6ES7134-7SD00-0AB0 ET200ISP, EL-MOD., 4 AI TC

Product Code: 6ES7134-7SD00-0AB0

Availability: In Stock

Price: $341.82
  
 
Artikelnummer 6ES7134-7SD00-0AB0
SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI, TC, FOR CONNECTION OF THERMOELEMENS (VOLTAGE MEASUREMENT)
Input current
from supply voltage L+, max. 30 mA
Power loss
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 4
Cycle time (all channels) max. 320 ms; 66 ms basic conversion time x 4 channels with 60 Hz interference frequency suppression; 80 ms basic conversion time x 4 channels with 50 Hz interference frequency suppression
Technical unit for temperature measurement adjustable Yes
Input ranges
● Voltage Yes
● Current No
● Thermocouple Yes
● Resistance thermometer No
● Resistance No
Input ranges (rated values), voltages
● -80 mV to +80 mV Yes
● Input resistance (-80 mV to +80 mV) 1 000 kΩ
Input ranges (rated values), thermocouples
● Type B Yes
● Input resistance (Type B) 1 000 kΩ
● Type C Yes
● Input resistance (Type C) 1 000 kΩ
● Type E Yes
● Input resistance (Type E) 1 000 kΩ
● Type J Yes
● Input resistance (type J) 1 000 kΩ
● Type K Yes
● Input resistance (Type K) 1 000 kΩ
● Type L Yes
● Input resistance (Type L) 1 000 kΩ
● Type N Yes
● Input resistance (Type N) 1 000 kΩ
● Type R Yes
● Input resistance (Type R) 1 000 kΩ
● Type S Yes
● Input resistance (Type S) 1 000 kΩ
● Type T Yes
● Input resistance (Type T) 1 000 kΩ
● Type U Yes
● Input resistance (Type U) 1 000 kΩ
Thermocouple (TC)
Temperature compensation
— internal temperature compensation Yes; via supplied TC sensor module
— external temperature compensation with compensations socket Yes; via temperature value, acquired by an analog module of the same ET 200iSP station
Characteristic linearization
● parameterizable Yes
— for thermocouples 1
Cable length
● Cable length, shielded, max. 50 m
Analog value generation
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Basic conversion time, including integration time, ms 80 ms at 50 Hz; 66 ms at 60 Hz
— additional conversion time for wire-break monitoring 5
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Smoothing of measured values
● parameterizable Yes; in 4 stages
● Step: None Yes; 1 x cycle time
● Step: low Yes; 4 x cycle time
● Step: Medium Yes; 32 x cycle time
● Step: High Yes; 64 x cycle time
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.015 %
Temperature error (relative to input range), (+/-) 0.02 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.01 %
Operational error limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.15 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● Common mode interference, min. 90 dB
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes; Parameterizable
● Limit value alarm Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog inputs
● between the channels Yes; Functional, yes
● between the channels and the backplane bus Yes
Standards, approvals, certificates
CE mark Yes
Highest safety class achievable in safety mode
● acc. to IEC 61508 none
● Performance level according to EN ISO 13849-1:2008 none
Use in hazardous areas
● Type of protection acc. to EN 50020 (CENELEC) II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
● Type of protection acc. to KEMA 04 ATEX 1246
Dimensions
Width 30 mm
Height 129 mm
Depth 136.5 mm
Weights
Weight, approx. 230 g
last modified: 31.07.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: