SIMATIC C7-635 KEYS, COMPACT UNIT WITH INTEGRATED COMPONENTS: S7-300 CPU314C-2 DP AND OP170B, 24 DI, 16 DO, 5 AI, 2 AO; MICRO MEMORY CARD AND CONNECTOR SET REQUIRED |
|
Operator control and monitoring |
Password protection |
Yes |
Password levels |
10 |
Text elements |
Yes |
Info texts |
Yes |
Alarms |
Yes; Fault messages, operating messages (no buffer) |
Graphics object |
Process images |
Yes |
Graphics object |
Yes |
Process images |
Number of process images |
100 |
Number of variables per image, max. |
50 |
Number of variables in message text, max. |
8 |
Operating/fault messages |
Operating messages |
Yes |
Number of entries in operational log, max. |
128; not retentive |
Operating messages, max. |
2000; total number of operation and fault messages |
Alarm messages |
Yes |
Number of fault message, max. |
2000; total number of operation and fault messages |
Number of entries in fault message buffer, max. |
128; not retentive |
Recipes |
Number of recipes, max. |
20 |
Data records per recipe, max. |
50; limited due to storage medium |
Entries per data record, max. |
60 |
Recipe data memory, max. |
32 kbyte; expandable using Compact Flash Card (CF-Card) |
Display |
Design of display |
STN, CCFL backlit, 5.7" blue mode (4 blue tones) |
Resolution (pixels) |
horizontal image resolution |
320 |
vertical image resolution |
240 |
Backlighting |
MTBF backlighting (at 20 °C) |
50000 h |
Control elements |
Keyboard fonts |
Number of operating cycles, keys |
1000000 |
Number of function keys |
10 |
Number of softkeys |
14 |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Load voltage L+ |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Input current |
Current consumption, typ. |
350 mA; idling |
Current consumption, max. |
1 A |
Inrush current, max. |
2 A; for 70 ms |
Digital inputs |
from load voltage L+ (without load), max. |
70 mA |
Digital outputs |
from load voltage L+, max. |
20 mA; per group |
Power loss |
Power loss, typ. |
14 W |
Memory |
Micro Memory Card |
Yes |
Compact Flash Card |
Yes; Optional |
Work memory |
integrated |
64 kbyte |
expandable |
No |
Load memory |
Plug-in (MMC) |
Yes |
Plug-in (MMC), max. |
8 Mbyte |
Backup |
present |
Yes; Guaranteed by MMC (maintenance-free) |
CPU processing times |
for bit operations, typ. |
0.1 µs |
for word operations, typ. |
0.2 µs |
for fixed point arithmetic, typ. |
2 µs |
for floating point arithmetic, typ. |
3 µs |
CPU-blocks |
DB |
Number, max. |
511; DB 0 reserved |
Size, max. |
16 kbyte |
FB |
Number, max. |
512; see instruction list |
Size, max. |
16 kbyte |
FC |
Number, max. |
512; see instruction list |
Size, max. |
16 kbyte |
OB |
Number, max. |
see instruction list |
Size, max. |
16 kbyte |
Nesting depth |
per priority class |
8 |
additional within an error OB |
4 |
Counters, timers and their retentivity |
S7 counter |
Number |
256 |
Retentivity |
adjustable |
Yes |
preset |
Z 0 to Z 7 |
Counting range |
lower limit |
0 |
upper limit |
999 |
IEC counter |
present |
Yes |
Type |
SFB |
Number |
Unlimited (limited only by RAM capacity) |
S7 times |
Number |
256 |
Retentivity |
adjustable |
Yes |
preset |
No retentivity |
Time range |
lower limit |
10 ms |
upper limit |
9990 s |
IEC timer |
present |
Yes |
Type |
SFB |
Number |
Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area in total (incl. times, counters, flags), max. |
all |
Flag |
Number, max. |
256 byte |
Retentivity available |
Yes |
Retentivity preset |
MB 0 to MB 15 |
Number of clock memories |
8; 1 memory byte |
Data blocks |
Number, max. |
511 |
Size, max. |
16 kbyte |
Local data |
per priority class, max. |
510 byte |
Address area |
I/O address area |
Inputs |
1 kbyte |
Outputs |
1 kbyte |
of which distributed |
Inputs |
1000 byte |
Outputs |
1000 byte |
Process image |
Inputs |
128 byte |
Outputs |
128 byte |
Default addresses of the integrated channels |
Digital inputs |
124.0 to 126.7 |
Digital outputs |
124.0 to 125.7 |
Analog inputs |
752 to 761 |
Analog outputs |
752 to 755 |
Digital channels |
Inputs |
8192 |
Outputs |
8192 |
Inputs, of which central |
922 |
Outputs, of which central |
922 |
Analog channels |
Inputs |
512 |
Outputs |
512 |
Inputs, of which central |
248 |
Outputs, of which central |
248 |
Hardware configuration |
Number of modules per system, max. |
23 |
Number of DP masters |
integrated |
1 |
via CP |
1 |
Number of operable FMs and CPs (recommended) |
FM |
8 |
CP, point-to-point |
8 |
CP, LAN |
10 |
Rack |
Racks, max. |
4 |
Modules per rack, max. |
4; 4 in subrack 0; 8 in subracks 1 and 2; 7 in subrack 3 |
Time of day |
Clock |
Hardware clock (real-time clock) |
Yes |
battery-backed and synchronizable |
Yes |
Deviation per day, max. |
10 s |
Backup time |
6 wk; At 40 °C ambient temperature |
Operating hours counter |
Number |
1 |
Number/Number range |
0 |
Range of values |
0 to 2^31 hours (when using SFC 101) |
Granularity |
1 hour |
retentive |
Yes; Must be restarted at each restart |
Clock synchronization |
supported |
Yes |
to MPI, master |
Yes |
to MPI, slave |
Yes |
in AS, master |
Yes |
Digital inputs |
Number of digital inputs |
24 |
of which inputs usable for technological functions |
16 |
integrated channels (DI) |
24 |
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Number of simultaneously controllable inputs |
horizontal installation |
up to 40 °C, max. |
12 |
vertical installation |
up to 40 °C, max. |
18 |
up to 50 °C, max. |
12 |
45° mounting position |
up to 45 °C, max. |
12 |
Input voltage |
Rated value, DC |
24 V |
for signal "0" |
-3 to +5 V |
for signal "1" |
15 to 30 V |
Input current |
for signal "1", typ. |
7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
parameterizable |
Yes; 0.1 / 0.5 / 3 / 15 ms |
Rated value |
3 ms |
for counter/technological functions |
at "0" to "1", max. |
8 µs |
Cable length |
Cable length, shielded, max. |
1000 m; 100 m for technological functions |
Cable length unshielded, max. |
600 m |
Technological functions |
shielded, max. |
50 m; at maximum count frequency |
unshielded, max. |
Unshielded cables are not permissible for technological functions |
Standard DI |
shielded, max. |
1000 m |
unshielded, max. |
600 m |
Digital outputs |
Number of digital outputs |
16 |
of which high-speed outputs |
4 |
integrated channels (DO) |
16 |
Short-circuit protection |
Yes; Clocked electronically |
Response threshold, typ. |
1 A |
Limitation of inductive shutdown voltage to |
L+ (-48 V) |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
Lamp load, max. |
5 W |
Load resistance range |
lower limit |
48 Ω |
upper limit |
4 kΩ |
Output voltage |
for signal "1", min. |
L+ (-0.8 V) |
Output current |
for signal "1" rated value |
0.5 A |
for signal "1" permissible range, min. |
5 mA |
for signal "1" permissible range, max. |
0.6 A |
for signal "1" minimum load current |
5 mA |
for signal "0" residual current, max. |
0.5 mA |
Parallel switching of 2 outputs |
for uprating |
No |
for redundant control of a load |
Yes |
Switching frequency |
with resistive load, max. |
100 Hz |
with inductive load, max. |
0.5 Hz |
on lamp load, max. |
100 Hz |
of the pulse outputs, with resistive load, max. |
2.5 kHz |
Total current of the outputs (per group) |
all mounting positions |
up to 40 °C, max. |
4 A |
up to 60 °C, max. |
2 A |
horizontal installation |
up to 40 °C, max. |
2 A |
vertical installation |
up to 40 °C, max. |
3 A |
up to 50 °C, max. |
2 A |
45° mounting position |
up to 45 °C, max. |
2 A |
Cable length |
Cable length, shielded, max. |
1000 m |
Cable length unshielded, max. |
600 m |
Analog inputs |
integrated channels (AI) |
4; and 1x PT100 |
Number of analog inputs |
4 |
Number of analog inputs for voltage/current measurement |
4 |
Number of analog inputs for resistance/resistance thermometer measurement |
1 |
Number of analog inputs for resistance measurement |
1 |
permissible input voltage for current input (destruction limit), max. |
2.5 V; continuous, max. 24 V momentarily |
permissible input voltage for voltage input (destruction limit), max. |
30 V; Permanent |
permissible input current for voltage input (destruction limit), max. |
0.5 mA; Permanent |
permissible input current for current input (destruction limit), max. |
50 mA; Permanent |
Technical unit for temperature measurement adjustable |
Yes; Degrees Celsius / degrees Fahrenheit / Kelvin |
Input ranges |
Voltage |
Yes |
Current |
Yes |
Resistance thermometer |
Yes |
Resistance |
Yes |
Input ranges (rated values), voltages |
0 to +10 V |
Yes |
Input resistance (0 to 10 V) |
100 kΩ |
-10 V to +10 V |
Yes |
Input resistance (-10 V to +10 V) |
100 kΩ |
Input ranges (rated values), currents |
0 to 20 mA |
Yes |
Input resistance (0 to 20 mA) |
50 kΩ |
-20 to +20 mA |
Yes |
Input resistance (-20 to +20 mA) |
50 kΩ |
4 to 20 mA |
Yes |
Input resistance (4 to 20 mA) |
50 kΩ |
Input ranges (rated values), resistance thermometers |
Pt 100 |
Yes |
Input resistance (Pt 100) |
10 MΩ |
Input ranges (rated values), resistors |
No-load voltage, typ. |
2.5 V |
Measured current, typ. |
1.8 to 3.3 mA |
0 to 600 Ohm |
Yes |
Input resistance (0 to 600 Ohm) |
10 MΩ |
Thermocouple (TC) |
Temperature compensation |
parameterizable |
No |
Resistance thermometer (RTD) |
Characteristic linearization |
for resistance thermometer |
Pt 100 |
Characteristic linearization |
parameterizable |
Yes; by software |
Cable length |
Cable length, shielded, max. |
100 m |
Analog outputs |
integrated channels (AO) |
2 |
Number of analog outputs |
2 |
Voltage output, short-circuit protection |
Yes |
Voltage output, short-circuit current, max. |
55 mA |
Current output, no-load voltage, max. |
17 V |
Output ranges, voltage |
0 to 10 V |
Yes |
-10 to +10 V |
Yes |
Output ranges, current |
0 to 20 mA |
Yes |
-20 to +20 mA |
Yes |
4 to 20 mA |
Yes |
Connection of actuators |
for voltage output two-wire connection |
Yes; Without compensation of the line resistances |
for voltage output four-wire connection |
No |
for current output two-wire connection |
Yes |
Load impedance (in rated range of output) |
with voltage outputs, min. |
1 kΩ |
with voltage outputs, capacitive load, max. |
0.1 µF |
with current outputs, max. |
300 Ω |
with current outputs, inductive load, max. |
0.1 mH |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA |
16 V; Permanent |
Current, max. |
50 mA; Permanent |
Cable length |
Cable length, shielded, max. |
200 m |
Analog value generation |
Measurement principle |
Actual value encryption (successive approximation) |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. |
12 bit |
Integration time, parameterizable |
Yes; 2,5 / 16,6 / 20 ms |
permissible input frequency, max. |
400 Hz |
Conversion time (per channel) |
1 ms |
Time constant of the input filter |
0.38 ms |
Basic execution time of the module (all channels released) |
1 ms |
Settling time |
for resistive load |
0.6 ms |
for capacitive load |
1 ms |
for inductive load |
0.5 ms |
Encoder |
Connection of signal encoders |
for voltage measurement |
Yes |
for current measurement as 2-wire transducer |
Yes; with external supply |
for current measurement as 4-wire transducer |
Yes |
for resistance measurement with two-wire connection |
Yes; Without compensation of the line resistances |
for resistance measurement with three-wire connection |
No |
for resistance measurement with four-wire connection |
No |
Connectable encoders |
2-wire sensor |
Yes |
permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.06 % |
Temperature error (relative to input range), (+/-) |
0.0060 %/K |
Crosstalk between the inputs, min. |
50 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.06 % |
Linearity error (relative to output range), (+/-) |
0.15 % |
Temperature error (relative to output range), (+/-) |
0.01 %/K |
Crosstalk between the outputs, min. |
60 dB |
Operational error limit in overall temperature range |
Voltage, relative to input area, (+/-) |
1 % |
Current, relative to input area, (+/-) |
1 % |
Resistance, relative to input area, (+/-) |
5 % |
Voltage, relative to output area, (+/-) |
1 % |
Current, relative to output area, (+/-) |
1 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input area, (+/-) |
0.7 % |
Current, relative to input area, (+/-) |
0.7 % |
Resistance, relative to input area, (+/-) |
3 % |
Resistance thermometer, relative to input area, (+/-) |
3 % |
Voltage, relative to output area, (+/-) |
0.7 % |
Current, relative to output area, (+/-) |
0.7 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. |
30 dB |
Common mode interference, min. |
40 dB |
Interfaces |
Number of printer interfaces |
1; serial |
1. Interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
isolated |
No |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Functionality |
MPI |
Yes |
MPI |
Number of connections |
12 |
Transmission rate, max. |
187.5 kbit/s |
Services |
PG/OP communication |
Yes |
Routing |
Yes |
Global data communication |
Yes |
S7 basic communication |
Yes |
S7 communication |
Yes |
S7 communication, as client |
Yes; Via CP and loadable FB |
S7 communication, as server |
Yes |
2. Interface |
Interface type |
Integrated RS 485 interface |
Physics |
RS 485 |
isolated |
Yes |
Power supply to interface (15 to 30 V DC), max. |
200 mA |
Number of connection resources |
12 |
Functionality |
MPI |
No |
DP master |
Yes |
DP slave |
Yes |
DP master |
Number of connections, max. |
12 |
Number of connections (of which reserved), max. |
1 for PG, 1 for OP |
Transmission rate, max. |
12 Mbit/s |
Number of DP slaves, max. |
32 |
Services |
PG/OP communication |
Yes |
Routing |
Yes |
Global data communication |
No |
S7 basic communication |
No |
S7 communication |
No |
S7 communication, as client |
No |
S7 communication, as server |
No |
Equidistance mode support |
Yes |
SYNC/FREEZE |
Yes |
Activation/deactivation of DP slaves |
Yes |
Direct data exchange (slave-to-slave communication) |
Yes |
Address area |
Inputs, max. |
1 kbyte |
Outputs, max. |
1 kbyte |
User data per DP slave |
Inputs, max. |
244 byte |
Outputs, max. |
244 byte |
DP slave |
Number of connections |
12 |
Transmission rate, max. |
12 Mbit/s |
Address area, max. |
32 |
User data per address area, max. |
32 byte |
Services |
PG/OP communication |
Yes |
Routing |
Yes; Only with active interface |
Global data communication |
No |
S7 basic communication |
No |
S7 communication |
No |
Direct data exchange (slave-to-slave communication) |
Yes |
DPV1 |
No |
Transfer memory |
Inputs |
244 byte |
Outputs |
244 byte |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
supported |
Yes |
Number of GD packets, max. |
4 |
Number of GD packets, transmitter, max. |
4 |
Number of GD packets, receiver, max. |
4 |
Size of GD packets, max. |
22 byte |
Size of GD packet (of which consistent), max. |
22 byte |
S7 basic communication |
supported |
Yes |
User data per job, max. |
76 byte |
User data per job (of which consistent), max. |
76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
supported |
Yes |
as server |
Yes |
as client |
Yes; Via CP and loadable FB |
User data per job, max. |
180 kbyte; With PUT/GET |
User data per job (of which consistent), max. |
64 byte |
S5 compatible communication |
supported |
Yes; Via CP and loadable FB |
Number of connections |
overall |
12 |
usable for PG communication |
11 |
reserved for PG communication |
1 |
adjustable for PG communication, min. |
1 |
adjustable for PG communication, max. |
11 |
usable for OP communication |
11 |
reserved for OP communication |
1 |
adjustable for OP communication, min. |
1 |
adjustable for OP communication, max. |
11 |
usable for S7 basic communication |
8 |
reserved for S7 basic communication |
8 |
adjustable for S7 basic communication, min. |
0 |
adjustable for S7 basic communication, max. |
8 |
usable for routing |
4 |
Number of logical connections (also in network), max. |
4; 1 fixed with integral CPU |
S7 message functions |
Number of login stations for message functions, max. |
12; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages |
Yes |
simultaneously active Alarm-S blocks, max. |
40 |
Test commissioning functions |
Status block |
Yes |
Single step |
Yes |
Number of breakpoints |
2 |
Status/control |
Status/control variable |
Yes |
Variables |
Inputs, outputs, memory bits, DB, times, counters |
Number of variables, max. |
30 |
of which status variables, max. |
30 |
of which control variables, max. |
14 |
Forcing |
Forcing |
Yes |
Diagnostic buffer |
present |
Yes |
Number of entries, max. |
100 |
adjustable |
No |
Interrupts/diagnostics/status information |
Alarms |
Alarms |
Yes |
Integrated Functions |
Number of counters |
4 |
Counting frequency (counter) max. |
60 kHz |
Frequency measurement |
Yes |
Number of frequency meters |
Frequency meter up to max. 60 kHz |
controlled positioning |
Yes |
integrated function blocks (closed-loop control) |
Yes; PID controller |
PID controller |
Yes |
Number of pulse outputs |
4; Pulse outputs up to 2.5 kHz |
Limit frequency (pulse) |
2.5 kHz |
Galvanic isolation |
Galvanic isolation digital inputs |
between the channels |
No |
between the channels, in groups of |
16 |
between the channels and the backplane bus |
Yes |
Galvanic isolation digital outputs |
between the channels |
Yes |
between the channels, in groups of |
8 |
between the channels and the backplane bus |
Yes |
Galvanic isolation analog inputs |
Galvanic isolation analog inputs |
Yes; common for analog I/O |
between the channels |
No |
between the channels and the backplane bus |
Yes |
Galvanic isolation analog outputs |
Galvanic isolation analog outputs |
Yes; common for analog I/O |
between the channels |
No |
between the channels and the backplane bus |
Yes |
Permissible potential difference |
between different circuits |
75 VDC / 60 VAC |
between inputs and MANA (UCM) |
8 V DC |
between MANA and M internally (UISO) |
75 VDC / 60 VAC |
Isolation |
Isolation tested with |
500 V DC |
EMC |
Interference immunity against discharge of static electricity |
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 |
Yes; ±6 kV contact discharge acc. to IEC 61000-4-2, ESD; ±8 kV air discharge acc. to IEC 61000-4-2, ESD |
Interference immunity to cable-borne interference |
on the supply lines acc. to IEC 61000-4-4 |
Yes |
Interference immunity on signal cables acc. to IEC 61000-4-4 |
Yes; ±2 kV to IEC 61000-4-4, Burst |
Interference immunity against voltage surge |
on the supply lines acc. to IEC 61000-4-5 |
Yes; Surge measurements with additional protection elements: ±1 kV (to IEC 61000-4-5; µs pulse / line to line);±2 kV (to IEC 61000-4-5; µs pulse / line to ground) |
Interference immunity against high-frequency electromagnetic fields |
Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 |
Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 80 MHz to 1 GHz (to IEC 61000-4-3); 10 V/m, pulse-modulated 50% duty cycle at 900 MHz and 1.89 GHz (to IEC61000-4-3) |
Interference immunity against conducted variable disturbance induced by high-frequency fields |
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 |
Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 10 kHz to 80 MHz (acc. to IEC 61000-4-6) |
Emission of radio interference acc. to EN 55 011 |
Emission of radio interference acc. to EN 55 011 (limit class A) |
Yes |
Degree and class of protection |
IP20 |
Yes; Housing |
IP65 |
Yes; Front |
Standards, approvals, certificates |
CSA approval |
Yes |
UL approval |
Yes |
FM approval |
Yes |
Ambient conditions |
Environmental conditions |
Not suitable for open-air use |
Operating temperature |
45 degree installation, min. |
0 °C |
45 degree installation, max. |
45 °C |
horizontal installation, min. |
0 °C |
horizontal installation, max. |
40 °C |
vertical installation, min. |
0 °C |
vertical installation, max. |
50 °C |
Storage/transport temperature |
min. |
-20 °C |
max. |
70 °C |
Air pressure |
Operation, min. |
795 hPa |
Operation, max. |
1080 hPa |
Storage/transport, min. |
660 hPa |
Storage/transport, max. |
1080 hPa |
Relative humidity |
Operation, min. |
5 % |
Operation, max. |
95 % |
Storage/transport, min. |
5 % |
Storage/transport, max. |
95 % |
Vibrations |
Operation, tested according to IEC 60068-2-6 |
Yes; 10 to 58 Hz: Amplitude 0.075 mm; 58 to 150 Hz: Acceleration 9.8 m/s2 |
Transport, tested acc. to IEC 60068-2-6 |
Yes; 5 to 9 Hz: amplitude 3.5 mm; 9 to 500 Hz: acceleration 9.8 m/s (storage/transport in the packaging) |
Shock test |
tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Shock testing |
Operation, tested according to IEC 60068-2-29 |
Yes; Half-sine: 150 m/s2 (15 g), 11 ms, 18 shocks |
Storage/transport, tested acc. to IEC 60068-2-29 |
Yes; 250 m/s2 (25 g), 6 ms, 1000 shocks |
Fire resistance |
Terminal strips |
FV2 (tested to IEC 60707) |
Basic strips in housing |
FV0 |
Configuration |
Configuration software |
STEP 7 |
Yes; V5.1 SP3, STEP 7 Lite |
ProTool |
Yes; or SIMATIC ProTool/Pro Configuration, Version 6.0 SP1 or higher |
ProTool/Lite |
Yes |
ProTool/Pro |
Yes; Configuration also with WinCC flexible |
WinCC flexible Compact |
Yes |
WinCC flexible Standard |
Yes |
WinCC flexible Advanced |
Yes |
Programming |
Command set |
see instruction list |
Nesting levels |
8 |
System functions (SFC) |
see instruction list |
System function blocks (SFB) |
see instruction list |
Programming language |
LAD |
Yes |
FBD |
Yes |
STL |
Yes |
SCL |
Yes |
CFC |
Yes |
GRAPH |
Yes |
HiGraph® |
Yes |
Know-how protection |
User program protection/password protection |
Yes |
Languages |
Online languages |
Number of online/runtime languages |
3 |
Dimensions |
Width |
260 mm |
Height |
274 mm |
Depth |
80 mm |
Mounting cutout/device depth (W x H x D) |
|
Mounting cutout, width |
231 mm |
Mounting cutout, height |
257 mm |
Weights |
Weight, approx. |
1500 g |
Status |
Jul 7, 2014 |