6ES7131-0BL00-0XB0 ET200B, EL-MOD., 32DI, DC 24V, 3MS

Product Code: 6ES7131-0BL00-0XB0

Availability: In Stock

Price: $370.59
  
 

SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 32DI 24V DC, 3MS INPUT DELAY
Supply voltage
24 V DC Yes; L5+; value at t < 0.5 s: 35 V
permissible range, lower limit (DC) 18.5 V
permissible range, upper limit (DC) 30.2 V
Input current
Current consumption, typ. 70 mA; From L5+; logic
Current consumption, max. 1000 mA; from L5+; sensor
I²t 0.05 A²·s; with starting current inrush
Encoder supply
Output voltage 18.5 to 30 V
Output current
Output current, rated value 1 A
Power losses
Power loss, typ. 4.8 W
Hardware configuration
Rack
Required terminal block TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC
Digital inputs
Number of digital inputs 32
Input voltage
Rated value, DC 24 V
for signal "0" -30 to +5 V
for signal "1" 13 to 30 V
Input current
for signal "1", typ. 4 mA; At 24 V min. 2 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", max. 3 ms
Cable length
Cable length unshielded, max. 100 m
Encoder
Connectable encoders
2-wire sensor Yes
Permissible quiescent current (2-wire sensor), max. 1.5 mA
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s
FREEZE capability Yes
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Diagnostics indication LED
Bus fault BF (red) Yes
Run mode RUN (green) Yes
Status indicator digital input (green) Yes
Galvanic isolation
between electronic block and PROFIBUS DP Yes
Galvanic isolation digital inputs
Galvanic isolation digital inputs No
Degree and class of protection
IP20 Yes
Ambient conditions
Operating temperature
horizontal installation, min. 0 °C
horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 15 %
max. relative humidity 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width 235 mm; EB and TB
Height 130 mm; EB and TB
Depth 60 mm; EB and TB
Weights
Weight, approx. 800 g; EB and TB
Status Jun 6, 2014