6ES7332-5HF00-0AB0 SIMATIC S7-300, ANALOG OUTPUT

Product Code: 6ES7332-5HF00-0AB0

Availability: In Stock

Price: $587.05
  
 
Artikelnummer 6ES7332-5HF00-0AB0
SIMATIC S7-300, ANALOG OUTPUT SM 332, OPTICALLY ISOLATED, 8 AO, U/I; DIAGNOSTICS; RESOLUTION 11/12 BITS, 40 PIN, REMOVE/INSERT W. ACTIVE, BACKPLANE BUS
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 340 mA
from backplane bus 5 V DC, max. 100 mA
Power losses
Power loss, typ. 6 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
● 0 to 10 V Yes
● 1 to 5 V Yes
● -10 to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 to +20 mA Yes
● 4 to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 10 mH
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit; +/-10 V, +/-20 mA, 4 to 20 mA, 1 to 5 V: 11 bits + sign; 0 to 10 V, 0 to 20 mA: 12 bits
● Conversion time (per channel) 0.8 ms
Settling time
● for resistive load 0.2 ms
● for capacitive load 3.3 ms
● for inductive load 0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH)
Errors/accuracies
Operational limit in overall temperature range
● Voltage, relative to output area, (+/-) 0.5 %
● Current, relative to output area, (+/-) 0.6 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output area, (+/-) 0.4 %
● Current, relative to output area, (+/-) 0.5 %
Interrupts/diagnostics/status information
Substitute values connectable Yes; Parameterizable
Alarms
● Diagnostic alarm Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable Yes
● Diagnostics Yes
Diagnostics indication LED
● Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog outputs
● between the channels and the backplane bus Yes
Isolation
Isolation checked with 500 V DC
Connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 272 g
last modified: 25.09.2014