6ES7132-7GD00-0AB0 ET200ISP, EL-MOD., 4DO, DC 23,1V, 20MA

Product Code: 6ES7132-7GD00-0AB0

Availability: In Stock

Price: $184.27
  
 
Digital input module 4DQ DC 23.1V

-
SIMATIC DP, ELECT. SUBMODULE FOR ET 200ISP, 4 DO, DC 23,1V/20MA, "L"-SHUT DOWN
Input current
from load voltage L+ (without load), max. 340 mA; with actuator supply
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 2.5 W
Address area
Address space per module
without packing 2 byte
Digital outputs
Number of digital outputs 4; additionally 1 intrinsically-safe input for L shutdown
Short-circuit protection Yes
No-load voltage Uao (DC) 23.1 V
Trend key points E
Voltage Ue (DC) 17.1 V
Current Ie 20 mA
Output current
for signal "1" rated value 0.02 A
Output delay with resistive load
"0" to "1", max. 2 ms
"1" to "0", max. 1.5 ms
Parallel switching of 2 outputs
for increased power No; for Ex reasons not possible; nor for predecessor
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 2 Hz
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 500 m
Interrupts/diagnostics/status information
Status indicator Yes
Alarms
Diagnostic alarm Yes; Parameterizable
Diagnostic messages
Diagnostic functions Yes
Diagnostic information readable Yes
Wire break Yes; R > 10 kohms, I < 100 µA
Short circuit Yes; R< 80 Ohm (one output), R< 40 Ohm (outputs connected in parallel)
Diagnostics indication LED
Group error SF (red) Yes
Status indicator digital output (green) Yes
Parameter
Remark 14 byte
Diagnosis: wire break Yes
Diagnosis: short circuit Yes
Behavior on CPU/Master STOP, channel-wise Substitute a value/keep last value
Ex(i) characteristics
Max. values of output circuits (per channel)
Ta (permissible ambient temperature), max. 70 °C
Galvanic isolation
Galvanic isolation digital outputs
between the channels No
between the channels and the backplane bus Yes
between the channels and the load voltage L+ Yes
Standards, approvals, certificates
CE mark Yes
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC) II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
Type of protection acc. to KEMA 04 ATEX 1249
Dimensions
Width 30 mm
Height 129 mm
Depth 136.5 mm
Weights
Weight, approx. 255 g
Status Jun 16, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: