SIMATIC WINAC RTX V4.1, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON CD, LICENSE KEY ON FD, CLASS B, 3 LANGUAGES (D,E,F), EXECUTABLE UNDER WIN 2000/XP AND VCI RTX, REFERENCE-HW: SIMATIC PC |
General information |
Firmware version |
4,1 |
Memory |
Work memory |
● Integrated |
PC RAM can be used (non-paged memory) |
Load memory |
● integrated RAM, max. |
PC RAM can be used (non-paged memory) |
CPU processing times |
for bit operations, typ. |
0.013 µs; Typical |
for fixed point arithmetic, typ. |
0.025 µs; Typical |
for floating point arithmetic, typ. |
0.025 µs; Typical |
Reference platform |
Pentium 4, 2.4 GHz |
CPU-blocks |
DB |
● Number, max. |
Limited only by available PC work memory |
● Size, max. |
64 kbyte |
FB |
● Number, max. |
Limited only by available PC work memory |
● Size, max. |
64 kbyte |
FC |
● Number, max. |
Limited only by available PC work memory |
● Size, max. |
64 kbyte |
OB |
● Size, max. |
64 kbyte |
● Number of time alarm OBs |
1 |
● Number of delay alarm OBs |
1 |
● Number of time interrupt OBs |
5 |
● Number of process alarm OBs |
1 |
Nesting depth |
● per priority class |
24 |
● additional within an error OB |
24 |
Counters, timers and their retentivity |
S7 counter |
● Number |
512 |
Retentivity |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
511 |
— preset |
8 |
Counting range |
— can be set |
Yes |
— lower limit |
0 |
— upper limit |
999 |
IEC counter |
● present |
Yes |
● Type |
SFB |
S7 times |
● Number |
512 |
Retentivity |
— lower limit |
0 |
— upper limit |
511 |
— preset |
0 |
Time range |
— lower limit |
10 ms |
— upper limit |
9 990 s |
IEC timer |
● present |
Yes |
● Type |
SFB |
Data areas and their retentivity |
Retentivity without UPS and PS Extension Board |
none |
Retentivity with UPS |
all data |
Flag |
● Number, max. |
2 kbyte |
● of which retentive |
MB 0 to MB 2048 |
● Retentivity preset |
MB 0 to MB 15 |
● Number of clock memories |
8 |
Address area |
I/O address area |
● Inputs |
16 kbyte |
● Outputs |
16 kbyte |
of which, distributed |
— DP interface, inputs |
16 kbyte |
— DP interface, outputs |
16 kbyte |
Process image |
● Inputs, adjustable |
8 kbyte |
● Outputs, adjustable |
8 kbyte |
● Inputs, default |
512 byte |
● Outputs, default |
512 byte |
Subprocess images |
● Number of subprocess images, max. |
15 |
Digital channels |
● Inputs |
131 072 |
● Outputs |
131 072 |
Analog channels |
● Inputs |
8 192 |
● Outputs |
8 192 |
Hardware configuration |
Submodules |
● Number of submodules, max |
4 |
● of which PROFIBUS, max. |
4; CP 5613, CP 5613-A2 |
● of which Industrial Ethernet, max. |
0 |
Number of operable FMs and CPs (recommended) |
● FM |
FM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2 |
● CP, point-to-point |
CP 340, CP 341 distributed |
● CP, LAN |
Over PC CP |
Time of day |
Clock |
● Hardware clock (real-time clock) |
Yes |
● battery-backed and synchronizable |
Yes |
Clock synchronization |
● supported |
No |
Interfaces |
2nd interface |
Interface type |
CP 5613, CP 5613-A2 |
Max. no. of simultaneously operable CPs |
4 |
Physics |
RS 485 / PROFIBUS |
Isolated |
Yes |
Functionality |
● MPI |
No |
● DP master |
Yes |
● DP slave |
No |
DP master |
● Number of connections, max. |
50 |
● Transmission rate, max. |
12 Mbit/s |
● Number of DP slaves, max. |
125 |
Services |
— PG/OP communication |
Yes |
— Routing |
Yes |
— Global data communication |
No |
— S7 basic communication |
No |
— S7 communication |
Yes |
— Equidistance mode support |
Yes |
— SYNC/FREEZE |
Yes |
— Activation/deactivation of DP slaves |
Yes |
— Direct data exchange (slave-to-slave communication) |
Yes |
— DPV0 |
Yes |
— DPV1 |
Yes |
Address area |
— Inputs, max. |
16 kbyte |
— Outputs, max. |
16 kbyte |
User data per DP slave |
— Inputs, max. |
244 byte |
— Outputs, max. |
244 byte |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Number of DP masters with isochronous mode |
2 |
User data per isochronous slave, max. |
128 byte |
equidistance |
Yes |
shortest clock pulse |
2.2 ms; 2.2 ms without partial process image; 2.2 ms with partial process image |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
● supported |
No |
S7 basic communication |
● supported |
No |
S7 communication |
● as server |
Yes |
● As client |
Yes |
Number of connections |
● overall |
64 |
● usable for PG communication |
|
— reserved for PG communication |
1 |
● usable for OP communication |
|
— reserved for OP communication |
1 |
S7 message functions |
Number of login stations for message functions, max. |
64 |
SCAN procedure |
No |
Process diagnostic messages |
Yes; Alarm_S |
Alarm 8-blocks |
No |
Process control messages |
No |
Test commissioning functions |
Status block |
Yes |
Single step |
Yes |
Status/control |
● Status/control variable |
Yes |
Forcing |
● Forcing |
No |
Diagnostic buffer |
● present |
Yes |
● Number of entries, max. |
|
— preset |
120 |
Hardware requirements |
Hardware required |
PC with color monitor, keyboard, mouse or pointing device for Windows |
Main memory, min. |
256 Mbyte |
Required memory on hard disk, min. |
100 Mbyte |
Processor |
Intel Pentium 800 MHz |
● Multi-processor system |
Yes; Dual Pentium |
● Hyper-threading |
Yes; WinAC RTX V4.1, SP1 or higher |
Operating systems |
Configuration |
Configuration software |
● STEP 7 |
Yes; as of V5.2, Engineering Tools (optional) |
programming |
● Nesting levels |
8 |
Programming language |
— LAD |
Yes |
— FBD |
Yes |
— STL |
Yes |
— SCL |
Yes |
— CFC |
Yes |
— GRAPH |
Yes |
— HiGraph® |
Yes |
Software libraries |
— Easy Motion Control |
Yes |
Know-how protection |
● User program protection/password protection |
No |
Open Development interfaces |
● CCX (Custom Code Extension) |
Yes; With WinAC ODK V4.1 |
● CMI (Controller Management Interface) |
Yes; With WinAC ODK V4.1 |
● SMX (Shared Memory Extension) |
Yes; With WinAC ODK V4.1 |
— Inputs |
4 kbyte |
— Outputs |
4 kbyte |
last modified: |
14.10.2014 |