual)
Counting frequency (counter) max. 30 kHz
Frequency measurement Yes
Number of frequency meters 3; 3 channels up to max. 30 kHz (see "Technological Functions" manual)
controlled positioning No
integrated function blocks (closed-loop control) PID controller (see "Technological Functions" manual)
PID controller Yes
Number of pulse outputs 3; 3 channels pulse width modulation up to max. 2.5 kHz (see "Technological Functions" manual)
Limit frequency (pulse) 2.5 kHz
Galvanic isolation
Galvanic isolation digital inputs
Galvanic isolation digital inputs Yes
between the channels, in groups of 16
between the channels and the backplane bus Yes
Galvanic isolation digital outputs
Galvanic isolation digital outputs Yes
between the channels, in groups of 8
between the channels and the backplane bus Yes
Configuration
Configuration software
STEP 7 Yes; V5.1 SP2
Programming
Command set see instruction list
Nesting levels 8
System functions (SFC) see instruction list
System function blocks (SFB) see instruction list
Programming language
LAD Yes
FBD Yes
STL Yes
SCL Yes
GRAPH Yes
HiGraph® Yes
Know-how protection
User program protection/password protection Yes
Dimensions
Width 120 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 566 g
Status Jul 5, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: