6ES7132-4HB50-0AB0 ET200S,2RO,DC48V/AC230V,MANUAL ACTUATION

Product Code: 6ES7132-4HB50-0AB0

Availability: In Stock

Price: $30.14
  
 
Relay module 2 RO NO/NC

-
SIMATIC DP, ELECTRON. MODULE ET200S: 2DO RELAY(FORM C CONT.) DC24V-48V/5A, AC24V-230V/5A, 15 MM WIDTH, FIRST-UP SIGNAL, WITH MANUAL ACTUATION
Supply voltage
Load voltage L+
Rated value (DC) 24 V; From power module
Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 30 mA
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, typ. 0.6 W
Address area
Address space per module
with packing 2 bit
without packing 1 byte
Digital outputs
Number of digital outputs 2
Short-circuit protection No
Limitation of inductive shutdown voltage to No
Controlling a digital input Yes
Output current
for signal "1" rated value 5 A
for signal "1" minimum load current 8 mA
Switching frequency
with resistive load, max. 2 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 2 Hz
Relay outputs
Switching capacity of contacts
Thermal continuous current, max. 5 A
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Isochronous mode
Isochronous mode (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Substitute values connectable Yes; 0/1
Diagnostic messages
Diagnostic functions No
Diagnostics indication LED
Status indicator digital output (green) Yes
Parameter
Behavior on CPU/master STOP, channel-wise Substitute a value/keep last value
Galvanic isolation
Galvanic isolation digital outputs
between the channels Yes
between the channels and the backplane bus Yes
between the channels and the load voltage L+ Yes
Isolation
tested with
Channels against backplane bus and load voltage L+ 1500 V AC
Load voltage L+ against backplane bus 500 V DC
Ambient conditions
Extended ambient conditions
relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation, maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 50 g
Status Jul 14, 2014