![](/image/data/SIEMENS_Original/6ES7/633/6ES7633-2BF02-0AE3/6ES76332BF020AE3.jpg) |
SIMATIC C7-633 DP, COMP.STATION WITH INTEGRATED COMPONENTS: S7-300 CPU 315-2DP, SIMATIC OP7 AND IM 360, WITH INTEGRATED PROFIBUS DP INTERFACE |
Operator control and monitoring |
Password protection |
Yes |
Password levels |
9 |
Graphics object |
● Character graphics |
Yes; As part of the character set |
Process images |
● Number of process images |
99 |
● Number of variables in message text, max. |
8 |
● Entries per process image |
99 |
Operating/fault messages |
● Number of lines |
4 |
● Number of characters per line |
20 |
● Character size |
8 mm |
● Number of entries in operational log, max. |
256 |
● Operating messages, max. |
499 |
● Scroll operating messages, max. |
256 |
● Alarm messages |
Yes |
● Number of fault message, max. |
499 |
● Number of entries in fault message buffer, max. |
256 |
● Number of symbol/character sets |
1 |
Recipes |
● Number of recipes, max. |
99 |
● Data records per recipe, max. |
99 |
● Entries per data record, max. |
99 |
● Recipe data memory, max. |
4 kbyte |
Display |
Design of display |
LCD backlit |
dynamic objects |
Input, output, input/output fields, date/time fields, symbolic input/output fields |
Backlighting |
● MTBF backlighting (at 20 °C) |
100 000 h; about 11 years |
Control elements |
Keyboard fonts |
● Number of function keys |
16 |
● Number of softkeys |
4 |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
30.2 V |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
Current consumption, typ. |
550 mA |
Current consumption, max. |
1 A |
Power loss |
Power loss, typ. |
12 W |
Memory |
Work memory |
● integrated |
64 kbyte; 20 K instructions RAM |
Load memory |
● expandable FEPROM |
Yes |
● expandable FEPROM, max. |
512 kbyte |
● integrated RAM, max. |
96 kbyte |
Backup |
● present |
Yes |
● with battery |
Yes; all data |
● without battery |
Yes; 4736 Byte: parameterizable for memory bits, times, counters, data |
CPU processing times |
for bit operations, typ. |
0.3 µs |
for bit operations, max. |
0.6 µs |
for word operations, typ. |
1 µs |
for fixed point arithmetic, typ. |
2 µs |
for floating point arithmetic, typ. |
50 µs |
for timer/counter operations, typ. |
12 µs |
CPU-blocks |
DB |
● Number, max. |
255; DB 0 reserved |
FB |
● Number, max. |
192; see instruction list |
FC |
● Number, max. |
192; see instruction list |
OB |
● Number, max. |
see instruction list |
● Number of free cycle OBs |
1; OB 1 |
● Number of time alarm OBs |
1; OB 10 |
● Number of time interrupt OBs |
1; OB 35 |
● Number of process alarm OBs |
1; OB 40 |
● Number of startup OBs |
1; OB 100 |
● Number of asynchronous error OBs |
8; OB 80, 81, 82, 85, 86, 87, 121, 122 |
Nesting depth |
● per priority class |
8 |
Counters, timers and their retentivity |
S7 counter |
● Number |
64 |
of which retentive with battery |
— adjustable |
Yes |
— lower limit |
0 |
— upper limit |
63 |
of which retentive without battery |
— adjustable |
Yes |
— lower limit |
0 |
— upper limit |
63 |
Counting range |
— lower limit |
0 |
— upper limit |
999 |
S7 times |
● Number |
128 |
of which retentive with battery |
— adjustable |
Yes |
— lower limit |
0 |
— upper limit |
127 |
of which retentive without battery |
— adjustable |
Yes |
— lower limit |
0 |
— upper limit |
127 |
Time range |
— lower limit |
10 ms |
— upper limit |
9 990 s |
Data areas and their retentivity |
Flag |
● Number, max. |
256 byte |
● Retentivity available |
Yes |
● of which retentive with battery |
0 to 2047 |
● of which retentive without battery |
0 to 2047 |
Address area |
I/O address area |
● Inputs |
1 kbyte |
● Outputs |
1 kbyte |
Process image |
● Inputs |
128 byte |
● Outputs |
128 byte |
Hardware configuration |
Number of modules per system, max. |
8 |
Number of modules per DP slave interface, max. |
32; 122 byte address space per DP station |
connectable programming devices/PCs |
SIMATIC PG/PC, standard PC |
Interface modules |
● Interface module IM 360 integrated |
Yes |
Number of DP masters |
● integrated |
1 |
● via CP |
1; CP 342-5 |
Number of operable FMs and CPs (recommended) |
● FM |
8 |
● CP, point-to-point |
4 |
● CP, LAN |
2 |
Expansion modules |
● Number of expansion modules, max. |
24 |
● Analog inputs/outputs, max. |
192 |
● Digital inputs/outputs, max. |
768 |
Rack |
● Modules per rack, max. |
8 |
● Rack, number of rows, max. |
3 |
Time of day |
Clock |
● Hardware clock (real-time clock) |
Yes; CPU |
● Software clock |
Yes; OP |
Interfaces |
Number of printer interfaces |
1; RS 232 |
MPI |
● Cable length, max. |
9 100 m; without repeaters 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with star hubs or OLMs) |
1. Interface |
Functionality |
● MPI |
Yes; occupies 2 nodes per device (1 x CPU, 1 x OP) |
● DP master |
Yes |
● DP slave |
Yes |
MPI |
● Number of nodes, max. |
32; PG/PC, OP, C7, S7-300/400, M7 |
● Transmission rate, max. |
187.5 kbit/s |
DP master |
● Transmission rate, max. |
12 Mbit/s |
● Number of DP slaves, max. |
64 |
User data per DP slave |
— User data per DP slave, max. |
122 byte |
2. Interface |
Functionality |
● DP master |
Yes |
● DP slave |
Yes |
DP master |
● Transmission rate, max. |
12 Mbit/s |
● Number of DP slaves, max. |
64 |
User data per DP slave |
— User data per DP slave, max. |
122 byte |
Communication functions |
PG/OP communication |
Yes |
Global data communication |
● supported |
Yes |
S7 basic communication |
● supported |
Yes |
S7 communication |
● S7 extended communication |
Yes; Server |
S5 compatible communication |
● supported |
Yes |
Standard communication (FMS) |
● supported |
Yes |
Number of connections |
● overall |
|
— of which dynamic |
8 |
— of which static |
4 |
Isolation |
Isolation tested with |
500 V DC |
EMC |
Interference immunity |
Noise immunity: IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4, IEC 1000-4-6, EN 50140 |
Emission of radio interference acc. to EN 55 022 |
● Interference emission acc. to EN 55022, class A |
Yes; Noise emission: Class A / EN 55022; conducted interference: IEC 1000-4-4, IEC 1000-4-5 |
Degree and class of protection |
IP20 |
Yes; Housing |
IP65 |
Yes; Front |
Standards, approvals, certificates |
DIN/ISO 9001 |
Yes |
CSA approval |
Yes; to Standard C22.2 number 142 |
UL approval |
Yes; UL 508 |
FM approval |
Yes; FM-Standards No. 3611, 3600, 3810 Class I, Division 2, Group A, B, C, D |
developed in accordance with IEC 61131 |
Yes; EN 61131-2 (IEC 1131-2) |
Ambient conditions |
Operating temperature |
● 45 degree installation, min. |
0 °C |
● 45 degree installation, max. |
45 °C |
● vertical installation, min. |
0 °C |
● vertical installation, max. |
50 °C |
Air pressure |
● permissible range, min. |
795 hPa |
● permissible range, max. |
1 080 hPa |
Relative humidity |
● Operation, min. |
5 % |
● Operation, max. |
95 %; no condensation |
Vibrations |
● Operation, tested according to IEC 60068-2-6 |
Yes; IEC 68, Part 2-6; 10 to 58 Hz; (constant amplitude 0.075 mm); 58 to 500 Hz; (constant acceleration 9.8 m/s2) |
Shock test |
● tested according to IEC 60068-2-29 |
Yes; IEC 68, Part 2-29 half-sine: 100 m/s2 (10 g), 16 ms, 100 shocks |
Configuration |
Configuration software |
● STEP 7 |
Yes |
● STEP 7 Lite |
Yes |
● ProTool |
Yes |
● ProTool/Lite |
Yes |
● ProTool/Pro |
Yes |
Programming |
● Command set |
see instruction list |
● Nesting levels |
8 |
● Program organization |
Linear, structured |
● System functions (SFC) |
see instruction list |
Programming language |
— LAD |
Yes |
— FBD |
Yes |
— STL |
Yes |
— SCL |
Yes |
— CFC |
Yes |
— GRAPH |
Yes |
— HiGraph® |
Yes |
Software libraries |
— Process diagnostics |
Yes; C7-CPU |
— Software controller |
Yes; 16 circles |
Know-how protection |
● User program protection/password protection |
Yes |
Cycle time monitoring |
● lower limit |
1 ms |
● upper limit |
6 000 ms |
● adjustable |
Yes |
● preset |
150 ms |
Languages |
Online languages |
● Number of online/runtime languages |
3 |
Dimensions |
Width |
240 mm |
Height |
203.5 mm |
Depth |
74.4 mm |
Mounting cutout/device depth (W x H x D) |
|
● Mounting cutout, width |
231 mm |
● Mounting cutout, height |
159 mm |
Weights |
Weight, approx. |
1 600 g |
last modified: |