6ES7134-4MB02-0AB0 ET200S, EL-MOD., 2AI HF I, +/-20MA

Product Code: 6ES7134-4MB02-0AB0

Availability: In Stock

Price: $102.75
  
 
Artikelnummer 6ES7134-4MB02-0AB0
SIMATIC DP, ELECTRONIC MODULE 2 AI I HIGH FEATURE FOR ET 200S, 15 MM WIDE, CYCLE TIME PER MODULE: 0.5MS, +/-20MA; 15 BIT + SIGN, 4 .. 20MA; 15 BIT, OPERATIONAL LIMITS +/-0.1% WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 48 mA
from backplane bus 3.3 V DC, max. 10 mA
Output voltage
Power supply to the transmitters
● present Yes
● short-circuit proof Yes
Power losses
Power loss, typ. 1.2 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input current for current input (destruction limit), max. 50 mA
Cycle time (all channels) max. 0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression
Input ranges
● Voltage No
● Current Yes
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), currents
● -20 to +20 mA Yes
● 4 to 20 mA Yes
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Measurement principle Sigma Delta
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit; as required
● Integration time, parameterizable Yes
● Interference voltage suppression for interference frequency f1 in Hz 60 / 50 Hz / no
● Conversion time (per channel) 0.04 ms; Without noise suppression 17/20 ms per channel with error
Smoothing of measured values
● Parameterizable Yes; In 4 stages: 1 x, 4 x, 16 x, 32 x cycle time
● Step: None Yes; 1 x
● Step: low Yes; 4 x
● Step: Medium Yes; 16 x
● Step: High Yes; 32 x
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.03 %
Temperature error (relative to input range), (+/-) 0.003 %/K
Crosstalk between the inputs, min. -100 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.01 %
Operational limit in overall temperature range
● Current, relative to input area, (+/-) 0.1 %; 0.2% without interference frequency suppression
Basic error limit (operational limit at 25 °C)
● Current, relative to input area, (+/-) 0.05 %; 0.1% without interference frequency suppression
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 90 dB
● common mode voltage (USS < 2.5 V) , min. 100 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Alarms
● Hardware interrupt Yes
Diagnostic messages
● Diagnostic functions Yes
● Wire break Yes; Measuring range 4 to 20 mA only
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 12 bytes, 4 bytes in compatibility mode
Diagnosis: wire break Disable / enable
Measurement type/range deactivated / +/-20 mA / 4 to 20 mA
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No; however, increased permissible potential difference between the inputs.
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ Yes
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 45 g
last modified: 25.09.2014