6ES7134-4LB00-0AB0 ET200S, EL-MOD., 2AI HF U, +/-10V, 1..5V

Product Code: 6ES7134-4LB00-0AB0

Availability: In Stock

Price: $123.30
  
 
Artikelnummer 6ES7134-4LB00-0AB0
SIMATIC DP, ELECTRONIC MODULE 2 AI HIGH FEATURE U FOR ET 200S, 15 MM WIDE, +/-10V, 15 BI + SIGN, +/-5V,15BIT+SIGN, 1..5V, 15BIT, OPERATIONAL LIMITS +/-0.1% WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 53 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 0.85 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input voltage for voltage input (destruction limit), max. 35 V; 35 V continuous; 75 V for max. 1 ms
Cycle time (all channels) max. 1 channel active per module: 75 / 90 / 30 ms; 2 channels active per module: 175 / 210 / 78 ms
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 1 to 5 V Yes
● -10 V to +10 V Yes
● -5 V to +5 V Yes
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit; 1 to 5 V: 15 bits, +/-10 V: 16 bits, +/-5 V: 16 bits
● Integration time, parameterizable Yes
● Integration time, ms 16,67 / 20 / 7,5 ms
● Interference voltage suppression for interference frequency f1 in Hz 60 / 50 Hz / no
● Conversion time (per channel) 1 channel active per module: 25 / 30 / 10 ms; 2 channels active per module: 58.3 / 70 / 26 ms
Smoothing of measured values
● Parameterizable Yes; In four stages by means of digital filtering
● Step: None Yes; 1 x cycle time
● Step: low Yes; 4 x cycle time
● Step: Medium Yes; 32 x cycle time
● Step: High Yes; 64 x cycle time
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.03 %
Temperature error (relative to input range), (+/-) 0.003 %/K; +/- 0.003%: Calibration enabled; +/- 0.015%: Calibration disabled
Crosstalk between the inputs, min. -100 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.01 %
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.1 %; +/- 0,1 %: Calibration enabled; +/0.5%; calibration disabled
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 90 dB
● common mode voltage (USS < 2.5 V) , min. 100 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic functions Yes; can be read out (wire break diagnostics is not supported by this module.)
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 4 byte
Diagnosis: wire break Disable / enable
Measurement type/range deactivated / +/-5 V / 1 to 5 V / +/-10 V
Interference frequency suppression Disable / enable
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ Yes
Permissible potential difference
between the inputs (UCM) 140V DC/100V AC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g