![](/image/data/SIEMENS_Original/6ES7/422/6ES7422-1FH00-0AA0/6ES74221FH000AA0.jpg) |
|
Supply voltage |
Load voltage L1 |
● Rated value (AC) |
230 V; 120/230 V AC |
● permissible range, lower limit (AC) |
79 V |
● permissible range, upper limit (AC) |
264 V |
Input current |
from load voltage L+ (without load), max. |
1.5 mA |
from load voltage L1 (without load), max. |
6 mA |
from backplane bus 5 V DC, max. |
400 mA |
Power losses |
Power loss, max. |
16 W |
Digital outputs |
Number of digital outputs |
16 |
Switching capacity of the outputs |
● Lamp load, max. |
50 W |
Output voltage |
● for signal "1", min. |
L1 (-18.1 V) |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" permissible range for 0 to 60 °C, min. |
10 mA |
● for signal "0" residual current, max. |
2.6 mA |
Switching frequency |
● with resistive load, max. |
10 Hz |
● with inductive load, max. |
0.5 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 60 °C, max. |
2 A; 5 A with fan subassembly; per 4 adjacent outputs |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels, in groups of |
4 |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
1500 V AC |
Dimensions |
Width |
25 mm |
Height |
290 mm |
Depth |
210 mm |
Weights |
Weight, approx. |
800 g |
last modified: |