6ES7134-4NB01-0AB0 ET200S, EL-MOD., 2AI TC HF, 15BIT

Product Code: 6ES7134-4NB01-0AB0

Availability: In Stock

Price: $95.90
  
 
Artikelnummer 6ES7134-4NB01-0AB0
SIMATIC DP, ELECTRONIC MODULE F. ET200S, 2 AI TC HIGH FEATURE 15 MM WIDE, 15 BIT + SIGN WITH INTERNAL TEMERATURE COMPENSATION
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 30 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 0.6 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input voltage for voltage input (destruction limit), max. 20 V; +/-20 V, continuous
Cycle time (all channels) max. Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustable Yes
Input ranges
● Voltage Yes
● Current No
● Thermocouple Yes
● Resistance thermometer No
● Resistance No
Input ranges (rated values), voltages
● -80 mV to +80 mV Yes
● Input resistance (-80 mV to +80 mV) 1 MΩ
Input ranges (rated values), thermoelements
● Type B Yes
● Input resistance (Type B) 1 MΩ
● Type C Yes
● Input resistance (Type C) 1 MΩ
● Type E Yes
● Input resistance (Type E) 1 MΩ
● Type J Yes
● Input resistance (type J) 1 MΩ
● Type K Yes
● Input resistance (Type K) 1 MΩ
● Type L Yes
● Input resistance (Type L) 1 MΩ
● Type N Yes
● Input resistance (Type N) 1 MΩ
● Type R Yes
● Input resistance (Type R) 1 MΩ
● Type S Yes
● Input resistance (Type S) 1 MΩ
● Type T Yes
● Input resistance (Type T) 1 MΩ
Thermocouple (TC)
Temperature compensation
— internal temperature compensation Yes; possible with TM-E15S24-AT, TM-E15C24-AT
— external temperature compensation with compensations socket Yes; one external compensating box per channel
Characteristic linearization
● Parameterizable Yes
— for thermocouples Type B, C, E, J, K, L, N, R, S, T to IEC 584
Cable length
● Cable length, shielded, max. 50 m
Analog value creation
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, ms 16,7 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz 60 / 50 Hz
● Conversion time (per channel) 66 ms; 66 / 80 ms; additional conversion time for diagnostic wire break test
Smoothing of measured values
● Parameterizable Yes; In four stages by means of digital filtering
● Step: None Yes; 1 x cycle time
● Step: low Yes; 4 x cycle time
● Step: Medium Yes; 32 x cycle time
● Step: High Yes; 64 x cycle time
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.05 %
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.1 %; +/-1.5 K for thermocouples, +/-7 K for thermocouples type C,+/-2.5 K with static thermal state (ambient temperature change < 0.3 K/min)
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.05 %; +/-1 K with thermocouples, +/-5 K with thermocouples type C, +/-1.5 K with static thermal state (ambient temperature change < 0.3 K/min)
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● common mode voltage (USS < 2.5 V) , min. 90 dB
Interrupts/diagnostics/status information
Diagnostic messages
● Wire break Yes; only thermocouples
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 4 byte
Diagnosis: wire break Disable / enable (wire break is detected only in thermocouples)
Measurement type/range Deactivated/ +/- 80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Comparison point none / yes, internal
Unit Celsius / Fahrenheit
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ Yes
Permissible potential difference
between inputs and MANA (UCM) 140V DC/100V AC
between MANA and M internally (UISO) 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
last modified: 08.09.2014